OK Fire Alarm Installer flashcards
OK Fire Alarm Installer · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 72
- The National Fire Alarm and Signaling Code, which establishes minimum requirements for the design, installation, testing, and maintenance of fire detection and alarm systems.
- NEC Article 760
- The National Electrical Code article governing fire alarm wiring, separating power-limited circuits (FPL) from non-power-limited circuits (NPLFA) with different installation rules.
- Authority having jurisdiction
- The organization or individual responsible for approving equipment, installations, and procedures, often the local fire marshal or building official enforcing the adopted code edition.
- FPLP cable
- Plenum-rated power-limited fire alarm cable, required where conductors run in environmental air spaces; FPLR is for risers and FPL for general-use locations.
- Class B circuit
- A fire alarm pathway in which a single open or ground fault causes a trouble signal but may prevent devices beyond the fault from operating.
- Class A circuit
- A fire alarm pathway that leaves the control unit and returns on a separate conductor, so one open fault does not stop any device on the circuit from operating.
- Pathway survivability level
- An NFPA 72 classification from Level 0 to Level 4 describing how well a circuit resists fire damage, with higher levels requiring rated cable, enclosures, or redundant paths.
- Spot smoke detector spacing
- On smooth ceilings, smoke detectors are spaced no more than 30 ft apart and no more than 15 ft from any wall, which covers about 900 square feet per detector.
- Photoelectric smoke detector
- A detector that senses smoke by light scattering or obscuration inside a chamber, and responds better than ionization types to smoldering fires producing larger visible particles.
- Ionization smoke detector
- A detector using a radioactive source to ionize air in a chamber; it responds quickly to flaming fires with small particles but is more prone to nuisance alarms from cooking.
- Rate-of-rise heat detector
- A device that signals when temperature rises faster than a preset rate, commonly 15 degrees F per minute, often combined with a fixed-temperature element for reliable response.
- Manual pull station height
- Manual fire alarm boxes are mounted so the operable portion sits 42 in to 48 in above the finished floor, placed within 5 ft of an exit doorway.
- Waterflow switch timing
- A sprinkler waterflow device must signal an alarm within 90 seconds of flow equal to one sprinkler, and must not alarm at flow rates below 10 gpm.
- Public mode audibility
- Alarm sound must be at least 15 dBA above average ambient, or 5 dBA above the maximum ambient lasting 60 seconds or longer, whichever is greater.
- Sleeping area alarm level
- In sleeping areas the audible alarm must produce at least 75 dBA at the pillow, or 15 dBA above ambient sound level, whichever is greater.
- 520 Hz alarm tone
- A low-frequency square-wave alarm tone required in commercial sleeping rooms because it is more effective at waking occupants, including those with hearing loss.
- Strobe synchronization
- Visible notification appliances in the same field of view must flash in sync, because unsynchronized strobes at different rates can reduce the effectiveness of the warning.
- End-of-line resistor
- A device at the far end of a Class B circuit that allows the panel to monitor wiring continuity; its removal or an open circuit produces a trouble signal.
- Addressable signaling line circuit
- A circuit on which every device has a unique address, so the control unit can report the specific device that alarmed, faulted, or went missing.
- Detector compatibility listing
- Two-wire smoke detectors must be listed as compatible with the particular control unit, because an unlisted pairing can prevent correct alarm, reset, or supervision.
- Power-limited conductor separation
- Power-limited fire alarm conductors must be kept at least 2 inches away from non-power-limited conductors, or separated by a listed barrier, to prevent fault energy transfer.
- Secondary power duration
- Protected premises systems typically require 24 hours of battery standby followed by 5 minutes of alarm load; voice evacuation systems require 15 minutes of alarm.
- Battery calculation formula
- Amp-hours equals 1.2 times the sum of standby current times standby hours plus alarm current times alarm hours, where 1.2 adds a 20 percent aging margin.
- Dedicated fire alarm circuit
- The panel's primary power must be a dedicated branch circuit marked fire alarm circuit control, with a lockable disconnect and no ground-fault circuit protection.
- Battery recharge time
- After a full discharge, the charging means must be capable of restoring the secondary batteries to full charge within 48 hours.
- Smoke detector functional test
- Detectors are functionally tested at least annually by a listed method or aerosol, and results are recorded and made available to the authority having jurisdiction.
- Battery load test
- An annual capacity test confirms the battery can carry the calculated load; a battery that fails is replaced, and monthly visual checks cover terminals and case condition.
- Impairment fire watch
- When a fire alarm system is out of service, the AHJ, owner, and monitoring company are notified and a documented fire watch is kept until restoration.
- ITM record retention
- Inspection, testing, and maintenance results must be documented with dates, devices, and signatures, and retained for the period required by the authority having jurisdiction.
- Record of completion
- An NFPA 72 form documenting that the installed system matches the approved design, signed by the installing contractor and verified during the acceptance test.
- Acceptance test
- A test performed after installation and before the system is placed in service, witnessed by the authority having jurisdiction, confirming each device and function operates as designed.
- Lockout tagout
- An OSHA-required practice for de-energizing circuits during service work; only the person who applied the lock and tag may remove them.