NM Journeyman Electrician study materials
NM Journeyman Electrician study resources

NM Journeyman Electrician flashcards

NM Journeyman Electrician · Build recall with a focused review session.

31 cards. Read the term and the definition here. The deck at the top of this page is optional.

NM Electrical Bureau authority
The Electrical Bureau of the New Mexico Regulation and Licensing Department licenses electricians and enforces the adopted electrical code; local authorities having jurisdiction may add amendments and permit requirements.
Journeyman electrician scope
A licensed journeyman may perform electrical installations while employed by or under the supervision of a licensed contractor or master; the license does not authorize independent contracting or bidding.
Master electrician role
A master electrician may contract for electrical work and serve as qualifying party for an electrical contractor; the master carries responsibility for code compliance of work performed under that license.
Qualifying party requirement
An electrical contractor license requires a designated qualifying party who holds the appropriate master or journeyman credential and who is responsible for the contractor's code-compliant work.
Experience documentation
Applicants must submit verifiable hours of practical experience under licensed supervision on forms accepted by the Bureau; falsified hours are grounds for denial or discipline.
Continuing education renewal
License renewal requires continuing education hours in categories set by the Bureau per renewal cycle; licensees should retain completion certificates because the Bureau audits compliance.
Permit and inspection rule
Most electrical installations require a permit before work begins and inspection before concealment; the authority having jurisdiction may require the licensed electrician's signature on the application.
Adopted code edition
New Mexico adopts an edition of the NEC statewide through the Construction Industries Commission; always confirm the edition and local amendments in effect for the project jurisdiction.
Unlicensed practice penalties
Contracting without a license, supervising beyond authority, or falsifying experience can result in fines, suspension, or revocation by the Electrical Bureau after disciplinary proceedings.
License lapse reinstatement
A lapsed license may be reinstated under Bureau rule with late fees and proof of continuing education; practicing on a lapsed license is unlicensed activity subject to discipline.
GFCI purpose
A ground-fault circuit interrupter detects small line-to-ground current imbalances and opens the circuit quickly to prevent electric shock to people.
AFCI purpose
An arc-fault circuit interrupter detects characteristic arcing signatures in branch circuit conductors and opens the circuit to reduce fire ignition risk.
GFCI dwelling locations
NEC 210.8 requires GFCI protection in dwelling bathrooms, garages, outdoors, kitchens, laundry areas, basements, and other listed locations for 125- to 250-volt receptacles.
AFCI dwelling circuits
NEC 210.12 requires arc-fault protection for most 120-volt, 15- and 20-ampere branch circuits supplying outlets in dwelling units, with limited exceptions.
Equipment grounding conductor
The equipment grounding conductor provides a low-impedance fault path back to the source so overcurrent devices open; its size follows NEC Table 250.122 based on device rating.
Bonding versus grounding
Bonding connects metallic parts to keep them at equal potential, while grounding connects the system to earth; bonding is what clears faults, not the earth connection alone.
Working clearance depth
NEC 110.26 requires working space in front of equipment based on voltage and condition; minimum depth is 3 feet and increases with voltage and exposed live parts.
Next-size-up rule
NEC 240.4(B) permits rounding up to the next standard overcurrent rating when conductor ampacity does not match a standard size, subject to strict conditions.
Lockout tagout
Before servicing equipment, isolate all energy sources, apply locks and tags, and verify the absence of voltage with a tested meter to prevent unexpected energization.
Arc-rated PPE selection
Arc-rated clothing and voltage-rated gloves are chosen from an incident-energy analysis or the hazard tables, matched to the task and equipment voltage.
Ground-fault protection equipment
GFPE for large services and feeders senses lower-level ground faults and opens the circuit to limit equipment damage; it is distinct from personnel GFCI protection.
Receptacle outlet defined
An outlet is any point on the wiring system where current is taken to supply utilization equipment; a receptacle is a specific type of outlet device.
Overcurrent device defined
An overcurrent device, such as a fuse or circuit breaker, automatically opens a circuit when current exceeds a safe value, protecting conductors from overheating.
Service disconnect location
The service disconnecting means must be installed at a readily accessible location nearest the point of entrance of service conductors, per NEC 230.70.
Bonding at service
At the service, the grounded conductor is bonded to the equipment grounding conductor and enclosure; downstream, neutral and ground must remain separate on the load side.
Temporary power safety
Temporary wiring must be protected from damage, supported properly, and supplied through GFCI protection for personnel on construction sites per NEC Article 590.
Voltage testing practice
Verify a voltage tester on a known live source before and after checking a circuit; a tester that fails either check cannot confirm the circuit is de-energized.
Conductor ampacity basis
Conductor ampacity comes from the applicable NEC tables, adjusted for ambient temperature and number of current-carrying conductors in a raceway or cable.
Class A GFCI threshold
A Class A GFCI trips at a ground-fault current of 4 to 6 milliamperes, a level intended to protect people from ventricular fibrillation risk.
Accessible and readily accessible
Accessible means reachable without climbing over or removing obstacles; readily accessible means reachable quickly without tools, stairs, ladders, or portable means.
Arc flash boundary
The arc flash boundary is the distance at which incident energy equals 1.2 calories per square centimeter, the threshold for second-degree burn injury.