PE Electrical · Get comfortable with the vocabulary.

Power factor

The ratio of real (average) power to apparent power in an AC circuit; for sinusoidal quantities it equals the cosine of the angle between voltage and current. Loads with low power factor draw more current for the same useful work.

Related: Complex power, Load factor
Load factor

The average load over a stated period divided by the peak load occurring in that period. A high load factor means equipment is used more evenly and fixed costs are spread over more energy sales.

Related: Demand factor, Diversity factor
Demand factor

The maximum demand of an installation divided by its total connected load, always one or less. It recognizes that not all connected equipment operates at the same time.

Related: Diversity factor, Load factor
Diversity factor

The sum of the individual maximum demands of two or more loads divided by the coincident maximum demand of the combined system; a value of one or greater.

Related: Demand factor, Load factor
Ampacity

The maximum continuous current a conductor can carry under specified installation conditions without exceeding its rated temperature, accounting for insulation type, ambient temperature, and the number of current-carrying conductors.

Related: Voltage drop, Triplen harmonics
Voltage drop

The reduction in voltage between the source and the load caused by current flowing through the impedance of conductors. Design limits usually cap total feeder plus branch-circuit drop at a small percentage of nominal voltage.

Related: Ampacity, Power factor
Interrupting rating

The maximum short-circuit current, at a stated voltage, that a protective device such as a circuit breaker or fuse can safely clear without damage or hazard to personnel.

Related: Transformer percent impedance, Per-unit system
Triplen harmonics

Odd multiples of the third harmonic, such as the third, ninth, and fifteenth, that are in phase in all three phases and therefore add arithmetically in the neutral of a four-wire system.

Related: Power factor, Ampacity
Phasor

A complex number that represents the magnitude and phase angle of a sinusoidal quantity at a single frequency, allowing steady-state AC circuits to be solved with ordinary complex arithmetic.

Related: Impedance, Complex power
Impedance

The total opposition to sinusoidal current flow, a complex quantity whose real part is resistance and whose imaginary part is reactance. It is the ratio of phasor voltage to phasor current.

Related: Phasor, Resonance
Complex power

The product of phasor voltage and the conjugate of phasor current, expressed in volt-amperes. Its real part is average power in watts and its imaginary part is reactive power in var.

Related: Power factor, Phasor
Thevenin equivalent

A two-terminal network replaced by a single voltage source in series with an impedance, valid at the terminals for any external connection. The source is the open-circuit voltage and the impedance is seen looking back with sources dead.

Related: Superposition, Impedance
Superposition

A method for linear circuits in which the response to several independent sources is found by adding the responses computed with each source acting alone, with other voltage sources shorted and current sources opened.

Related: Thevenin equivalent
Resonance

The condition in an RLC circuit where inductive and capacitive reactances cancel, leaving only resistance, so current and voltage are in phase and impedance magnitude is minimum in series or maximum in parallel.

Related: Impedance, Time constant
Time constant

The interval after which a first-order RC or RL circuit's transient response changes by about 63 percent of the way toward its final value; roughly five time constants are treated as steady state.

Related: Resonance
Slip

The difference between synchronous speed and actual rotor speed of an induction machine, usually expressed as a fraction or percentage of synchronous speed. Slip is zero at synchronous speed and one at standstill.

Related: Synchronous speed, Breakdown torque
Synchronous speed

The rotational speed of the rotating magnetic field produced by a polyphase winding, equal to 120 times the frequency divided by the number of poles.

Related: Slip, Field excitation
Armature reaction

The magnetomotive force produced by current flowing in the armature winding, which distorts or opposes the main field flux and shifts the neutral axis in a DC machine.

Related: Synchronous reactance, Field excitation
Field excitation

The direct current supplied to a synchronous machine's field winding, which sets the internal generated voltage and therefore controls reactive power output and terminal voltage.

Related: Synchronous reactance, Power factor
Synchronous reactance

The effective reactance of a synchronous machine in steady state, combining armature leakage reactance and the reactance representing armature reaction; it relates internal voltage to terminal voltage and current.

Related: Armature reaction, Field excitation
Locked-rotor current

The current an induction motor draws when its rotor is held stationary and rated voltage is applied; typically five to eight times rated current and used for starting and protection studies.

Related: Breakdown torque, Transformer percent impedance
Breakdown torque

The maximum torque an induction motor can develop without stalling, occurring at a slip greater than the slip at full load. Loads demanding more than this torque cause the motor to stall.

Related: Slip, Locked-rotor current
Transformer percent impedance

The voltage, as a percentage of rated voltage, that must be applied to one winding with the other short-circuited to circulate rated current; it sets short-circuit current magnitude and voltage regulation.

Related: Per-unit system, Locked-rotor current
Core loss

Power dissipated in the magnetic core of a transformer or machine by hysteresis and eddy currents; it depends on flux density and frequency and is essentially constant from no load to full load.

Related: Transformer percent impedance
ACSR

Aluminum conductor steel reinforced: a stranded overhead conductor whose outer aluminum strands carry current while a central steel core provides tensile strength for long spans.

Related: Sag, Bundled conductors
Sag

The vertical distance between a conductor's support points and its lowest point; it depends on span, conductor weight, tension, and temperature and must keep clearances safe while limiting tension.

Related: ACSR
Corona

Ionization of air around a conductor when the surface voltage gradient exceeds the breakdown strength of air, causing power loss, radio noise, and audible hum, especially at high altitude or in rain.

Related: Bundled conductors, ACSR
Bundled conductors

Two or more subconductors per phase spaced a small distance apart. Bundling reduces corona loss and inductive reactance and increases line capacitance compared with a single conductor.

Related: Corona, ACSR
Ferranti effect

The rise in receiving-end voltage above sending-end voltage on a long, lightly loaded AC line, caused by the line's shunt capacitance charging current flowing through series inductance.

Related: Load flow
BIL

Basic impulse insulation level: the crest voltage a piece of equipment must withstand under a standard lightning impulse wave without flashover or breakdown; used to coordinate insulation with protective devices.

Related: Surge arrester
Surge arrester

A protective device that presents high impedance at normal voltage but conducts surge current to ground above a threshold, then reseals, limiting overvoltage on equipment insulation.

Related: BIL, Corona
Per-unit system

A scaling method in which voltages, currents, powers, and impedances are divided by chosen base values so that transformer turns ratios disappear and results are dimensionless and easy to compare.

Related: Transformer percent impedance, Bus admittance matrix
Symmetrical components

A technique that resolves unbalanced three-phase phasors into three balanced sets - positive, negative, and zero sequence - so unbalanced faults and loads can be analyzed with per-phase networks.

Related: Sequence network, Bus admittance matrix
Sequence network

The positive-, negative-, or zero-sequence equivalent circuit of the system, interconnected according to fault type to compute sequence currents and voltages at an unbalanced fault.

Related: Symmetrical components
Bus admittance matrix

A square matrix whose diagonal entries are the sum of admittances connected to each bus and whose off-diagonal entries are the negatives of the admittances between buses; the basis of load-flow and short-circuit calculations.

Related: Load flow, Per-unit system
Load flow

The iterative solution of network equations that finds bus voltage magnitudes and angles and the resulting real and reactive power flows for specified generation and load conditions.

Related: Swing bus, Bus admittance matrix
Swing bus

The reference bus in a load flow, with voltage magnitude and angle fixed, that supplies whatever real and reactive power balances system losses against scheduled generation.

Related: Load flow
Equal area criterion

A graphical stability test in which the accelerating area under a synchronous machine's power-angle curve must not exceed the maximum decelerating area available after a disturbance for the system to remain stable.

Related: Synchronous speed
Distance relay

A protective relay that measures the ratio of voltage to current at its location to estimate the impedance to a fault, then trips if that impedance falls inside a set zone.

Related: Symmetrical components, Sequence network
Incremental cost

The additional cost to produce one more megawatt from a generating unit, equal to the derivative of its cost curve; economic dispatch equalizes incremental costs among committed units within their limits.

Related: Load flow, Swing bus