Quick reference

Electrical Trade Knowledge - Journeyman Electrician

  • Ohm's law: E = I × R; power P = I × E = I²R = E²/R.

  • Series circuit: current is the same everywhere; resistances add; voltage divides in proportion to resistance.

  • Parallel circuit: voltage is the same across all branches; branch currents add; total resistance is less than the smallest branch resistance.

  • Three-phase power: P = √3 × E_line × I_line × power factor for a balanced load.

  • Conductor ampacity is adjusted for ambient temperature and for more than three current-carrying conductors in a raceway or cable.

  • Voltage drop for a single-phase two-wire circuit: VD = 2 × K × I × L ÷ CM, where K is the resistivity constant and CM is circular mils.

  • Box fill is computed by counting each conductor, each device yoke, and each equipment grounding conductor, then comparing to the box's cubic-inch capacity.

  • Motor branch-circuit conductors are sized at not less than 125 percent of the motor full-load current rating.

Quick reference

Electrical Trade Knowledge - Master Electrician

  • Service and feeder calculations begin with the calculated load; the service disconnect rating must be at least the calculated load and the service conductors must carry it.

  • Standard overcurrent device ratings follow the standard ampere-rating table; the next higher standard rating may be used only where the calculated load does not exceed the device rating.

  • For a single-family dwelling, the general lighting load is computed at 3 VA per square foot of floor area, then demand factors are applied.

  • Feeder and service neutral loads may be reduced for household electric ranges and similar appliances where the maximum unbalanced load is less than the branch-circuit rating.

  • Grounding electrode conductor size is selected from the table keyed to the largest service conductor; it is not sized by overcurrent device rating.

  • A grounded (neutral) conductor may serve as the equipment grounding conductor only in existing installations of the type permitted by the Code for the specific wiring method.

  • Interrupting rating of overcurrent devices must be at least the available fault current at the point of application.

  • Conductor fill in a raceway is limited to 40 percent for three or more conductors; 53 percent for one conductor; 31 percent for two conductors.

Quick reference

Residential Electrical Trade Knowledge - Residential Journeyman/Master

  • Small-appliance branch circuits: at least two 20-ampere circuits for the kitchen, pantry, and dining area receptacle outlets.

  • Laundry branch circuit: at least one 20-ampere circuit for the laundry receptacle outlet(s).

  • Bathroom receptacle outlets must be supplied by at least one 20-ampere branch circuit, and that circuit may not supply outlets outside the bathroom.

  • Ground-fault circuit-interrupter protection is required for receptacle outlets in bathrooms, garages, outdoors, kitchens (countertop surfaces), and unfinished basements.

  • Arc-fault circuit-interrupter protection is required for most 120-volt, 15- and 20-ampere branch circuits supplying outlets in dwelling units.

  • Receptacle spacing in habitable rooms: no point along the floor line may be more than 6 feet from a receptacle outlet.

  • Receptacles in a dwelling unit must be of the grounding type, and the grounding contacts must be connected to an equipment grounding conductor.

  • A 125-volt, single-phase, 15- or 20-ampere receptacle outlet in a dwelling unit must be tamper-resistant where required by the Code for the location.

Quick reference

Electrical Trade Knowledge - Industrial Journeyman Electrician

  • Motor disconnecting means must be located within sight of the motor controller and must open all ungrounded conductors.

  • Motor overload protection is sized to the motor's nameplate full-load current and service factor; it is separate from branch-circuit short-circuit and ground-fault protection.

  • Motor branch-circuit short-circuit and ground-fault protection may be a nontime-delay fuse, time-delay fuse, instantaneous trip circuit breaker, or inverse-time circuit breaker, each sized by a percentage of full-load current.

  • A controller must be capable of starting and stopping the motor it serves and must have a horsepower rating not less than the motor.

  • Flexible cord and cable connections to motors must be suitable for the environment and must include an equipment grounding conductor.

  • Class I locations are those in which flammable gases or vapors may be present; equipment must be marked for the class, division, and group.

  • A motor circuit's conductors are sized at 125 percent of the motor full-load current, and the overload device protects the motor, not the conductors.

  • Phase converters and variable-frequency drives require conductors and overcurrent protection sized per the manufacturer's instructions and the Code.

Quick reference

Electrical Code and Administrative Rules - SPS 316

  • SPS 316 adopts the National Electrical Code with Wisconsin amendments; where the state rule and the NEC differ, the state rule governs.

  • Electrical work in Wisconsin requires a permit from the local municipality or the Department of Safety and Professional Services where no local program exists.

  • Licensed electricians must be credentialed by the Department; journeyman and master electrician credentials are separate categories.

  • Inspections are performed by the authority having jurisdiction, and work must be inspected before being concealed.

  • The Department may adopt fee schedules and administrative procedures for permits, inspections, and credentials.

  • Electrical installations must comply with the adopted edition of the NEC as amended by SPS 316, including local ordinances that are more stringent.

  • Unsafe or noncompliant installations may be ordered corrected, and the Department may pursue enforcement action against unlicensed practice.

Quick reference

Electrical Trade Knowledge - Journeyman Electrician (Supplementary)

  • Ampacity tables are based on an ambient temperature of 30 degrees C for conductors in free air and on the table's stated conditions for raceways.

  • Equipment grounding conductors must be sized per the table keyed to the rating of the overcurrent device protecting the circuit.

  • A junction box must be accessible; boxes must be supported and have sufficient volume for the conductors and devices.

  • Receptacle outlets on a 20-ampere branch circuit must be rated 20 amperes or be a 15-ampere receptacle protected by the branch-circuit overcurrent device.

  • Switches must be connected to the ungrounded conductor, not the grounded conductor, so the fixture is de-energized when the switch is open.

  • Cable assemblies installed in exposed locations must be protected from physical damage where subject to damage.

  • The neutral conductor of a multiwire branch circuit must be sized to carry the maximum unbalanced load and must not be opened by a single-pole switch.