NY Water/Wastewater Operator flashcards
NY Water/Wastewater Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- CT value
- Product of disinfectant residual concentration in mg/L and baffled contact time in minutes. Used to demonstrate pathogen inactivation credit under the Surface Water Treatment Rule.
- Chlorine demand
- Difference between the chlorine dose applied and the residual remaining after contact. Demand must be satisfied before a measurable free residual persists.
- Turbidity limit
- Combined filter effluent must be at or below 0.3 NTU in 95% of monthly measurements and never exceed 1 NTU. Turbidity indicates filtration effectiveness and pathogen risk.
- Filter loading rate
- Flow in gallons per minute divided by filter surface area in square feet. Rapid sand filters typically operate at 2 to 4 gpm per square foot.
- Langelier Saturation Index
- A calculated value describing water's tendency to deposit or dissolve calcium carbonate. Positive is scale-forming, negative is corrosive, and near zero is balanced.
- Minimum distribution pressure
- New York requires at least 20 psi throughout the distribution system under all conditions, including main breaks. Lower pressure triggers boil-water notification.
- Main flushing velocity
- Flushing should reach at least 2.5 to 3 feet per second to scour sediment. Velocity equals flow in cubic feet per second divided by pipe area.
- BOD5 test
- Measures oxygen consumed by microorganisms over five days at 20 degrees Celsius. Typical domestic wastewater influent runs 200 to 250 mg/L BOD.
- F/M ratio
- Pounds of BOD applied per day divided by pounds of MLSS in the aeration tank. Conventional activated sludge operates around 0.2 to 0.4.
- Sludge age (MCRT)
- Pounds of MLSS in the aeration tank divided by pounds of solids leaving the system daily. Controls nitrification and settling characteristics in activated sludge.
- Sludge Volume Index
- Thirty-minute settled sludge volume in mL/L divided by MLSS in mg/L, multiplied by 1,000. Values of 80 to 150 indicate good settling.
- Clarifier hydraulic loading
- Flow in gallons per day divided by clarifier surface area in square feet. Overflow rate and solids loading rate must both be evaluated for adequate settling.
- Infiltration versus inflow
- Infiltration enters sewers through defects from groundwater; inflow enters through direct connections such as storm drains and sumps. Both add clear water to treatment.
- Sewer design velocity
- Collection systems target 2 to 10 feet per second. Lower velocities allow solids to settle; higher velocities cause abrasion and sulfide generation.
- Nitrification oxygen demand
- Oxidizing ammonia consumes 4.57 mg of oxygen per mg of ammonia nitrogen. Denitrification in anoxic zones returns alkalinity and reduces aeration demand.
- Effluent disinfection
- Chlorine dose and contact time must achieve fecal coliform limits in the SPDES permit. Dechlorination protects aquatic life in the receiving water.
- System classification
- New York categorizes public water systems by population and source type: community, non-transient non-community, and transient non-community systems.
- Total coliform rule
- No more than 5 percent of monthly samples may be positive for systems collecting 40 or more samples. Any E. coli positive requires repeat sampling and public notice.
- Lead action level
- The 90th percentile lead level must not exceed 0.015 mg/L. Exceedance requires corrosion control, source water treatment, or lead service line replacement.
- TTHM limit
- Stage 2 Disinfectants/Disinfection Byproducts Rule sets a locational running annual average limit of 0.080 mg/L for total trihalomethanes.
- HAA5 limit
- Locational running annual average limit of 0.060 mg/L for five haloacetic acids under the Stage 2 Disinfectants/Disinfection Byproducts Rule.
- Surface Water Treatment Rule
- Requires 99.9 percent Giardia and 99.99 percent virus removal or inactivation. Achieved through combined filtration and disinfection CT credits.
- Consumer Confidence Report
- Annual water quality report delivered to customers by July 1. Lists detected contaminants, source water, and health effects, with prior-year monitoring data.
- Public notification tiers
- Tier 1 requires notice within 24 hours for acute health risks. Tier 2 allows 30 days and Tier 3 allows annual notice for less urgent violations.
- Backflow prevention
- Air gaps, reduced pressure zone assemblies, and double check valves stop reverse flow. Containment is required at service connections under New York regulations.
- SPDES permit
- New York State Pollutant Discharge Elimination System permit. Sets enforceable effluent limits, monitoring frequency, and reporting deadlines for discharges to surface waters.
- Discharge Monitoring Report
- Monthly or permit-specified report of effluent monitoring results. Late or inaccurate reports are permit violations subject to enforcement and penalties.
- Confined space testing order
- Test oxygen first, then combustible gases, then toxic gases. Acceptable oxygen is 19.5 to 23.5 percent, and entry requires a permit and attendant.
- Hydrogen sulfide IDLH
- Immediately dangerous to life or health concentration is 100 ppm. Methane lower explosive limit is 5 percent in air, and carbon monoxide IDLH is 1,200 ppm.
- Chlorine gas detection
- Chlorine is heavier than air and pools at low points. Aqueous ammonia forms a white cloud at leaks. Entry requires SCBA and a standby person.
- Lockout/tagout
- Isolate all energy sources, verify zero energy, and apply locks and tags. Only the person who applied a lock may remove it.
- Chemical dose formula
- Pounds per day equals dose in mg/L times flow in MGD times 8.34. Used to set chlorine, alum, polymer, and fluoride feed rates.