- Working space depth, 480 volts
- For equipment operating at 151 to 600 volts to ground, NEC Table 110.26(A)(1) requires a working space depth of 3 ft for Condition 1, 3.5 ft for Condition 2, and 4 ft for Condition 3.
- Meaning of listed equipment
- Equipment is listed when it appears in a list published by an organization acceptable to the authority having jurisdiction that evaluates products and maintains periodic inspection of production of listed equipment.
- Dedicated equipment space dimensions
- NEC 110.26(E) requires a dedicated equipment space extending 30 in. from the front of electrical equipment, the width of the equipment, and 6 ft above it or to the structural ceiling.
- Available fault current marking
- NEC 110.24 requires service equipment in other than dwelling units to be field marked with the maximum available fault current and the date the fault current calculation was performed.
- NM cable fastening intervals
- Nonmetallic-sheathed cable must be secured within 12 in. of each box and at intervals not exceeding 4.5 ft, as required by NEC 334.30.
- Box volume per 12 AWG
- NEC Table 314.16(B) assigns 2.25 cubic inches of box volume per 12 AWG conductor, 2.0 for 14 AWG, 2.5 for 10 AWG, and 1.75 for 18 and 16 AWG.
- Direct burial cover, UF cable
- NEC Table 300.5 requires 24 in. of cover for direct-buried UF cable generally, reduced to 18 in. for 120 V, 20 A residential circuits and 12 in. where GFCI-protected.
- Angle pull box sizing
- NEC 314.28(A)(2) requires an angle-pull box dimension of at least six times the trade size of the largest raceway, plus the trade sizes of the other raceways in the same row.
- Small conductor protection, 14 AWG
- NEC 240.4(D) limits overcurrent protection for 14 AWG copper to 15 A, for 12 AWG to 20 A, and for 10 AWG to 30 A, apart from specific permitted exceptions.
- Concrete-encased grounding electrode
- A concrete-encased electrode is at least 20 ft of 1/2 in. or larger reinforcing steel, or 4 AWG bare copper, encased in at least 2 in. of concrete near the bottom of a footing.
- Equipment grounding conductor, 200 A
- NEC Table 250.122 requires a 6 AWG copper equipment grounding conductor for a circuit protected by a 200 A overcurrent device, while a 100 A device requires 8 AWG copper.
- Ten-foot tap rule
- NEC 240.21(B)(1) permits a tap up to 10 ft long if its ampacity is at least one-tenth the rating of the overcurrent device ahead of it, with no splices and a single termination.
- Dwelling receptacle wall spacing
- NEC 210.52(A)(1) requires dwelling receptacle outlets so that no point along the wall line is more than 6 ft from a receptacle, which limits outlets to 12 ft apart.
- Two small appliance circuits
- NEC 210.11(C)(1) requires at least two 20 A small-appliance branch circuits for dwelling kitchen, pantry and dining areas, supplying only receptacle outlets there.
- Overhead service clearance, driveway
- NEC 230.24 requires overhead service conductors to have at least 12 ft clearance above a residential driveway, 10 ft above a sidewalk, and 18 ft above a public road.
- Dwelling service disconnect rating
- NEC 230.79(C) requires the service disconnecting means for a one-family dwelling to have a rating of not less than 100 A, with a three-wire service.
- Flexible cord prohibited uses
- NEC 400.8 prohibits using flexible cord as a substitute for fixed wiring, running it through holes in walls or ceilings, or concealing it above suspended ceilings.
- Water heater branch circuit
- NEC 422.13 requires the branch circuit for a storage-type water heater rated 20 gallons or more to have an ampacity of at least 125 percent of the appliance nameplate rating.
- Air-conditioning disconnect location
- NEC 440.14 requires the disconnecting means for air-conditioning and refrigerating equipment to be located within sight of and not more than 50 ft from the equipment.
- Hazardous location classes
- NEC Article 500 designates Class I for flammable gases and vapors, Class II for combustible dust, and Class III for ignitable fibers or flyings, each divided into Division 1 and Division 2.
- Pool perimeter equipotential bonding
- NEC 680.26 requires equipotential bonding of conductive pool shell parts and of perimeter surfaces extending at least 3 ft horizontally from the inside walls of the pool.
- Photovoltaic source circuit current
- NEC 690.8(A) requires photovoltaic source-circuit current to be calculated at 125 percent of short-circuit current, and conductor ampacity to be at least 125 percent of that result.
- PV rapid shutdown voltage
- NEC 690.12 requires rapid shutdown to reduce conductors outside the photovoltaic array boundary to 30 volts or less within 30 seconds after shutdown is initiated.
- Motor full-load current source
- NEC 430.6(A)(1) requires motor full-load current for sizing conductors, feeders and protection to be taken from Tables 430.247 through 430.250, not from the motor nameplate.
- Motor branch circuit 125 percent
- NEC 430.22 requires branch-circuit conductors supplying a single motor to have an ampacity of at least 125 percent of the motor full-load current rating.
- Motor overload, 1.15 service factor
- NEC 430.32 requires overload protection set at 125 percent of nameplate current for motors marked with a 1.15 service factor or a 40 degrees C temperature rise.
- Compressor protection, 175 percent
- NEC 440.22(A) permits short-circuit protection for an air-conditioning compressor at up to 175 percent of rated-load current, increased to 225 percent if the unit will not start.
- Communications cable separation
- NEC 800.133(A)(1) requires communications cables to be separated by at least 2 in. from power conductors, Class 1 circuits and non-power-limited fire alarm conductors unless a barrier separates them.
- Intersystem bonding termination
- NEC 250.94 requires a terminal bar at the service to bond communications, community antenna television and other systems, providing a common point for intersystem bonding.
- Class 2 circuit limits
- NEC Article 725 defines Class 2 circuits as limited-energy circuits whose power does not exceed the values in Tables 725.121, permitting reduced wiring and separation requirements.
- Oklahoma electrical licensing authority
- Electrical licenses in Oklahoma are issued by the Construction Industries Board under the Oklahoma Electrical Licensing Act, located in Title 59 of the Oklahoma Statutes, Sections 1680 through 1697.
- Oklahoma apprentice supervision
- Oklahoma requires registered electrical apprentices to work under the supervision of a licensed journeyman or contractor, with apprentice registration filed with the Construction Industries Board.