OH Boiler Operator study materials
OH Boiler Operator study resources

OH Boiler Operator flashcards

OH Boiler Operator · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Firetube boiler
A boiler in which hot combustion gases pass through tubes surrounded by water; common for low- to medium-pressure heating and process steam.
Watertube boiler
A boiler in which water flows through tubes heated by combustion gases; used for high pressure and large steam capacity.
Safety valve
An automatic pressure-relief valve that opens at a set pressure to prevent overpressure; its capacity must equal or exceed the boiler's maximum steaming capacity.
Staybolt
A threaded rod tying two flat plates, such as tube sheets, together to support pressure loads; a broken or leaking staybolt is a structural defect.
Water column
A fitting connected to the boiler steam and water spaces that mounts the gauge glass, try cocks, and low-water cutoff to show true water level.
Maximum allowable working pressure
The highest pressure at which a boiler may operate, set by its weakest component and stamped on the nameplate; safety valves are set at or below this pressure.
Normal water level
The water level at the center of the gauge glass, keeping the crown sheet or tubes covered and providing steam space above.
Low-water fuel cutoff
A safety device that senses low water and automatically stops fuel firing before the boiler overheats; it must be tested regularly and never bypassed.
Bottom blowdown
Opening a valve at the lowest boiler point to discharge sludge and sediment; performed with short, frequent blows while the boiler is under normal load.
Carryover
Water droplets or foam carried with steam into the piping, caused by high dissolved solids, alkalinity, oil contamination, or sudden steam demand.
Water hammer
A banging shock in steam or water piping caused by trapped condensate or rapid valve movement; drain and trap lines before admitting steam.
Continuous blowdown
A controlled flow from the steam drum that removes dissolved solids and controls boiler water chemistry, adjusted from conductivity or TDS tests.
Stoichiometric air
The exact amount of air needed to burn a fuel completely with no oxygen left over; practical burners use more than this to ensure complete combustion.
Excess air
Air supplied beyond stoichiometric requirements; too little causes carbon monoxide and smoke, too much lowers efficiency by carrying heat up the stack.
Induced draft
A fan downstream of the boiler pulls combustion gases through the furnace and keeps furnace pressure slightly negative, preventing hot gas leakage.
Flame safeguard
A control system that monitors the flame and closes fuel valves on flame failure, requiring a purge before any restart.
Boiler horsepower
A measure of boiler capacity equal to 33,475 Btu per hour, about 9.81 kW, or evaporation of about 34.5 pounds of water per hour.
Pre-lightoff purge
Forcing air through the furnace before ignition to remove combustible gases; typically at least four furnace air changes are required.
Ultrasonic thickness testing
A nondestructive method using sound waves to measure remaining wall thickness and detect corrosion or erosion in boiler tubes and shells.
Hydrostatic test
A pressure test using water at 1.5 times the maximum allowable working pressure with safety valves isolated, checking for leaks and structural integrity.
Lockout/tagout
An energy-isolation procedure using locks and tags to prevent accidental startup during maintenance; verify zero energy before work begins.
Safety valve pop test
A test that confirms a safety valve opens at its set pressure and reseats properly; performed by qualified personnel with the boiler under pressure.
Refractory inspection
Checking furnace walls, baffles, and seals for cracks, spalling, or hot spots that can reduce efficiency and allow hot gases to escape.
High-pressure limit switch
A control that stops fuel firing when boiler pressure reaches a set point below the safety valve setting, preventing unnecessary safety-valve lifting.
Flame failure response
On loss of flame, the flame safeguard closes fuel valves and locks out the burner; the operator must purge the furnace before restarting.
Broken gauge glass
Close the upper and lower gauge-glass valves immediately, then use try cocks to check water level; avoid standing directly in front of the glass.
Confined space entry
Entry into a boiler or vessel requires a permit, atmospheric testing, ventilation, an attendant, and a rescue plan before anyone enters.
Fuel leak emergency
Stop firing, shut off fuel at the source, ventilate the area, eliminate ignition sources, and evacuate if the leak is large or uncontrollable.
ASME Section I
The ASME Boiler and Pressure Vessel Code section covering power boilers; Section IV covers heating boilers. Ohio adopts ASME construction requirements by reference.
Ohio boiler jurisdiction
The Ohio Division of Industrial Compliance, Bureau of Boiler and Pressure Vessel Compliance, administers boiler rules, inspections, and inspector certification.
Operator logbook
A record of boiler pressure, water level, blowdown, tests, fuel use, and abnormal conditions; it must be kept available for inspection.
Boiler inspection access
Operators must provide inspectors access to the boiler, nameplate, fittings, and records, and must not operate equipment under a failed inspection.