Water Treatment Plant Operator flashcards
Water Treatment Plant Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Turbidity (NTU)
- A measure of light scattering by suspended particles, reported in nephelometric turbidity units. Filtered water must be 0.3 NTU or less in at least 95 percent of monthly samples.
- Hardness as CaCO3
- The concentration of calcium and magnesium expressed as calcium carbonate equivalent. One grain per gallon equals 17.1 mg/L as CaCO3.
- Groundwater under direct influence
- Groundwater contaminated by surface water, judged by indicators such as turbidity or fecal coliform. It requires at least 4-log virus inactivation under the Ground Water Rule.
- Total organic carbon
- A measure of natural organic matter in source water. It is a precursor for disinfection byproducts and a driver of coagulant demand during enhanced coagulation.
- Alum alkalinity consumption
- Alum consumes about 0.45 mg/L of alkalinity as CaCO3 per mg/L of coagulant applied. Low-alkalinity waters can drop in pH sharply unless alkalinity is supplemented.
- Jar test
- A bench procedure using multiple beakers and paddle speeds to simulate rapid mix, flocculation, and settling, determining coagulant dose, pH, and polymer dose.
- Velocity gradient (G)
- A measure of mixing intensity in reciprocal seconds. Rapid mix is typically 300 to 1000 per second; flocculation is typically 10 to 75 per second.
- Surface overflow rate
- Clarifier flow divided by surface area, expressed as gallons per day per square foot. It represents the settling velocity that particles must exceed to be captured.
- Stokes' law
- Settling velocity of a discrete particle increases with the square of its diameter and its density difference from water, and decreases as water viscosity rises.
- Dual-media filter
- A bed of anthracite over sand over gravel. The coarse upper layer allows deeper solids penetration, producing longer filter runs and higher loading rates.
- Filter backwash expansion
- The percent increase in bed depth during backwash, typically 15 to 25 percent. Adequate expansion is needed to release captured solids without washing media to waste.
- Filter-to-waste
- Routing filtered water to waste during the ripening period after backwash and before returning it to the clearwell, reducing turbidity spikes and pathogen passage.
- CT value
- Disinfectant residual concentration in mg/L multiplied by contact time in minutes. Required CT increases as water temperature decreases and pH increases.
- Breakpoint chlorination
- The chlorine dose beyond which ammonia demand is satisfied and free chlorine residual begins to appear and increase with further dosing.
- Hypochlorous acid
- The dominant free chlorine species below about pH 7.5. It is a far more effective disinfectant than the hypochlorite ion that dominates at higher pH.
- UV254 disinfection
- Ultraviolet light at 254 nanometers inactivates Cryptosporidium without creating a residual. Effectiveness depends on turbidity and UV transmittance of the water.
- Chemical feed rate formula
- Feed rate equals flow multiplied by dose divided by solution strength. Feed pumps are verified by timed collection in a graduated cylinder.
- Sodium hypochlorite storage
- Hypochlorite degrades faster with heat, sunlight, and heavy metal contamination. Store it cool and shaded, rotate stock, and avoid long storage times.
- Secondary containment
- A curbed or lined area sized to hold the largest container plus precipitation. It prevents spills of acids, caustics, and coagulants from reaching drains or soil.
- Affinity laws
- For a centrifugal pump, flow varies with impeller speed, head with the square of speed, and power with the cube of speed.
- Cavitation
- Vapor bubble formation and collapse when available net positive suction head falls below required. It causes noise, vibration, and impeller damage.
- Pump power equation
- Brake horsepower equals flow in gpm times head in feet, divided by 3960 times pump efficiency. It sizes motors and estimates energy use.
- System curve
- A plot of head required versus flow, combining static lift and friction loss. Its intersection with the pump curve defines the operating point.
- 4 to 20 mA loop
- An analog signal standard where 4 mA represents zero and 20 mA represents full scale. A current below 4 mA indicates a broken wire or fault.
- pH meter calibration
- A two-point adjustment using fresh pH 4 and 7 or 7 and 10 buffers with temperature compensation. Drifting readings indicate electrode fouling or aging.
- Cross-connection
- Any actual or potential link between a potable water supply and a source of contamination. Protection methods include air gaps and reduced pressure zone assemblies.
- Air gap
- The highest level of backflow protection: a physical separation of at least twice the pipe diameter and never less than one inch above the flood level rim.
- Reduced pressure zone assembly
- A testable backflow preventer with two check valves and a relief valve. It requires annual testing by a certified tester and visible relief discharge.
- Water age
- The average time water resides in the distribution system. High age from low demand or dead ends degrades residual and increases disinfection byproduct formation.
- Lead and Copper Rule
- A regulation using action levels rather than maximum contaminant levels. Exceeding the lead action level triggers corrosion control, monitoring, and public education requirements.
- Public notification tiers
- Tier 1 acute violations require notice within 24 hours, Tier 2 within 30 days, and Tier 3 within one year. Notices describe the violation and required actions.
- Confined space entry
- Entry into a space with limited access and poor ventilation requires atmospheric testing for oxygen, flammables, and hydrogen sulfide, plus a permit, attendant, and rescue plan.