- NFPA 72
- National Fire Alarm and Signaling Code; covers design, installation, testing, inspection, and maintenance of fire alarm and signaling systems, and is adopted by reference through the NYC codes.
- NEC Article 760
- The National Electrical Code article governing fire alarm circuit wiring, including Class 1, Class 2, Class 3, and power-limited fire alarm circuits, conductor listing, and separation from power wiring.
- Authority having jurisdiction
- In New York City, the FDNY performs this role for fire alarm plan review, permits, and witnessed acceptance testing, enforcing the adopted Fire Code and its referenced standards.
- UL 864 listing
- The product standard for fire alarm control units; equipment must be listed for its intended use and installed in accordance with the manufacturer's published instructions and listing conditions.
- Protected premises system
- A local fire alarm system that sounds notification only within the protected building and does not transmit signals off premises to a supervising station.
- Central station system
- A supervising station listed to UL 827, staffed 24 hours a day, that receives alarm, supervisory, and trouble signals over two independent supervised communication paths.
- NYC high-rise definition
- A building having an occupied floor located more than 75 feet above the lowest level of fire department vehicle access, triggering voice evacuation and other high-rise features.
- Voice evacuation system
- An in-building emergency communications system delivering live or prerecorded voice messages; it requires intelligible speaker coverage and 24 hours standby plus 15 minutes of alarm secondary power.
- Smoke detector spacing
- On smooth ceilings, spot-type smoke detectors are spaced no more than 30 feet apart, with the last detector within 15 feet of walls or partitions and at least 4 inches from the wall.
- Heat detector spacing
- Baseline spacing of 50 feet with 25 feet to walls for a 10-foot ceiling; the listed spacing of the specific device governs and must be reduced as ceiling height increases.
- Duct smoke detector
- Required in supply ducts over 2,000 cfm and return ducts over 15,000 cfm; mounted per the airflow arrow, away from bends, and ahead of filters and branch takeoffs.
- Manual pull station placement
- Manual fire alarm boxes are mounted 42 to 48 inches above finished floor, within 5 feet of the exit door opening, and unobstructed along the normal path of egress.
- Waterflow alarm timing
- A sprinkler waterflow switch must cause alarm annunciation within 90 seconds of sustained flow; valve tamper switches on control valves report as supervisory signals instead.
- Audible alarm level
- Notification appliances must produce a sound level 15 dBA above the average ambient, or 5 dBA above ambient where ambient exceeds 105 dBA, measured in the occupied area.
- Sleeping area alarm level
- Alarms in sleeping areas must reach at least 75 dBA at the pillow and 15 dBA above ambient, and must use a 520 Hz low-frequency tone where required.
- Candela rating selection
- Visible appliance intensity is sized to room dimensions and ceiling height per NFPA 72 tables, for example about 15 cd for a 20 by 20 foot room with a 10-foot ceiling.
- Temporal-3 pattern
- The standard evacuation tone: three 0.5-second pulses separated by 0.5-second pauses, followed by a 1.5-second pause, then repeating continuously.
- Visible signal synchronization
- Visible notification appliances within the same field of view must flash in synchronization at a rate of 1 to 2 flashes per second to reduce seizure risk.
- Class B circuit
- A supervised two-wire circuit terminated with an end-of-line resistor; a single open fault causes a trouble and disables every device located beyond the break.
- Class A circuit
- A supervised circuit with a return path to the control unit; a single open or ground fault does not prevent any device on the circuit from operating.
- FPLR and FPLP cable
- Fire alarm cable listings under NEC Article 760: FPLR is listed for riser use, FPLP for plenum spaces, and FPL for general-purpose use in approved locations.
- Two-hour circuit survivability
- High-rise and partial-evacuation systems must protect alarm and voice circuits with 2-hour circuit integrity, using CI cable or a listed 2-hour rated enclosure.
- 24-hour standby requirement
- Protected premises secondary power must carry the system 24 hours in standby plus 5 minutes in alarm; voice evacuation systems require 24 hours plus 15 minutes of alarm.
- Battery sizing formula
- Capacity equals standby current times 24 hours plus alarm current times alarm duration, with the result multiplied by a derating factor such as 1.25 for battery aging.
- Battery capacity rating
- Sealed lead-acid battery capacities are published at the 20-hour discharge rate; sizing uses that rating and the manufacturer's derating data for temperature and end voltage.
- Dedicated AC circuit
- The fire alarm control unit branch circuit must be dedicated, unswitched, provided with a lockable disconnecting means, and marked "FIRE ALARM CIRCUIT CONTROL".
- Acceptance test scope
- Acceptance testing verifies 100 percent of initiating devices, notification appliances, and interface functions, plus primary power, secondary power, and simulated 24-hour standby operation.
- Elevator recall interface
- Smoke detectors in elevator lobbies, the machine room, and the hoistway initiate Phase I automatic recall; Phase II is keyed in-car operation used by firefighters.
- Record of Completion
- The NFPA 72 document prepared by the installing contractor at acceptance, describing the system, devices, and certifications, and delivered to the building owner.
- Smoke detector sensitivity test
- Detector sensitivity must be verified within one year of installation and at subsequent NFPA 72 intervals; detectors outside the listed range are cleaned, adjusted, or replaced.
- Impairment procedure
- Before taking a fire alarm system out of service, notify occupants and the FDNY, establish a fire watch, and record the impairment and its restoration in the log.
- ITM records retention
- Inspection, testing, and maintenance records are retained until the next scheduled test and must be made available to the authority having jurisdiction on request.