PE Mechanical flashcards
PE Mechanical · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ton of refrigeration
- Rate of heat removal equal to 12,000 Btu per hour, 200 Btu per minute, or 3.517 kilowatts; the standard basis for sizing cooling and refrigeration equipment.
- Sensible heat equation for air
- Qs equals 1.08 times cfm times the dry-bulb temperature difference in F, derived from 60 minutes per hour, 0.075 lb per cubic foot, and 0.24 Btu per lb-F.
- Fan affinity laws
- For a fixed fan and system, airflow varies directly with speed, static pressure with the square of speed, and brake horsepower with the cube of speed.
- Water flow heat equation
- Q in Btu per hour equals 500 times gallons per minute times the water temperature change in F, based on 8.33 lb per gallon and specific heat of 1.0.
- Standard air properties
- At 70 F and sea level, air has density 0.075 lb per cubic foot, specific heat 0.24 Btu per lb-F, and specific volume 13.3 cubic feet per pound of dry air.
- Humidity ratio formula
- W equals 0.622 times water vapor partial pressure divided by total pressure minus vapor pressure, giving pounds of water per pound of dry air.
- Moist air enthalpy
- Enthalpy equals 0.240T plus W times (1061 plus 0.444T) in Btu per pound of dry air, where T is dry-bulb temperature in F.
- Coil bypass factor
- Fraction of entering air that leaves a cooling coil untreated; leaving enthalpy equals apparatus dew point plus bypass factor times the entering-to-ADP enthalpy difference.
- Sensible heat ratio
- Sensible load divided by total load for a space or coil; it fixes the slope of the process line on the psychrometric chart.
- Relative humidity
- Water vapor partial pressure divided by the saturation vapor pressure at the same dry-bulb temperature, expressed as a percent; it depends on both moisture content and temperature.
- Conduction heat transfer equation
- Q equals U times area times temperature difference; the U-factor is the reciprocal of total R-value including surface films and each assembly layer.
- CLTD cooling load method
- Estimates envelope load as U times area times a corrected cooling load temperature difference, adjusted for latitude, month, wall color, and indoor-outdoor temperature swing.
- Ventilation latent load
- QL equals about 4,840 times cfm times the humidity ratio difference, or roughly 0.68 times cfm times the difference in grains per pound.
- Heating degree days
- Sum over the heating season of 65 F minus the daily mean outdoor temperature for days below the balance point; used to estimate annual heating energy.
- Internal heat gain from lighting
- All lighting wattage inside a conditioned space becomes heat at 3.412 Btu per hour per watt; a portion is radiant and appears as load after a time lag.
- Sensible effectiveness
- For an energy recovery device, the temperature change of one airstream divided by the maximum possible difference between the two entering airstreams.
- Enthalpy wheel
- Rotary total-energy exchanger that transfers both sensible heat and moisture between airstreams, typically achieving total effectiveness between 50 and 80 percent.
- Runaround coil energy recovery
- Two coils joined by a pumped glycol loop that transfers sensible heat only; there is no cross-contamination and the airstreams may be located far apart.
- Latent effectiveness
- Change in humidity ratio of the supply airstream divided by the maximum humidity ratio difference between the entering exhaust and outside airstreams.
- Cooling tower approach
- Leaving condenser water temperature minus entering wet-bulb temperature; a smaller approach requires a larger tower but lowers chiller condensing temperature and power.
- Chiller efficiency kW per ton
- Compressor input power per ton of cooling; it equals 12 divided by EER, and COP equals 3.412 divided by the kW-per-ton value.
- Duct velocity pressure
- For standard air, velocity pressure in inches of water equals duct velocity in feet per minute divided by 4,005, with the quotient then squared.
- VAV terminal minimum airflow
- Lowest airflow setting of a variable air volume box, established by ventilation requirements, box turndown, and diffuser throw rather than by space load.
- Air-side economizer
- Uses cool outside air for free cooling when its temperature or enthalpy is below the return air, modulating dampers and reducing or stopping mechanical cooling.
- Carnot refrigeration COP
- Maximum coefficient of performance between a cold region at TL and a warm region at TH, both absolute: TL divided by (TH minus TL).
- Thermostatic expansion valve
- Meters refrigerant into the evaporator to hold a nearly constant superheat at the outlet, modulating in response to bulb temperature and evaporator pressure.
- Subcooling
- Liquid refrigerant temperature below the saturation temperature at condenser pressure; it increases refrigeration effect and prevents flash gas ahead of the expansion valve.
- Refrigerant temperature glide
- Difference between bubble and dew point temperatures of a zeotropic blend at a given pressure; it complicates charging, leak detection, and coil design.
- Proportional band
- The error span, expressed as a percent of sensor range, over which a proportional controller moves its output from minimum to maximum.
- Integral control action
- Controller output changes in proportion to the accumulated error over time; this eliminates steady-state offset but slows response and can cause overshoot.
- RTD versus thermistor
- Resistance temperature detectors use platinum and are stable and near-linear; thermistors are cheaper and more sensitive but nonlinear and limited in temperature range.
- Offset in proportional control
- Steady-state deviation from setpoint that persists with proportional-only control because a nonzero error is required to hold the output at the load value.