NM Boiler Operator study materials
NM Boiler Operator study resources

NM Boiler Operator flashcards

NM Boiler Operator · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

ASME Section I
Covers power boilers and high-temperature water boilers operated above 15 psig steam pressure; it sets construction, material, welding, inspection, and stamping requirements.
ASME Section IV
Covers heating boilers limited to 15 psig steam or 160 psig and 250°F water; rules address construction, relief valves, and installation.
S stamp
ASME Code symbol stamped on a power boiler built to Section I; the Manufacturer's Data Report documents design, materials, and tests.
H stamp
ASME Code symbol for a heating boiler built to Section IV; it signifies compliance with heating-boiler construction and inspection rules.
MAWP
Maximum allowable working pressure marked on a boiler; the lowest-rated pressure part or component establishes the limit for operation and safety-valve setting.
Hydrostatic test
Pressure test using water, commonly 1.5 times MAWP for new ASME power boilers; it checks strength and tightness before service.
NBIC R stamp
Symbol used by qualified repair organizations for repairs or alterations to ASME-stamped boilers and pressure vessels under the National Board Inspection Code.
Boiler horsepower
Heat rate equal to 33,475 Btu per hour, roughly 34.5 pounds of steam per hour evaporated from and at 212°F.
Latent heat
Heat absorbed or released during a phase change at constant temperature; for saturated steam it decreases as pressure rises and is zero at the critical point.
Pre-purge
Controlled airflow through the furnace and flue before ignition to remove combustible gases; typically four to eight furnace volume changes.
Low-water trip
Safety action that stops fuel firing when water level falls below the safe limit; water must not be added to an overheated boiler until it cools.
Normal boiler shutdown
Reduce firing, stop the burner, keep feedwater available, and allow controlled cooldown; do not drain a hot boiler until pressure and temperature are safe.
Saturated steam
Steam at the boiling-point temperature for its pressure, containing no superheat; its temperature and pressure are fixed together in the saturated state.
Stoichiometric air
Minimum air theoretically needed for complete combustion; natural gas requires about 9.5 to 10 cubic feet of air per cubic foot of gas.
Excess air
Air supplied beyond stoichiometric requirements; typical values are 5 to 10 percent for gas, 10 to 15 percent for oil, and 15 to 25 percent for coal.
Flame safeguard
Control system that proves pilot or main flame and closes fuel valves within a set time if flame is lost, preventing fuel accumulation in the furnace.
Forced draft
Combustion-air fan located upstream of the burner that pushes air into the furnace; it must overcome burner and furnace resistance.
Induced draft
Fan downstream of the boiler that pulls flue gas through the unit and maintains negative furnace pressure; it handles hot, dirty gas.
Burner turndown
Ratio of maximum firing rate to minimum stable firing rate; excess air, flame stability, and emissions limit the achievable turndown.
Deaerator
Feedwater heater that removes dissolved oxygen and other gases by heating water and venting the gases; it reduces corrosion pitting in the boiler.
Oxygen scavenger
Chemical such as sodium sulfite or hydrazine added to feedwater to remove residual dissolved oxygen after deaeration and protect metal surfaces.
Scale
Deposit mainly of calcium and magnesium salts on waterside surfaces; it insulates metal, reduces heat transfer, and can overheat tubes.
Continuous blowdown
Controlled blowdown from the boiler water surface to limit dissolved solids and foam; rate is set from feedwater and boiler-water TDS limits.
Bottom blowdown
Short, controlled blowdown from the lowest point to remove sludge and sediment; two valves in series are used for safety.
Water hammer
Pressure surge caused by steam condensing or fast valve closure; condensate drains and traps prevent it in steam lines.
Softener
Ion-exchange unit that replaces calcium and magnesium hardness with sodium; it prevents scale but does not remove dissolved solids.
Low-water fuel cutoff
Required safety device that senses low water and stops fuel firing; its chamber and linkages must be kept clean and tested.
Safety valve
Automatic pressure-relief device that opens at set pressure and closes after pressure drops; its capacity must equal or exceed boiler steam output.
Gauge glass
Water-level indicator connected to the boiler with upper and lower fittings; it must be kept clear and protected by shields.
Three-way gauge cock
Valve fitting that allows a pressure gauge to be isolated, vented to zero, or connected to the boiler through a siphon.
NM Mechanical Safety Bureau
New Mexico office that administers boiler and pressure-vessel safety, adopts ASME and NBIC codes, and issues inspection certificates.
Certificate to operate
Document issued after required inspection shows a boiler may be operated; it must be posted and kept current under New Mexico rules.