PE Mechanical HVAC flashcards
PE Mechanical HVAC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ton of refrigeration
- A rate of heat removal equal to 12,000 Btu/h, 200 Btu/min, or 3.517 kW; it is used to size cooling equipment and to convert catalog data to kW per ton.
- Air-side sensible heat equation
- Qs in Btu/h equals 1.08 times the airflow in cfm times the dry-bulb temperature difference in F, valid for standard sea-level air at 0.075 lbm/ft3.
- Water-side sensible heat equation
- Q in Btu/h equals 500 times the water flow in gpm times the temperature difference in F, based on water density and specific heat near 60 F.
- Fan and pump power
- Air horsepower equals cfm times total pressure in inches of water divided by 6356 and by efficiency; pump horsepower equals gpm times psi divided by 1714 and efficiency.
- Steady-flow energy equation
- For a control volume at steady state, heat added minus work delivered equals the change in enthalpy plus kinetic and potential energy between inlet and outlet.
- Carnot COP
- The maximum coefficient of performance: for a refrigerator, evaporating absolute temperature divided by the difference between condensing and evaporating absolute temperatures.
- Isentropic compression relation
- For an ideal gas compressed without heat transfer, T2/T1 equals the pressure ratio raised to the power (k-1)/k, with k equal to 1.4 for air.
- Throttling process
- Expansion through a valve or capillary is adiabatic with no work, so enthalpy stays constant while pressure falls and both temperature and entropy change.
- Steam quality
- The mass fraction of vapor in a saturated liquid-vapor mixture; mixture enthalpy equals hf plus quality times hfg, so quality is (h minus hf) over hfg.
- Humidity ratio
- Mass of water vapor per mass of dry air, equal to 0.621945 times vapor pressure divided by total pressure minus vapor pressure; it is unchanged by sensible heating.
- Relative humidity
- The ratio of actual water-vapor partial pressure to the saturation pressure at the same dry-bulb temperature; it falls when air is heated at constant humidity ratio.
- Moist air enthalpy
- Enthalpy in Btu per pound of dry air equals 0.240 times dry-bulb F plus humidity ratio times the quantity 1061 plus 0.444 times dry-bulb F.
- Sensible heat ratio
- Sensible load divided by total load; it fixes the slope of the room process line on a psychrometric chart and helps locate the coil apparatus dew point.
- Apparatus dew point
- The saturation-curve point where the line through entering and leaving coil conditions intersects saturation; leaving air lies between it and the entering air condition.
- Reynolds number
- Velocity times diameter divided by kinematic viscosity, representing inertial over viscous forces; pipe flow is laminar below about 2300 and turbulent above 4000.
- Darcy-Weisbach equation
- Friction head loss equals the friction factor times length divided by diameter times the velocity head V squared over 2g; the factor is 64/Re in laminar flow.
- Velocity pressure
- For standard air, velocity pressure in inches of water equals the velocity in feet per minute divided by 4005, then squared; velocity equals 4005 times its square root.
- Hydraulic diameter
- Four times the flow area divided by the wetted perimeter; it extends round-duct friction and Reynolds number correlations to rectangular and annular ducts.
- NPSH available
- Atmospheric head minus vapor pressure head, plus static suction head, minus suction line losses; it must exceed the pump's required NPSH to prevent cavitation.
- Thermal resistance
- Conduction resistance equals thickness divided by conductivity and area; convection resistance equals one divided by coefficient and area; resistances in series add directly.
- Log mean temperature difference
- The difference of the two terminal temperature differences divided by the natural log of their ratio; counterflow arrangement produces the largest possible value.
- Effectiveness-NTU method
- Effectiveness is actual heat transfer divided by the thermodynamic maximum; it increases with NTU, defined as overall conductance divided by the minimum capacity rate.
- Critical insulation radius
- The outer insulation radius at which heat loss from a cylinder stops increasing, equal to insulation conductivity divided by the outside convection coefficient.
- Biot number
- The ratio of internal conduction resistance to surface convection resistance, equal to h times characteristic length over k; below 0.1 lumped capacitance is valid.
- Breathing-zone outdoor airflow
- The ASHRAE 62.1 rate equals the people component Rp times occupants plus the area component Ra times zone floor area, before correcting for zone air distribution.
- Economizer cycle
- A strategy that cools with outdoor air when its temperature or enthalpy is below the return-air value, reducing or eliminating mechanical cooling energy.
- VAV box minimum airflow
- The lowest airflow a variable-air-volume terminal delivers, set by ventilation and minimum cooling needs; higher minimums limit turndown and support system ventilation efficiency.
- Coil bypass factor
- The fraction of leaving air treated as missing the coil surface: leaving-air enthalpy minus apparatus dew point enthalpy, divided by the same difference for entering air.
- Vapor-compression COP
- Evaporator refrigerating effect divided by compressor work, computed as (h1 minus h4) over (h2 minus h1) using evaporator outlet, discharge, and expansion inlet enthalpies.
- Isenthalpic expansion
- The expansion valve drops refrigerant pressure at constant enthalpy, forming a liquid-vapor mixture at the evaporator inlet; flash gas reduces the net refrigerating effect.
- Condenser approach temperature
- Leaving condensing refrigerant temperature minus entering cooling-medium temperature; it indicates condenser cleanliness and runs roughly 1 to 3 F on clean water-cooled shells.
- Chiller kW per ton
- An efficiency measure equal to 3.517 divided by COP, or 12 divided by EER; lower values are better, and typical centrifugal chillers run about 0.5 to 0.6.