Electrical Power Systems Analysis and Design

  • Per-unit value = actual value ÷ base value; base impedance Z_base = V_base² / S_base (line-to-line kV and three-phase MVA).

  • For a three-phase balanced load: S = √3·V_LL·I_L, P = √3·V_LL·I_L·cos φ, Q = √3·V_LL·I_L·sin φ.

  • Voltage regulation (%) = (|V_no-load| − |V_full-load|) / |V_full-load| × 100.

  • Complex power S = P + jQ = V·I*; total load power factor is set by the phasor sum of all P and Q, not by averaging individual power factors.

  • Fault level (short-circuit MVA) = √3·V_LL·I_fault; a higher fault level means lower source impedance.

  • Symmetrical components: positive (1), negative (2), zero (0) sequence; a single line-to-ground fault involves all three sequences in series.

  • Power factor correction capacitor kVAR = P·(tan φ₁ − tan φ₂), where φ₁ and φ₂ are the initial and target power-factor angles.

  • In per-unit, transformer turns ratio is 1:1 when bases are chosen on each side of the transformer, which removes ratio errors from calculations.

Quick reference

Power Generation, Transmission, and Distribution

  • Thermal plant efficiency = (net work output) / (heat input); overall plant efficiency = electrical output / fuel energy input.

  • Rankine cycle efficiency is raised by higher steam pressure/temperature and by lowering condenser pressure (reducing heat rejection temperature).

  • Transmission line surge impedance Z_c = √(L/C); surge impedance loading SIL = V_LL² / Z_c.

  • Short line (<80 km): series impedance only. Medium line (80–250 km): nominal π or T model. Long line (>250 km): distributed ABCD (hyperbolic) parameters.

  • Skin effect increases AC resistance above DC resistance; it is significant at high frequency and in large conductors.

  • Ferranti effect: on a lightly loaded or open-circuit long line, receiving-end voltage rises above sending-end voltage.

  • Distribution feeders are typically radial; voltage drop ≈ I·(R cos φ + X sin φ) per phase for a short feeder.

  • Power transfer over a line P ≈ (V_S·V_R / X)·sin δ, so angle δ (not resistance) governs steady-state transfer for high-X lines.

Quick reference

Electrical Machines and Transformers

  • Transformer EMF equation: E = 4.44·f·N·Φ_max (RMS); induced EMF is proportional to frequency, turns, and peak flux.

  • Ideal transformer: V₁/V₂ = N₁/N₂ = I₂/I₁; VA rating is the same on both sides (neglecting losses).

  • Synchronous speed N_s = 120·f / P (rpm), where P is the number of poles.

  • Induction motor slip s = (N_s − N_r)/N_s; rotor frequency f_r = s·f.

  • Torque of an induction motor T ∝ (rotor input power)/slip; maximum torque occurs at slip where rotor resistance equals rotor reactance.

  • DC machine EMF: E = (P·Φ·N·Z)/(60·A) for a generator; for a motor E is back-EMF and armature current I_a = (V − E)/R_a.

  • Transformer losses: copper loss ∝ I² (varies with load), core loss is approximately constant; maximum efficiency occurs when copper loss equals core loss.

  • Open-circuit and short-circuit tests on a transformer give core (shunt) parameters and series (copper) parameters respectively.

Quick reference

Power Electronics and Drives

  • Single-phase full-wave rectifier (uncontrolled): average DC output V_dc = 2·V_m/π; RMS output = V_m/√2.

  • Controlled rectifier average output V_dc = (2·V_m/π)·cos α for a full converter with firing angle α.

  • Thyristor conducts only when anode is positive relative to cathode AND a gate pulse is applied; it turns off when current falls below holding current.

  • DC chopper output: buck V_o = D·V_in; boost V_o = V_in/(1 − D), where D is duty cycle.

  • Inverter output frequency and voltage are set by switching pattern; V/f control keeps air-gap flux constant in induction motor drives.

  • PWM inverters reduce low-order harmonics; increasing switching frequency moves harmonics higher and eases filtering.

  • Freewheeling (flyback) diode protects switches from inductive kickback and provides a current path during switch-off.

  • Variable frequency drive (VFD) energy saving follows affinity laws: flow ∝ speed, power ∝ speed³ for centrifugal pumps and fans.

Quick reference

Electrical Installations in Buildings

  • Design current I_b ≤ protective device rating I_n ≤ cable current-carrying capacity I_z.

  • Voltage drop limit for a final circuit is commonly 3% of nominal voltage (5% for the whole installation from origin).

  • Cable current-carrying capacity is corrected by factors for ambient temperature, grouping, and thermal insulation.

  • Earth fault loop impedance must satisfy Z_s ≤ (nominal voltage) / (protective device operating current) to ensure disconnection in time.

  • Diversity factor = maximum demand of an installation / sum of individual maximum demands; applied to size service and feeder.

  • Socket outlets and lighting are typically split across separate final circuits to limit inconvenience and load per circuit.

  • Bathroom and wet-location zones restrict socket placement and require supplementary equipotential bonding.

  • RCD (residual current device) rated 30 mA is used for additional protection against electric shock in many final circuits.

Quick reference

Protection, Earthing, and Lightning Systems

  • Protective relay must be selective, fast, sensitive, and reliable; grading margin between upstream and downstream devices ensures selectivity.

  • Overcurrent relay characteristic: inverse, very inverse, and extremely inverse curves define time-versus-current response.

  • IDMT relay operating time t = TMS · k / (I/Is)^α − 1, where TMS is the time multiplier setting.

  • Differential protection compares currents entering and leaving a protected zone; it is used for transformers, generators, and busbars.

  • Earth resistance is measured by the fall-of-potential (three-point) method; lower earth resistance improves fault current return.

  • Lightning protection system consists of air termination, down conductor, and earth termination; rolling sphere and protection angle methods define the zone of protection.

  • Surge protective devices (SPDs) divert transient overvoltages to earth and are coordinated in Type 1, 2, and 3 stages.

  • Touch voltage is the potential difference a person may bridge; step voltage is the potential difference between feet on the ground.

Quick reference

Electrical Codes, Standards, and Regulations

  • Codes and standards are mandatory when adopted by regulation; standards become enforceable through reference in law or contract.

  • Standard voltage tolerances: supply voltage typically maintained within ±6% to ±10% of nominal, depending on the national code.

  • Conductor sizing considers ampacity, voltage drop, short-circuit withstand, and mechanical strength - all must be satisfied.

  • Earthing conductor cross-section is governed by the phase conductor size and the required fault-current withstand.

  • Classification of hazardous areas (zones 0, 1, 2 for gas; 20, 21, 22 for dust) determines the equipment protection level required.

  • Inspection and testing of an installation includes continuity, insulation resistance, polarity, earth loop impedance, and RCD trip tests.

  • Degree of protection (IP) code: first digit = solids, second digit = liquids; higher digits indicate greater protection.

Quick reference

Health, Safety, and Environmental Practice

  • Lockout/tagout (LOTO) isolates energy sources and prevents unexpected energization during maintenance.

  • Live working requires a permit, insulated tools, and appropriate PPE; de-energization is the default safe practice.

  • Arc flash hazard is characterized by incident energy (cal/cm²) and arc flash boundary; PPE category is selected from incident energy.

  • Approach boundaries (limited, restricted) define how close an unqualified or qualified person may come to exposed live parts.

  • Electric shock severity depends on current magnitude and duration; ventricular fibrillation risk rises sharply above about 30 mA for prolonged exposure.

  • Safety signs follow a colour code: red = prohibition/fire, yellow = warning, blue = mandatory, green = safe condition/first aid.

  • Environmental controls address SF6 handling (high global warming potential), oil spill containment, and disposal of lamps containing mercury.

Quick reference

Project Management, Contracts, and Engineering Ethics

  • Critical path is the longest-duration path through the network; it determines the minimum project duration and has zero float.

  • Earned value: CV = EV − AC; SV = EV − PV; CPI = EV/AC; SPI = EV/PV.

  • Float (slack) = late start − early start = late finish − early finish; activities on the critical path have zero total float.

  • Common contract types: lump-sum (fixed price), unit-price (re-measured), and cost-plus (cost reimbursable); risk allocation differs by type.

  • A variation order changes scope, time, or price and must be authorized in writing before work proceeds.

  • Professional ethics require competence within one's field, disclosure of conflicts of interest, and protection of public safety, health, and welfare.

  • A bill of quantities supports unit-price contracts; a lump-sum contract prices the whole defined scope.

Quick reference

Renewable Energy and Energy Efficiency

  • Solar PV power P = G·A·η, where G is irradiance (W/m²), A is array area, and η is module efficiency.

  • PV module temperature coefficient: output falls as cell temperature rises; typical power coefficient is about −0.3% to −0.5% per °C.

  • Wind turbine power P = ½·ρ·A·v³·Cp, where ρ is air density, A is swept area, v is wind speed, and Cp is the power coefficient (Betz limit 0.593).

  • Energy payback and capacity factor: capacity factor = actual energy output / (rated power × hours in period).

  • LED lighting efficiency is expressed in lumens per watt (lm/W); higher efficacy means more light per unit electrical power.

  • Power factor correction and harmonic filtering reduce losses and improve efficiency in industrial installations.

  • Load shifting and demand-side management reduce peak demand charges without reducing total energy consumption.

  • Betz limit states no wind turbine can extract more than 59.3% of the kinetic energy in the wind stream.

Quick reference

Electrical Power Systems Analysis and Design

  • Per-unit value = actual value ÷ base value; base impedance Z_base = V_base² / S_base (line-to-line kV and three-phase MVA).

  • For a three-phase balanced load: S = √3·V_LL·I_L, P = √3·V_LL·I_L·cos φ, Q = √3·V_LL·I_L·sin φ.

  • Voltage regulation (%) = (|V_no-load| − |V_full-load|) / |V_full-load| × 100.

  • Complex power S = P + jQ = V·I*; total load power factor is set by the phasor sum of all P and Q, not by averaging individual power factors.

  • Fault level (short-circuit MVA) = √3·V_LL·I_fault; a higher fault level means lower source impedance.

  • Symmetrical components: positive (1), negative (2), zero (0) sequence; a single line-to-ground fault involves all three sequences in series.

  • Power factor correction capacitor kVAR = P·(tan φ₁ − tan φ₂), where φ₁ and φ₂ are the initial and target power-factor angles.

  • In per-unit, transformer turns ratio is 1:1 when bases are chosen on each side of the transformer, which removes ratio errors from calculations.

Quick reference

Power Generation, Transmission, and Distribution

  • Thermal plant efficiency = (net work output) / (heat input); overall plant efficiency = electrical output / fuel energy input.

  • Rankine cycle efficiency is raised by higher steam pressure/temperature and by lowering condenser pressure (reducing heat rejection temperature).

  • Transmission line surge impedance Z_c = √(L/C); surge impedance loading SIL = V_LL² / Z_c.

  • Short line (<80 km): series impedance only. Medium line (80–250 km): nominal π or T model. Long line (>250 km): distributed ABCD (hyperbolic) parameters.

  • Skin effect increases AC resistance above DC resistance; it is significant at high frequency and in large conductors.

  • Ferranti effect: on a lightly loaded or open-circuit long line, receiving-end voltage rises above sending-end voltage.

  • Distribution feeders are typically radial; voltage drop ≈ I·(R cos φ + X sin φ) per phase for a short feeder.

  • Power transfer over a line P ≈ (V_S·V_R / X)·sin δ, so angle δ (not resistance) governs steady-state transfer for high-X lines.

Quick reference

Electrical Machines and Transformers

  • Transformer EMF equation: E = 4.44·f·N·Φ_max (RMS); induced EMF is proportional to frequency, turns, and peak flux.

  • Ideal transformer: V₁/V₂ = N₁/N₂ = I₂/I₁; VA rating is the same on both sides (neglecting losses).

  • Synchronous speed N_s = 120·f / P (rpm), where P is the number of poles.

  • Induction motor slip s = (N_s − N_r)/N_s; rotor frequency f_r = s·f.

  • Torque of an induction motor T ∝ (rotor input power)/slip; maximum torque occurs at slip where rotor resistance equals rotor reactance.

  • DC machine EMF: E = (P·Φ·N·Z)/(60·A) for a generator; for a motor E is back-EMF and armature current I_a = (V − E)/R_a.

  • Transformer losses: copper loss ∝ I² (varies with load), core loss is approximately constant; maximum efficiency occurs when copper loss equals core loss.

  • Open-circuit and short-circuit tests on a transformer give core (shunt) parameters and series (copper) parameters respectively.

Quick reference

Power Electronics and Drives

  • Single-phase full-wave rectifier (uncontrolled): average DC output V_dc = 2·V_m/π; RMS output = V_m/√2.

  • Controlled rectifier average output V_dc = (2·V_m/π)·cos α for a full converter with firing angle α.

  • Thyristor conducts only when anode is positive relative to cathode AND a gate pulse is applied; it turns off when current falls below holding current.

  • DC chopper output: buck V_o = D·V_in; boost V_o = V_in/(1 − D), where D is duty cycle.

  • Inverter output frequency and voltage are set by switching pattern; V/f control keeps air-gap flux constant in induction motor drives.

  • PWM inverters reduce low-order harmonics; increasing switching frequency moves harmonics higher and eases filtering.

  • Freewheeling (flyback) diode protects switches from inductive kickback and provides a current path during switch-off.

  • Variable frequency drive (VFD) energy saving follows affinity laws: flow ∝ speed, power ∝ speed³ for centrifugal pumps and fans.

Quick reference

Electrical Installations in Buildings

  • Design current I_b ≤ protective device rating I_n ≤ cable current-carrying capacity I_z.

  • Voltage drop limit for a final circuit is commonly 3% of nominal voltage (5% for the whole installation from origin).

  • Cable current-carrying capacity is corrected by factors for ambient temperature, grouping, and thermal insulation.

  • Earth fault loop impedance must satisfy Z_s ≤ (nominal voltage) / (protective device operating current) to ensure disconnection in time.

  • Diversity factor = maximum demand of an installation / sum of individual maximum demands; applied to size service and feeder.

  • Socket outlets and lighting are typically split across separate final circuits to limit inconvenience and load per circuit.

  • Bathroom and wet-location zones restrict socket placement and require supplementary equipotential bonding.

  • RCD (residual current device) rated 30 mA is used for additional protection against electric shock in many final circuits.

Quick reference

Protection, Earthing, and Lightning Systems

  • Protective relay must be selective, fast, sensitive, and reliable; grading margin between upstream and downstream devices ensures selectivity.

  • Overcurrent relay characteristic: inverse, very inverse, and extremely inverse curves define time-versus-current response.

  • IDMT relay operating time t = TMS · k / (I/Is)^α − 1, where TMS is the time multiplier setting.

  • Differential protection compares currents entering and leaving a protected zone; it is used for transformers, generators, and busbars.

  • Earth resistance is measured by the fall-of-potential (three-point) method; lower earth resistance improves fault current return.

  • Lightning protection system consists of air termination, down conductor, and earth termination; rolling sphere and protection angle methods define the zone of protection.

  • Surge protective devices (SPDs) divert transient overvoltages to earth and are coordinated in Type 1, 2, and 3 stages.

  • Touch voltage is the potential difference a person may bridge; step voltage is the potential difference between feet on the ground.

Quick reference

Electrical Codes, Standards, and Regulations

  • Codes and standards are mandatory when adopted by regulation; standards become enforceable through reference in law or contract.

  • Standard voltage tolerances: supply voltage typically maintained within ±6% to ±10% of nominal, depending on the national code.

  • Conductor sizing considers ampacity, voltage drop, short-circuit withstand, and mechanical strength - all must be satisfied.

  • Earthing conductor cross-section is governed by the phase conductor size and the required fault-current withstand.

  • Classification of hazardous areas (zones 0, 1, 2 for gas; 20, 21, 22 for dust) determines the equipment protection level required.

  • Inspection and testing of an installation includes continuity, insulation resistance, polarity, earth loop impedance, and RCD trip tests.

  • Degree of protection (IP) code: first digit = solids, second digit = liquids; higher digits indicate greater protection.

Quick reference

Health, Safety, and Environmental Practice

  • Lockout/tagout (LOTO) isolates energy sources and prevents unexpected energization during maintenance.

  • Live working requires a permit, insulated tools, and appropriate PPE; de-energization is the default safe practice.

  • Arc flash hazard is characterized by incident energy (cal/cm²) and arc flash boundary; PPE category is selected from incident energy.

  • Approach boundaries (limited, restricted) define how close an unqualified or qualified person may come to exposed live parts.

  • Electric shock severity depends on current magnitude and duration; ventricular fibrillation risk rises sharply above about 30 mA for prolonged exposure.

  • Safety signs follow a colour code: red = prohibition/fire, yellow = warning, blue = mandatory, green = safe condition/first aid.

  • Environmental controls address SF6 handling (high global warming potential), oil spill containment, and disposal of lamps containing mercury.

Quick reference

Project Management, Contracts, and Engineering Ethics

  • Critical path is the longest-duration path through the network; it determines the minimum project duration and has zero float.

  • Earned value: CV = EV − AC; SV = EV − PV; CPI = EV/AC; SPI = EV/PV.

  • Float (slack) = late start − early start = late finish − early finish; activities on the critical path have zero total float.

  • Common contract types: lump-sum (fixed price), unit-price (re-measured), and cost-plus (cost reimbursable); risk allocation differs by type.

  • A variation order changes scope, time, or price and must be authorized in writing before work proceeds.

  • Professional ethics require competence within one's field, disclosure of conflicts of interest, and protection of public safety, health, and welfare.

  • A bill of quantities supports unit-price contracts; a lump-sum contract prices the whole defined scope.

Quick reference

Renewable Energy and Energy Efficiency

  • Solar PV power P = G·A·η, where G is irradiance (W/m²), A is array area, and η is module efficiency.

  • PV module temperature coefficient: output falls as cell temperature rises; typical power coefficient is about −0.3% to −0.5% per °C.

  • Wind turbine power P = ½·ρ·A·v³·Cp, where ρ is air density, A is swept area, v is wind speed, and Cp is the power coefficient (Betz limit 0.593).

  • Energy payback and capacity factor: capacity factor = actual energy output / (rated power × hours in period).

  • LED lighting efficiency is expressed in lumens per watt (lm/W); higher efficacy means more light per unit electrical power.

  • Power factor correction and harmonic filtering reduce losses and improve efficiency in industrial installations.

  • Load shifting and demand-side management reduce peak demand charges without reducing total energy consumption.

  • Betz limit states no wind turbine can extract more than 59.3% of the kinetic energy in the wind stream.