Quick reference

Structural Systems

  • Bending stress fb = M/S; required section modulus S = M/Fb. For a rectangular section S = bd²/6, so capacity rises with the square of depth.

  • Simply supported beam under uniform load: Δmax = 5wL⁴/(384EI) at midspan - deflection varies with the fourth power of span.

  • Cantilever under uniform load: Δmax = wL⁴/(8EI) at the free end, about 4.8 times the deflection of an equal simple span under the same load.

  • Tributary area of an interior column equals the product of the two adjacent bay spacings; axial load = tributary area × unit floor load × number of floors carried.

  • ASCE 7 live load reduction: L = L0(0.25 + 15/√(KLL·AT)); KLL = 4 for interior columns and 2 for beams, with a 50% floor for members supporting one floor.

  • LRFD gravity combination 1.2D + 1.6L versus ASD D + L; allowable-stress capacities must never be compared with factored demands.

  • Elastic moduli: steel 29,000 ksi, concrete Ec ≈ 57,000√f'c psi, sawn wood ≈ 1.6 × 10⁶ psi; steel stiffness is roughly ten times that of concrete.

  • Seismic base shear V = Cs·W; wind pressure p = 0.00256·V² times pressure coefficients, about 20 psf at 90 mph before adjustment factors.

  • Footing area A = P/q_allow; allowable bearing is typically 2,000–4,000 psf for granular soils and 1,000–2,000 psf for soft clays.

Quick reference

Mechanical Systems

  • Sensible heat: Qs (Btu/h) = 1.08 × CFM × ΔT(°F) for standard air at sea level.

  • Latent heat: QL = 0.68 × CFM × Δgr (grains/lb); total heat: Qt = 4.5 × CFM × Δh (Btu/lb).

  • 1 ton of refrigeration = 12,000 Btu/h = 200 Btu/min; a rough office cooling check is 25–35 Btu/h per square foot.

  • Internal gains dominate commercial loads: a seated adult releases roughly 250 Btu/h sensible plus 200 Btu/h latent under design conditions.

  • Duct design: 1,000–1,500 fpm in supply mains, 600–900 fpm in branches, friction rate about 0.1 in. w.g. per 100 ft of equivalent length.

  • Static water pressure rises 0.433 psi per foot of height; a fixture 40 ft below the main sees about 17 psi more than at the main.

  • Building drain slope: 1/4 in./ft for pipe 3 in. and smaller, 1/8 in./ft for 4 in. and larger; every fixture trap requires a vent.

  • Fan laws: airflow varies linearly with speed, static pressure with speed squared, and brake horsepower with speed cubed.

  • ASHRAE 62.1 ventilation = people outdoor-air rate × occupants plus area outdoor-air rate × floor area; CO₂ demand control modulates to occupancy.

Quick reference

Electrical Systems

  • Ohm's law V = I·R; power P = V·I for direct current and unity-power-factor loads.

  • Single-phase P = V·I·PF; three-phase P = √3·V·I·PF, so a balanced three-phase circuit carries about 1.73 times the single-phase power at the same amperage.

  • Single-phase voltage drop: VD = 2·K·I·L/CM, with K = 12.9 for copper and 21.2 for aluminum; L in feet, CM in circular mils.

  • Voltage drop targets: 3% maximum on a branch circuit and 5% total from service to the farthest outlet.

  • Continuous loads are calculated at 125% of ampere rating when sizing overcurrent devices and conductors; a 20A breaker therefore serves 16A continuous.

  • NEC 110.26 working space in front of panels: 30 in. wide, 36 in. deep (48 in. above 600V), 6 ft 6 in. high, never used for storage.

  • Conduit fill limits: 53% for one conductor, 31% for two, 40% for three or more of the interior cross-sectional area.

  • Illuminance in footcandles = lumens ÷ area in square feet; efficacy in lumens per watt and lighting power density in W/ft² drive code compliance.

  • GFCI protection applies to bathrooms, kitchens, garages, outdoors, and receptacles within 6 ft of a sink; AFCI protects dwelling branch circuits.

Quick reference

Architectural Systems

  • Egress capacity (IBC Table 1005.3.2): 0.3 in. per occupant for stairways and 0.2 in. for other components; sprinklered buildings reduce these to 0.2 in. and 0.15 in.

  • Occupant load factors: business 150 gross, mercantile 60 gross, classrooms 20 net, unconcentrated assembly 15 net, concentrated assembly 7 net.

  • Two means of egress are required at an occupant load of 50 or more, or wherever the common path or travel distance limits are exceeded.

  • Travel distance limits for business occupancies are typically 200 ft unsprinklered and 250 ft sprinklered, measured along the path of egress travel.

  • Stairs: maximum riser 7 in., minimum tread 11 in.; riser plus tread should total about 17–18 in. for a safe, comfortable gait.

  • Handrails are required on both sides of stairs with four or more risers, mounted 34–38 in. above the tread nosing.

  • Doors in a means of egress provide 32 in. minimum clear width and swing in the direction of travel when serving 50 or more occupants.

  • Accessibility: 36 in. clear route, 60 in. turning space, ramp slope maximum 1:12 with a landing every 30 in. of rise, grab bars at 33–36 in.

  • Minimum ceiling height is 7 ft 6 in. in habitable rooms and corridors, with 6 ft 8 in. permitted at doors and in bathrooms.

Quick reference

Materials

  • Concrete compressive strength f'c is measured on cylinders at 28 days; Ec = 57,000√f'c psi, and normal exposure uses a water-cement ratio of 0.40–0.50.

  • Steel: ASTM A36 has Fy = 36 ksi, A992 has Fy = 50 ksi; E = 29,000 ksi and elongation at fracture is roughly 20%.

  • Coefficients of thermal expansion: steel 6.5 × 10⁻⁶/°F, concrete 5.5 × 10⁻⁶/°F, aluminum 13 × 10⁻⁶/°F - mismatched materials need joints or slip connections.

  • Gypsum fire ratings: 5/8 in. Type X on steel studs yields about 1 hour; two layers or added insulation raises the rating toward 2 hours.

  • Wood framing should be dried to 19% moisture content or less before enclosure; shrinkage is greatest in the tangential direction, about 1% of width per 4% moisture change.

  • Concrete masonry unit nominal size is 8 × 8 × 16 in. with 3/8 in. mortar joints; mortar Types M, S, N, O descend in compressive strength.

  • Safety glazing (tempered or laminated) is required in doors, in sidelights within 24 in. of a door edge, and in glazing whose bottom edge is within 18 in. of the floor.

  • Stiff substrates are required for brittle finishes: tile and terrazzo need deflection limited to L/360, while carpet tolerates greater movement.

  • Thermal mass in concrete or masonry shifts peak cooling load by roughly 4–6 hours rather than reducing steady-state conduction.

Quick reference

Project Management

  • The critical path is the longest path through the activity network; its duration establishes the contract completion date and its activities carry zero float.

  • Total float = LS − ES = LF − EF; free float = early start of the successor minus early finish of the activity.

  • Contract types: lump sum suits fully defined scope, guaranteed maximum price shares savings, and cost plus fee suits fast-track work with incomplete documents.

  • AIA documents: B101 owner-architect agreement, A101 owner-contractor agreement, A201 general conditions defining the architect's authority and standard of care.

  • Retainage is commonly 5–10% withheld from each progress payment, reduced at substantial completion and released at final completion.

  • Bid bonds guarantee the bidder will execute the contract; performance bonds guarantee completion; payment bonds guarantee subcontractors and suppliers are paid.

  • A change order is written, priced, and signed by the owner; a construction change directive authorizes work before the price is agreed.

  • Progress payments use AIA G702/G703 with a conditional lien waiver, certified by the architect after site observation of the work in place.

  • Design liability statutes of limitation typically run 6–10 years from substantial completion, varying by jurisdiction.