WA Electrician flashcards
WA Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- Voltage equals current multiplied by resistance (E = I × R); rearranged, I = E ÷ R and R = E ÷ I. In a resistive circuit, power equals E × I.
- Single-phase voltage drop formula
- VD = (2 × K × I × L) ÷ circular mils, where K is 12.9 for copper and 21.2 for aluminum, I is amperes, and L is the one-way length in feet.
- Series circuit current
- In a series circuit the same current flows through every component, total resistance is the sum of the resistances, and source voltage equals the sum of the voltage drops.
- Parallel circuit voltage
- In a parallel circuit the voltage is identical across every branch, total current is the sum of branch currents, and total resistance is less than the smallest branch resistance.
- Dwelling general lighting load
- NEC 220.12 assigns a general lighting load of 3 volt-amperes per square foot for dwelling occupancies, which is then reduced by the demand factors of Table 220.42.
- Small appliance branch circuit load
- A dwelling unit requires at least two 20-ampere small appliance branch circuits, each computed at 1,500 volt-amperes when calculating the service or feeder load.
- Washington electrical code adoption
- Washington adopts the National Electrical Code with amendments published in WAC 296-46B, administered by the Department of Labor & Industries, which licenses electricians and inspects installations.
- Continuous load 125 percent factor
- A continuous load operates for three hours or more; branch-circuit conductors, overcurrent devices, and feeders serving it must be sized at 125 percent of the load current.
- Securing Type NM cable
- Type NM cable must be fastened within 12 inches of every box and at intervals not exceeding 4.5 feet, and its ampacity is limited to the 60°C column.
- EMT fastening intervals
- Electrical metallic tubing must be secured within 3 feet of each box or fitting and at intervals not exceeding 10 feet along the remainder of the run.
- Raceway fill for three conductors
- Three or more conductors in a raceway may occupy no more than 40 percent of the interior cross-sectional area; a single conductor is limited to 53 percent.
- Box fill per 12 AWG conductor
- Each 12 AWG conductor requires 2.25 cubic inches of box volume, 14 AWG requires 2.00 cubic inches, and 10 AWG requires 2.50 cubic inches under Table 314.16(B).
- Equipment working space dimensions
- For equipment operating at 150 volts to ground or less, working space must be at least 3 feet deep, 30 inches wide, and 6 feet 6 inches high.
- Derating for bundled conductors
- Where four to six current-carrying conductors share a raceway, ampacity drops to 80 percent; seven to nine drop to 70 percent; ten to twenty drop to 50 percent.
- Protecting cable in bored holes
- Cable run through a bored hole less than 1¼ inches from the nearest edge of a framing member must be protected by a steel plate at least 1/16 inch thick.
- Identifying the grounded conductor
- The grounded conductor is identified by a white or gray finish; equipment grounding conductors use green, green with yellow stripes, or bare copper conductors.
- Dwelling wall receptacle spacing
- In dwelling units no point along the floor line of a wall space may be more than 6 feet from a receptacle, and spaces 2 feet or wider require one.
- Countertop receptacle spacing
- Kitchen countertop receptacles must be placed so that no point along the counter wall is more than 24 inches from a receptacle, with one on each island.
- GFCI protection in bathrooms
- All 125-volt, single-phase, 15- and 20-ampere receptacles installed in dwelling unit bathrooms require ground-fault circuit-interrupter protection for personnel.
- Inverse-time breaker for motors
- A motor branch circuit may use an inverse-time circuit breaker sized up to 250 percent of the motor full-load current for short-circuit and ground-fault protection.
- Dual-element fuse motor limit
- Time-delay, dual-element fuses providing short-circuit protection for a motor branch circuit may be sized up to 175 percent of the motor full-load current.
- Motor overload trip setting
- Overload protection for a continuous-duty motor with a marked service factor of 1.15 or more is set at no more than 125 percent of nameplate full-load amperes.
- Motor branch conductor size
- Conductors supplying a single motor must have an ampacity of at least 125 percent of the motor full-load current taken from Tables 430.248 through 430.250.
- Motor disconnect location
- The motor disconnecting means must be within sight of the motor and driven machinery and within 50 feet of it, unless the device can be locked open.
- Pool receptacle distance
- Receptacles serving a permanently installed swimming pool must be at least 6 feet from the inside wall of the pool and no more than 20 feet from it.
- Overhead conductors near pools
- Insulated overhead conductors rated up to 750 volts must be at least 10 feet horizontally from the pool edge, with greater clearances where diving structures are installed.
- PV rapid shutdown
- Photovoltaic conductors more than 1 foot from the array must be reduced to 80 volts or less within 30 seconds after rapid shutdown is initiated.
- Class I Division 2 location
- An area where ignitable concentrations of flammable gases or vapors are expected only under abnormal operating conditions, such as equipment failure or a fault.
- Emergency lighting duration
- Exit signs and emergency illumination supplied by an emergency system must be capable of providing the required level of light for at least 90 minutes.
- GFCI on construction sites
- All 125-volt, 15- and 20-ampere receptacles used for temporary wiring on construction sites must be protected by ground-fault circuit interrupters.
- Arc flash boundary
- The distance from energized equipment at which a person could receive a second-degree burn, defined as an incident energy of 1.2 calories per square centimeter.
- Limited approach boundary
- A shock-protection boundary that unqualified persons may not cross unless continuously escorted by a qualified person; the distance depends on voltage and appears in NFPA 70E tables.