R-410A flashcards
R-410A · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- R-410A composition
- A near-azeotropic blend of 50% R-32 (difluoromethane) and 50% R-125 (pentafluoroethane) by mass, with a temperature glide of only about 0.1 to 0.2 K.
- R-410A atmospheric boiling point
- At one atmosphere R-410A boils at about -51.4 °C (-60.6 °F), so at any given temperature its pressure is far higher than that of R-22.
- R-410A pressure at 38 °C
- Saturation pressure at 38 °C (100 °F) is roughly 317 psig (2185 kPa gauge), about 60% higher than R-22 under the same conditions, which drives component pressure ratings.
- R-410A ASHRAE A1 rating
- R-410A is class A1: low toxicity and no flame propagation in standard tests. It is still an asphyxiant, and liquid contact can cause frostbite or eye injury.
- POE oil moisture absorption
- Polyolester lubricant used with R-410A is highly hygroscopic; it absorbs moisture in minutes, forming acids and sludge that damage compressor windings and block small passages.
- Section 608 certification
- US EPA certification under Section 608 of the Clean Air Act is required before a technician may service, maintain, repair, or dispose of equipment containing ozone-depleting refrigerants or their HFC substitutes.
- Venting prohibition
- Knowingly venting CFC, HCFC, or HFC refrigerant to the atmosphere is illegal; the refrigerant must be recovered and then recycled, reclaimed, or destroyed.
- Leak rate thresholds
- EPA thresholds that trigger mandatory repair are 10% per year for comfort cooling, 20% for commercial refrigeration, and 30% for industrial process refrigeration appliances.
- Recordkeeping requirement
- Refrigerant purchase records, service logs, and leak repair verification documents must be kept for at least three years and made available to EPA on request.
- Four main cycle components
- The compressor raises pressure and temperature, the condenser rejects heat and condenses the vapor, the metering device drops pressure, and the evaporator absorbs heat and boils the refrigerant.
- Superheat definition
- Superheat equals the actual suction line temperature minus the saturated suction temperature at the measured pressure; it confirms that only vapor leaves the evaporator.
- Subcooling definition
- Subcooling equals the saturated condensing temperature at the measured head pressure minus the liquid line temperature; it confirms solid liquid reaches the metering device.
- Compression ratio formula
- Compression ratio is absolute discharge pressure divided by absolute suction pressure, expressed in psia or kPa absolute; gauge readings must be converted before dividing.
- Nitrogen purge while brazing
- Dry nitrogen must flow through the tubing at about 1 to 2 SCFH during brazing so internal copper oxide scale does not form and later clog driers and valves.
- Micron evacuation target
- A tight system is evacuated to 500 microns (0.5 mm Hg) or lower; one atmosphere equals 760 mm Hg, or 760,000 microns.
- Standing vacuum decay test
- After reaching 500 microns, isolate the pump and hold 10 to 15 minutes; a rise above roughly 1000 microns indicates a leak, moisture, or outgassing.
- Triple evacuation procedure
- Evacuate, break the vacuum with dry nitrogen, and repeat three times; the nitrogen sweeps moisture out when the vacuum will not hold or the system was opened.
- Pressure testing safety
- Dry nitrogen is the only acceptable test gas; oxygen or air mixed with refrigerant oil can detonate, and acetylene must never be used for pressure testing.
- Weigh-in charging
- The most accurate method is charging liquid refrigerant by weight on a scale, using the nameplate charge plus any adjustment for line length or added components.
- Charging by subcooling
- Systems with a TXV are charged to the manufacturer's target subcooling, typically 8 to 12 °F (4 to 7 K) at the liquid line, at design indoor and outdoor conditions.
- Charging by superheat
- Fixed-orifice systems are charged to a target superheat taken from the manufacturer's chart, using indoor wet-bulb and outdoor dry-bulb temperatures.
- Liquid-only R-410A charging
- R-410A must always be charged as a liquid; drawing vapor from the cylinder fractionates the blend and changes the R-32 to R-125 ratio and the system's performance.
- High head pressure causes
- Dirty or blocked condenser coils, overcharge, non-condensable air, high ambient temperature, and a failed condenser fan all raise discharge pressure above normal.
- Recovery cylinder 80% limit
- A recovery cylinder may never be filled above 80% of its capacity by weight; liquid expansion at higher temperatures can rupture a full cylinder, so a scale must be used.
- Recovery recycling reclamation
- Recovery is removal of refrigerant into a cylinder; recycling is on-site cleaning with oil separation and filter-driers; reclamation is off-site reprocessing to AHRI 700 purity.
- AHRI 700 purity standard
- AHRI Standard 700 sets the purity and composition limits for reclaimed refrigerant, and only an EPA-certified reclaimer with laboratory analysis can certify it.
- Never mix refrigerants
- Mixing different refrigerants in one cylinder creates an unidentifiable blend that cannot be reclaimed and may not be reused; keep each refrigerant in its own cylinder.
- Recovery cylinder identification
- DOT recovery cylinders are usually gray with a yellow top and must carry current hydrostatic test dates; virgin R-410A cylinders are rose colored and are never used for recovery.
- AIM Act phasedown schedule
- The US AIM Act caps HFC production and consumption, stepping down 10% in 2022, 40% in 2023, 70% in 2029, 80% in 2034, and 85% by 2036.
- A2L classification
- A2L refrigerants have low toxicity and mild flammability with burning velocity at or below 10 cm/s, requiring charge limits, leak detection, and ignition-source control.
- R-454B composition and GWP
- R-454B is a near-azeotropic blend of about 68.9% R-32 and 31.1% R-1234yf with a 100-year GWP near 466, roughly one-fifth that of R-410A.
- R-410A GWP value
- R-410A has a 100-year GWP of 2088 (IPCC AR4) and zero ozone depletion potential; its high GWP is the reason for the transition to lower-GWP alternatives.