FSOE Qualifying Test · Keep the key ideas within reach.

Quick reference

Functional safety fundamentals and standards context

  • IEC 61508 is the generic functional safety standard; it defines SIL 1-4, the safety lifecycle, hardware fault tolerance, safe failure fraction, and PFH/PFDavg concepts.

  • IEC 61784-3 defines functional safety fieldbus profiles; IEC 61784-3-12 is CPF 12, the profile for Safety over EtherCAT (FSoE).

  • IEC 62061 is the machinery sector standard using SIL 1-3; it is derived from IEC 61508 and applies to safety-related control systems.

  • ISO 13849-1 is the machinery sector standard using Performance Levels PL a-e; it uses category, MTTFd, DCavg, and CCF.

  • IEC 62061 and ISO 13849-1 are alternative routes for machinery; a given safety function should be designed to one method, not mixed arbitrarily.

  • Approximate mapping: PL e corresponds to SIL 3, PL d to SIL 2, and PL c to SIL 1; the mapping is not an exact equivalence.

  • FSoE communication can support SIL 3 per IEC 61508 and PL e per ISO 13849-1 when the devices, architecture, and integration are suitably qualified.

  • The black channel principle from IEC 61784-3 places all safety measures in the safety layer; the underlying fieldbus is assumed to be non-safe.

  • IEC 61784-3 specifies residual error probability requirements; FSoE meets them using CRC, sequence monitoring, timeouts, watchdog, and connection ID checks.

Quick reference

Safety over EtherCAT architecture

  • Black channel: FSoE treats EtherCAT as an unsecured transport; all safety-related error detection is implemented in the FSoE layer, so EtherCAT itself need not be safety-certified.

  • FSoE master: typically resides in the safety controller or safety PLC; it initiates and controls the FSoE state machine, sends commands and safe outputs, and monitors slave responses.

  • FSoE slave: resides in the field device such as a drive, I/O module, or sensor; it responds to master commands, validates CRC, connection ID, and watchdog, and drives safe outputs.

  • Safety stack placement: the FSoE slave stack sits above the EtherCAT slave stack and below the safety application; it handles FSoE frames, state machine, CRC, watchdog, and safe data mapping.

  • On the master side, the FSoE master stack is part of the safety runtime and exchanges safe process data with the safety application.

  • FSoE frames are embedded in EtherCAT process data for cyclic safe exchange; the EtherCAT mailbox carries non-safety diagnostics and parameters such as CoE objects.

  • Safe data container: the FSoE payload carries mapped safe inputs and outputs; EtherCAT transports it but does not interpret the safety content.

  • FSoE master and slave both run the FSoE state machine; the master sends the Data command cyclically, and the slave returns safe input data in its response.

  • A device safety stack may be certified as a unit for SIL 3 capability; integration must still verify its placement, interfaces, and configuration consistency.

Quick reference

FSoE frame structure and data coding

  • FSoE frame layout: 6-byte header = Command (2 bytes) + CRC_0 (2 bytes) + Connection ID (2 bytes); then safe data of configured length; then CRC_1 (2 bytes).

  • Command field: 2 bytes; the lower byte carries the command code (0x01 Reset, 0x02 Session, 0x03 Connection, 0x04 Parameter, 0x05 Data, 0x06 FailSafe); the upper byte is reserved.

  • CRC_0 is a 16-bit CRC protecting the header, including the command and connection ID; CRC_1 is a 16-bit CRC protecting the safe data field.

  • Connection ID: a 16-bit identifier carried in every FSoE frame; the slave compares it with its configured value and rejects a mismatch as an error.

  • Safe data container: the data field that carries the mapped safe inputs and outputs; its length is fixed by configuration and must match at master and slave.

  • FSoE address: a 16-bit address identifying the FSoE slave or connection; it is used by the master to route frames and must be unique on the network.

  • Data coding: safe data is bit- or byte-mapped without implicit scaling; the mapping must be identical in master and slave configuration.

  • Frame check order at the receiver: command validity, CRC_0, connection ID, CRC_1, data length, sequence, and watchdog.

  • Changing the safe data length or mapping changes the connection configuration and requires matching updates at both ends.

Quick reference

FSoE state machine and communication phases

  • FSoE states: Reset, Session, Connection, Parameter, Data, and FailSafe.

  • Reset: communication is not established; the slave holds outputs in the safe state; the master sends Reset to start or restart the connection.

  • Session: master and slave establish a session and check addressing; no cyclic safe data is exchanged yet.

  • Connection: the master sends the Connection command with the connection ID; the slave validates it and acknowledges, establishing the connection.

  • Parameter: safety parameters such as watchdog time, data length, and mapping are exchanged and validated before data exchange.

  • Data: cyclic exchange of safe process data; the master sends outputs, the slave returns inputs, and sequence and watchdog are monitored.

  • FailSafe: entered on communication error, watchdog timeout, or a FailSafe command; the slave sets outputs to safe values and requires a Reset to exit.

  • State transitions are controlled by master commands; the slave transitions only on a valid command with correct CRC and connection ID.

  • Normal phase order is Session -> Connection -> Parameter -> Data; any error can force FailSafe, and recovery requires Reset.

Quick reference

Error detection and residual-error measures

  • Sequence monitoring: FSoE data frames carry an incrementing counter; the receiver checks the expected increment and detects lost, duplicated, or out-of-order frames.

  • Watchdog: the slave restarts a timer on each valid FSoE frame; if no valid frame arrives within the configured watchdog time, the slave enters FailSafe.

  • Timeouts: the master also monitors slave responses; a missing or late response within the configured timeout triggers a fail-safe reaction.

  • Addressing checks: the FSoE address and connection ID ensure a frame belongs to the correct connection; wrong address or ID is rejected.

  • Data integrity: CRC_0 detects header corruption and CRC_1 detects safe data corruption; a CRC failure causes the frame to be discarded and an error to be counted.

  • Length check: the receiver verifies that the safe data length matches the configured length; a mismatch is treated as an error.

  • Command check: the receiver verifies that the command is valid for the current state; an invalid command leads to an error or FailSafe.

  • IEC 61784-3 residual error measures combine CRC, sequence monitoring, timeouts, watchdog, and connection ID checks to achieve the required residual error probability.

  • FSoE slaves maintain error counters for CRC, sequence, watchdog, and connection errors to support diagnostics and fault tracing.

Quick reference

FSoE configuration parameters

  • FSoE address: a 16-bit unique address per FSoE slave; it is configured in master and slave, and a mismatch prevents connection establishment.

  • Watchdog time: configured in milliseconds; it must exceed the EtherCAT cycle time plus jitter; too short causes spurious fail-safe, too long increases reaction time.

  • Connection ID: a 16-bit value configured for the connection; master and slave must match, and it is checked on every frame.

  • Slave-to-slave communication: one FSoE slave consumes safe data directly from another slave using the source FSoE address and connection ID; the master configures it but may not be in the data path.

  • Mapping of safe inputs and outputs: safe data container bits or bytes are assigned to device I/O; the mapping must be identical in master and slave configuration.

  • Data length: the configured length of the safe data container is fixed per connection and must match at both ends.

  • Fail-safe values: the safe state for each output, such as 0 or de-energized, is defined per output and applied on communication loss.

  • FSoE master configuration includes the slave list, FSoE addresses, watchdog times, connection IDs, and safe I/O mapping, stored in the safety controller.

  • The Parameter phase exchanges and validates safety parameters such as watchdog time, data length, and mapping before the Data phase begins.

Quick reference

Diagnostics, fault tracing and conformance testing

  • FSoE slave diagnostics report error codes for watchdog, CRC, sequence, connection ID, command, and parameter errors; these are read via EtherCAT CoE or process data.

  • Fault tracing order: check FSoE address and connection ID mismatch first, then watchdog time versus cycle time, then CRC errors from EMI or wiring, then sequence errors from frame loss.

  • EtherCAT diagnostics: use topology, link status, working counter, and CoE error objects to isolate network faults that affect FSoE.

  • FSoE error counters track CRC errors, sequence errors, watchdog errors, and connection errors; counters are cleared only after the fault is resolved.

  • ETG conformance testing for FSoE verifies the state machine, frame handling, CRC, watchdog, error reactions, and fail-safe behavior against the FSoE specification.

  • Fault injection testing introduces CRC errors, dropped frames, delayed frames, and wrong connection IDs to confirm the slave reacts safely within the watchdog time.

  • Network conformance: verify that EtherCAT cycle time, jitter, and topology support the configured FSoE watchdog time and that FSoE frames fit the process data.

  • If all FSoE slaves fail simultaneously, suspect the master or network; if one slave fails, suspect that slave's configuration, wiring, or device fault.

  • Conformance documentation should record test cases, error injection results, configuration records, and the conformance certificate.

Quick reference

Integration, verification and validation

  • Risk assessment inputs: required SIL or PL, safety function response time, safe state definition, proof test interval, architecture (HFT), and common cause requirements.

  • SIL/PL verification: calculate PFH or PFDavg for the complete safety function including FSoE communication; use device safety data such as PFH, MTTFd, and DC.

  • FSoE contribution: treat FSoE as part of the safety function; use its residual error rate and watchdog time in the response time and integrity calculations.

  • Response time: worst case = sensor delay + FSoE cycle(s) + watchdog time + actuator delay; this must be less than the process safety time.

  • Proof tests: periodic tests detect dangerous undetected failures; for FSoE include communication fault injection and device proof tests per the safety manual.

  • Validation: functionally test each safety function, including FSoE fault injection for CRC, timeout, and connection ID errors, to confirm the specified safe reaction.

  • Documentation: safety requirements specification, configuration records, verification and validation report, proof test records, and the device safety manual.

  • Modification rule: any change to FSoE address, mapping, watchdog time, or firmware requires impact analysis and re-verification.

  • Integration checks: confirm FSoE stack certification, correct stack placement, mapping consistency, and that non-safe EtherCAT faults cannot defeat the safety measures.