Hydrokinetic vs hydrostatic panel
Hydrokinetic (architectural) panels shed water by gravity and need about 3:12 slope; hydrostatic (structural) panels resist water at the seam and can go to 1/4:12 with double-lock seams.
Standing seam seam height
Common heights are 1, 1-1/2, 2, and 2-3/8 inches. Taller seams stiffen the panel, increase span capacity, and resist water siphoning at low roof slopes.
Oil canning cause
Elastic buckling of the flat panel pan caused by residual coil stress, wide pan widths, uneven substrate, or overdriven fasteners. Narrower pans, striations, and backer plates reduce its visibility.
G90 galvanized coating
A hot-dip zinc coating designation meaning 0.90 ounces of zinc per square foot of sheet. It is the common corrosion baseline for steel roof panels in moderate environments.
OSHA low-slope fall trigger
Under 29 CFR 1926.501(b)(10), fall protection is required when work is within 15 feet of the roof edge. A warning line plus safety monitor is allowed only on roofs 50 feet wide or less.
Fall arrest anchorage strength
Anchorage must support 5,000 pounds per worker, or be designed by a qualified person with a safety factor of at least two. Maximum arresting force is limited to 1,800 pounds.
Steep roof fall protection
Roofs steeper than 4:12 require fall protection at all times under 1926.501(b)(11), regardless of the distance from the edge. Warning lines alone are not acceptable.
Ladder extension above landing
Extension ladders must extend at least 3 feet above the roof landing, be set at a 1:4 angle, and be secured against displacement before the worker ascends.
Purlin alignment tolerance
Purlins must be straight and aligned within about 1/4 inch over any 10-foot run. Misalignment causes clip racking, loose seams, and visible panel distortion.
Vapor retarder perm classes
Class I is 0.1 perm or less, Class II is 0.1 to 1.0 perm, and Class III is 1.0 to 10 perms. Class I or II is typical on the warm side in cold climates.
Eave ice dam membrane
IRC R905.1.2 requires a self-adhering membrane from the eave edge to 24 inches inside the exterior wall line where the average January temperature is 25 degrees F or lower.
Thermal break at purlin
A foam block or high-density polyiso strip placed between the purlin and panel. It interrupts the conductive bridge that can cut effective insulation R-value by 20 to 40 percent.
Panel coverage versus width
Coverage is the net width after seam engagement, always less than the flat sheet width. Order quantity equals roof area divided by coverage, times one plus waste.
Fastener penetration minimums
Fasteners must penetrate steel purlins at least 1/2 inch and wood at least 1 inch. Overdriving crushes the washer; underdriving leaves the head proud and leaks.
Thermal movement of panels
A 40-foot aluminum panel moves about 0.55 inch over a 100 degree F swing. Slotted clips and fixed-free end conditions accommodate this movement without buckling.
Uplift zone priority
ASCE 7 components-and-cladding pressures are highest at corners, then edges, then the field. Fastener and clip density increases from field to edge to corner.
Double-lock seam
A seam folded twice by a powered seamer, producing the strongest and most water-resistant standing seam. It is commonly required for hydrostatic panels at slopes near 1/4:12.
Seam sealant tape
A butyl or urethane tape placed in the seam pan before closing. It supplements, but never replaces, a fully closed seam, and must not be stretched or left exposed to UV.
Hose test for seams
A water test applying a hose stream at about 5 psi for at least 5 minutes, working from the low side up. It is used to verify new seams and flashings before closeout.
Counterflashing overlap
Counterflashing is embedded at least 1 inch into the wall and overlaps the base flashing by at least 4 inches. The two are not fastened together so thermal movement is free.
Curb height minimum
A roof curb for a skylight or large penetration is typically at least 8 inches above the roof surface, flashed with a minimum 4 to 6 inch overlap onto the panel.
Ridge cap fastening rule
Ridge and hip caps are fastened on one side only, over a profiled closure, with at least a 6 inch end lap. Fastening both sides locks thermal movement and buckles the cap.
Penetration size threshold
Holes larger than 12 inches in any dimension require a structural curb and framed opening. Smaller penetrations may use a manufactured boot or field flashing.
Vent area ratio
IRC R806 requires 1 square foot of net free vent area per 150 square feet of attic floor, or 1:300 when a vapor retarder is present, split equally between intake and exhaust.
Unvented hot roof strategy
Seal a Class I or II vapor retarder on the warm side, seal all joints, and place rigid insulation above the deck so the deck stays above the interior dew point.
Polyiso R-value per inch
Polyisocyanurate provides roughly R-6.0 to R-6.5 per inch, the highest of the common rigid foams, and is often foil-faced for use above a metal deck.
Minimum slope by panel type
Architectural hydrokinetic panels need about 3:12. Structural hydrostatic panels can be listed to 1/4:12 (2 percent) when double-lock seams and sealant are used.
Gutter slope and hangers
Gutters slope at least 1/16 inch per foot toward the outlet, with hangers spaced no more than 24 inches on center and an expansion joint on long runs.
Secondary drainage overflow
Where a parapet can pond water, an overflow scupper or secondary drain is set at least 2 inches above the primary drain and sized for the 100-year storm.
Backed-out fastener repair
A fastener backed out about 1/8 inch or more is replaced in a new hole, not simply retightened. Retightening enlarges the hole and the fastener will loosen again.
Metal-over-metal retrofit
A new panel installed over an existing metal roof with a slip sheet and often new battens or purlins. It avoids tear-off and adds insulation and a new finish warranty.
UL 580 uplift rating
UL 580 is the standard uplift test for roof assemblies. The listed assembly requires the exact panel, clip, fastener, and substrate combination named in the listing.