- MCL
- Maximum contaminant level: the enforceable highest concentration of a contaminant allowed in public drinking water under the Safe Drinking Water Act, based on health effects and treatability.
- CT value
- Product of disinfectant residual concentration in mg/L and contact time in minutes. Required CT depends on pH, temperature, and the target log inactivation of pathogens.
- Secondary standard
- A non-enforceable aesthetic guideline for contaminants such as iron, manganese, chloride, and sulfate that affect taste, odor, color, or staining rather than health.
- Lead action level
- The 90th-percentile lead concentration of 0.015 mg/L in tap samples. Exceedance triggers corrosion control treatment, public education, and lead service line planning.
- TTHM MCL
- Total trihalomethanes limit of 0.080 mg/L, evaluated as a locational running annual average under the Stage 2 Disinfectants and Disinfection Byproducts Rule.
- Pressure conversion
- One psi equals about 2.31 feet of water head. A 100-foot column of water produces roughly 43.3 psi at its base.
- Static head
- The vertical elevation difference between a water source and discharge point, independent of flow. It determines the pressure available before friction losses.
- Total coliform positive
- A routine sample containing total coliform triggers repeat sampling at the same and adjacent taps; an E. coli-positive repeat is an acute violation requiring 24-hour notice.
- Operator class
- Oklahoma certification grade from A (highest) through D, tied to system size and treatment complexity. An operator may serve as chief only at or below their class.
- BOD5
- Biochemical oxygen demand measured over five days at 20°C. It estimates biodegradable organic matter; untreated domestic wastewater is typically 200–250 mg/L.
- Secondary treatment limits
- Thirty-day average effluent limits of 30 mg/L BOD5 and 30 mg/L total suspended solids for publicly owned treatment works, with percent-removal alternatives.
- F/M ratio
- Food-to-microorganism ratio: pounds of BOD applied per pound of MLSS per day. Typical activated sludge values are 0.2 to 0.5.
- Sludge age
- Solids retention time, calculated as the MLSS inventory divided by the solids leaving the system per day. It controls wasting rate and sludge settling.
- RAS
- Return activated sludge: settled biomass returned from the clarifier to the aeration basin, typically at 5,000–10,000 mg/L, to maintain the mixed liquor population.
- SSO reporting
- A sanitary sewer overflow must be reported to Oklahoma DEQ, with public notice and corrective action, because it releases untreated sewage to the environment.
- Composite sample
- A flow-proportioned or time-proportioned mixture of grab samples collected over a period, used for most NPDES effluent monitoring parameters.
- SWPPP
- Stormwater Pollution Prevention Plan required under a construction general permit. It identifies best management practices, inspection schedules, and erosion controls before land disturbance.
- Dechlorination
- Removal of chlorine residual from treated effluent, often with sulfur dioxide or sodium bisulfite, to protect aquatic life from total residual chlorine toxicity.
- Construction permit
- Oklahoma DEQ approval required before building or modifying water or wastewater facilities. Plans must be sealed by a licensed professional engineer.
- Water-sewer separation
- Minimum 10 feet horizontal separation between water mains and sanitary sewers. If closer, the sewer must be encased and the water main pressure-tested.
- Vertical separation
- Water mains crossing above sewers need at least 18 inches clearance. Crossing below a sewer requires encasement of the sewer and pressure testing.
- Air gap
- The only absolute backflow protection: a physical unobstructed vertical separation between a supply outlet and the flood level of the receiving vessel.
- RPZ assembly
- Reduced-pressure-zone backflow preventer used for high-hazard cross-connections. It must be tested annually by a certified tester and records retained.
- Capacity analysis
- A design calculation submitted with a construction permit application showing hydraulic and treatment capacity to serve projected flows and loads.
- Pre-construction inspection
- An inspection required before operation of newly constructed facilities confirms that construction matches approved plans and that treatment processes function as designed.
- Erosion control
- Best management practices such as silt fence and sediment basins installed before grading and maintained until final stabilization to prevent sediment discharge.
- Watershed
- The land area draining to a common outlet or point. It is delineated from topographic maps or digital elevation models by tracing flow paths.
- Time of concentration
- The travel time for runoff from the hydraulically most distant point to reach the outlet, used as the storm duration in the Rational Method.
- Rational Method
- Q (cfs) = C × i × A, where C is the runoff coefficient, i is rainfall intensity in inches per hour, and A is area in acres.
- TMDL
- Total maximum daily load: the maximum pollutant loading a waterbody can receive while meeting standards, allocated among point sources, nonpoint sources, and a margin of safety.
- Source water protection
- Planning that identifies potential contamination sources within a wellhead or surface intake area and sets management strategies to reduce risk.
- Impervious cover
- Land surface that prevents infiltration, increasing runoff volume and peak flow. About 10% imperviousness signals stream degradation and 25% severe impairment.
- Green infrastructure
- Practices such as rain gardens, permeable pavement, and bioswales that infiltrate or detain runoff, reducing volume and pollutant loading to receiving waters.