NEC Electrical Engineering flashcards
NEC Electrical Engineering · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Working space depth
- Minimum clear distance in front of electrical equipment per NEC 110.26(A): 3 ft for 0-150 V to ground, 3.5 ft for 151-300 V, 4 ft for 301-600 V, and 5 ft above 600 V.
- Dedicated equipment space
- Space reserved per NEC 110.26(E) from floor to 6 ft above equipment or structural ceiling, whichever is higher, kept clear of foreign piping and ducts not related to the equipment.
- Informational Note status
- NEC Informational Notes are explanatory only and are not enforceable code requirements; only mandatory text and referenced standards govern the installation.
- NM cable support interval
- Nonmetallic-sheathed cable must be secured within 12 in of boxes and supported at intervals not exceeding 4.5 ft per NEC 334.30.
- EMT fastening rule
- Electrical metallic tubing must be securely fastened within 3 ft of boxes and supported at intervals not exceeding 10 ft per NEC 358.30.
- Direct burial cover depth
- NEC 300.5 requires 24 in minimum cover for general direct-buried conductors, 18 in for residential GFCI branch circuits, and 12 in for 120 V landscape lighting.
- Dwelling receptacle spacing
- NEC 210.52(A) requires that no point along a dwelling wall floor line is more than 6 ft from a receptacle, and wall spaces 2 ft or wider need a receptacle.
- Small-appliance branch circuits
- NEC 210.11(C)(1) requires at least two 20 A small-appliance branch circuits to serve dwelling kitchen countertop receptacles.
- Dwelling optional calculation
- NEC 220.82 method: 100 percent of the first 10 kVA of general load plus 40 percent of the remainder, plus nameplate ratings of appliances and motors.
- Grounding electrode conductor sizing
- NEC 250.66 sizes the grounding electrode conductor using Table 250.66 based on the largest service-entrance conductor; no conductor smaller than 8 AWG copper is permitted.
- Equipment grounding conductor sizing
- NEC 250.122 sizes the equipment grounding conductor using Table 250.122 based on the rating of the overcurrent device protecting the circuit.
- Single rod 25 ohm rule
- NEC 250.53(A)(2) requires a supplemental electrode where a single rod, pipe, or plate electrode has a resistance to ground exceeding 25 ohms.
- Standard ampere ratings
- NEC 240.6(A) lists standard overcurrent device ratings including 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150, 200, 400, and 600 A.
- Next higher rating rule
- NEC 240.4(B) permits the next higher standard overcurrent device where conductor ampacity does not match a standard rating, subject to limits for 800 A and below.
- Series-rated systems
- NEC 240.86 requires listed and marked combinations of overcurrent devices for series ratings; the sum of ratings must not exceed the load-side device rating.
- Motor conductor sizing
- NEC 430.22 requires motor branch-circuit conductors to have ampacity of at least 125 percent of the motor full-load current from NEC tables.
- Motor overload protection
- NEC 430.32 sets overload protection at 115-125 percent of nameplate current for motors over 1 hp with service factor 1.15 or higher.
- Motor disconnect requirement
- NEC 430.102 requires a disconnecting means within sight of the motor and driven machinery, and 430.103 requires it to open all ungrounded conductors.
- Class I Division 1
- NEC Article 500 location where flammable gases or vapors are present under normal operating conditions or frequently during repair and maintenance.
- Zone classification system
- NEC Article 505 uses Zones 0, 1, and 2 for gases and Zones 20, 21, and 22 for dusts, with Zone 0 indicating continuous presence of flammable gas.
- Pool equipotential bonding
- NEC 680.26 requires bonding of pool shells, decks, metal parts, and associated equipment to an equipotential bonding grid to limit voltage gradients.
- Emergency system scope
- NEC Article 700 covers emergency systems for illumination and power required for safety during interruption of normal power, with a 90-minute minimum illumination requirement.
- Legally required standby
- NEC Article 701 covers legally required standby systems that supply power for systems required by law, distinct from emergency systems under Article 700.
- Class 2 circuit limits
- NEC Article 725 covers Class 2 remote-control and signaling circuits, which are limited in power and voltage and may use smaller conductors than Class 1 circuits.
- Limited approach boundary
- NFPA 70E distance from exposed energized conductors within which a shock hazard exists; for 120-750 V it is 10 ft for movable conductors and 3 ft 6 in for fixed parts.
- Restricted approach boundary
- NFPA 70E boundary within which only qualified persons with shock protection may enter; for 120-750 V it is 1 ft from exposed energized parts.
- AHJ authority
- NEC 90.4 gives the authority having jurisdiction responsibility for interpreting the code, granting approvals, and enforcing compliance with electrical installations.
- Continuous load factor
- NEC 210.19(A) requires branch-circuit conductors to have ampacity of at least the noncontinuous load plus 125 percent of the continuous load.
- GFCI dwelling locations
- NEC 210.8 requires GFCI protection in dwelling bathrooms, garages, outdoors, kitchens, laundry areas, and within 6 ft of sinks.
- AFCI protection
- NEC 210.12 requires arc-fault circuit-interrupter protection for dwelling branch circuits supplying most habitable rooms, including bedrooms and living areas.
- Supply-side bonding jumper
- NEC 250.102(C) sizes the supply-side bonding jumper using Table 250.102(C)(1) based on the largest ungrounded supply conductor.
- Fire pump feeder
- NEC 695.6 covers the dedicated fire pump feeder, which has specific overcurrent protection limits to ensure reliable operation during a fire.