TX Fire Alarm Installer study materials
TX Fire Alarm Installer study resources

TX Fire Alarm Installer flashcards

TX Fire Alarm Installer · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

NFPA 72
National Fire Alarm and Signaling Code; it establishes design, installation, testing, and maintenance requirements for fire alarm and emergency signaling systems in buildings.
NEC Article 760
National Electrical Code article covering fire alarm systems; it governs wiring methods, conductors, and circuit requirements for fire alarm and signaling circuits.
Texas fire alarm license
Credential issued through the Texas Department of Insurance State Fire Marshal's Office that authorizes regulated fire alarm installation work; local permits may still be required.
Authority having jurisdiction
Official or agency responsible for enforcing code and approving fire alarm plans, installations, and acceptance tests; may adopt local amendments to model codes.
Alarm signal
Fire alarm signal indicating a detected fire emergency; it activates notification appliances and is distinct from supervisory and trouble signals.
Supervisory signal
Signal indicating an off-normal condition in a system or suppression component, such as a closed valve, that could impair fire protection but is not an alarm.
Addressable system
Fire alarm system in which each initiating or notification device has a unique address, allowing the panel to identify the specific device in alarm or trouble.
Spot smoke detector spacing
For smooth ceilings, NFPA 72 permits maximum 30-foot spacing and 900 square feet per detector, with reduced spacing near beams and walls.
Manual fire alarm box
Pull station mounted within 5 feet of an exit doorway at 42 to 48 inches above finished floor, providing manual initiation of the fire alarm signal.
Duct smoke detector
Detector installed in air-handling ductwork to sense smoke and shut down or control the air handler; it does not replace area smoke detection.
Heat detector ratings
Common fixed-temperature ratings are 135°F ordinary, 194°F intermediate, and 286°F high; selection depends on ambient conditions and listing.
Smoke detector sensitivity test
Functional check of detector response within one year of installation and every two years thereafter, using listed test methods or manufacturer instructions.
Temporal-three pattern
Standard evacuation tone with three half-second pulses separated by half-second pauses, followed by a one-and-a-half-second pause before repeating.
Public mode audibility
Notification sound must be 15 dBA above ambient or 5 dBA above maximum ambient, with a minimum of 65 dBA at the measuring point.
Sleeping area audibility
Alarm sound must reach 75 dBA at the pillow or 15 dBA above ambient, whichever is greater; low-frequency 520 Hz tone may be required.
Visible appliance synchronization
Flashing visible notification appliances in the same field of view must flash in synchronization to avoid seizure risk and meet code.
Class A circuit
Fire alarm circuit that continues to operate after a single open or ground fault because it has a redundant return path to the control panel.
Class B circuit
Fire alarm circuit that uses an end-of-line resistor and annunciates a trouble but cannot continue operating after an open circuit.
FPL fire alarm cable
Listed fire alarm cable rated for general use; FPLR is riser-rated and FPLP is plenum-rated for installation in those spaces.
Ground fault detection
Control panel function that monitors fire alarm circuits for unintended connection to ground and annunciates a trouble condition.
Secondary power requirement
Fire alarm systems must have automatically connected standby power, typically batteries or generator, sized for 24 hours standby plus 5 minutes alarm.
Battery capacity formula
Required amp-hours equal standby current times 24 hours plus alarm current times alarm hours, multiplied by an aging factor such as 1.2.
Dedicated fire alarm circuit
Primary 120-volt branch circuit supplying the fire alarm control panel; it must be dedicated, marked, and protected against accidental disconnection.
NAC voltage drop
Calculation verifying that voltage at the farthest notification appliance remains within its listed operating range under alarm load.
Annual fire alarm test
Periodic verification that initiating devices, notification appliances, control functions, and annunciation operate as designed; records are kept for the authority.
Waterflow switch testing
Quarterly test of waterflow alarms to confirm activation and signal transmission, commonly required by NFPA 72 inspection tables.
Fire watch during impairment
Temporary human patrol or other approved measure required when a fire alarm system is impaired, with notification to the authority having jurisdiction.
Test record retention
Inspection and testing records must be documented, retained, and made available to the authority having jurisdiction for code compliance.
Record of Completion
NFPA 72 document signed by installer and owner listing system features, device inventory, and verification that installation complies with approved plans.
As-built drawings
Final drawings showing actual fire alarm device locations, circuit routing, panel schedules, and changes made during installation.
Sequence of Operations
Written description of how the fire alarm system responds to alarm, supervisory, and trouble conditions, including cause-and-effect actions.
Battery calculation submittal
Design document showing standby and alarm loads, battery amp-hour capacity, voltage drop, and recharge capability for the fire alarm system.