OH Fire Sprinkler · Put your knowledge to work in context.

All case studies

ESFR System and a Tenant's Taller Racks

A 180,000 sq ft warehouse has a 32-ft ceiling and an existing ESFR system with K-14 pendent sprinklers at 10 ft spacing, designed for 25-ft storage of Class III commodities. The owner leases 40,000 sq ft to a tenant that installs 30-ft-high racking. The tenant's shelving contractor asks the sprinkler contractor to add 12 ceiling sprinklers over the new racks and to 'keep the existing calc' because the water supply has extra pressure. The sprinkler contractor's designer says the change is minor. No plan revision has been filed with the local fire official. The warehouse is occupied and operating, and the tenant wants to stock the racks within two weeks. The contractor has a copy of the original approved plans but has not reviewed the commodity classification of the tenant's goods.

1. Is the proposed field change acceptable under the ESFR design basis? Explain the controlling technical issue.

Read the worked answer

No. ESFR sprinklers depend on a clear ceiling-to-storage clearance, commonly 36 in., to develop the required fire plume and suppression performance. With a 32-ft ceiling and 30-ft storage, the clearance is only 2 ft, which violates the ESFR design basis and the approved plans. Adding 12 ceiling sprinklers does not fix that clearance problem and is not a substitute for a properly designed ESFR or in-rack system. The contractor also cannot 'keep the existing calc' because additional sprinklers, different racking, and a changed storage height alter the hydraulic demand and the design area. The designer's statement that the change is minor is not sufficient. The correct answer is to stop and require a redesign by a qualified designer before any sprinkler modification or rack loading.

2. What technical factors and approvals must be addressed before the tenant can use the 30-ft racks?

Read the worked answer

The contractor and designer must first confirm the commodity classification and the rack configuration, because ESFR protection depends on storage height, aisle width, flue spaces, and commodity hazard. They must evaluate whether the existing ceiling-only ESFR system can be modified or whether in-rack sprinklers, a different sprinkler type, or a redesigned system is required. A new hydraulic calculation and shop drawings must be prepared, and the plans must be submitted to the AHJ as a permit revision. The fire official may also require an engineering analysis or a review of the tenant's storage arrangement. The contractor should coordinate with the owner, tenant, and shelving contractor so that no racks are loaded beyond the approved height before the revised system is inspected and approved. Schedule pressure does not override the clearance and design requirements.

3. What should the contractor tell the owner and tenant about proceeding with the requested change?

Read the worked answer

The contractor should give written notice that the proposed 30-ft racking cannot be protected by the existing ESFR design as requested and that adding ceiling sprinklers without a redesign would be a code violation. It should explain the clearance violation, the need for a new design and permit revision, and the risk that the AHJ will reject the installation or require the tenant to unload the racks. The contractor should not accept a verbal instruction to proceed or sign off on the existing calculation. If the tenant wants to move quickly, the contractor can offer a compliant path: expedite a design review, submit revised drawings, and phase the rack loading if the AHJ allows. The contractor should document the refusal and the recommended corrective actions so its license and professional judgment are protected.