AABC Test and Balance Engineer (TBE) flashcards
AABC Test and Balance Engineer (TBE) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible Heat Ratio
- The ratio of sensible heat to total heat (sensible plus latent) for an airstream or coil load. Used to plot the room condition line on a psychrometric chart.
- Apparatus Dew Point
- The effective coil surface temperature at which the coil curve intersects the saturation line. Used with entering and leaving conditions to compute the coil bypass factor.
- Coil Bypass Factor
- Fraction of air passing the coil without contacting the surface. Computed as (entering DB minus leaving DB) divided by (entering DB minus ADP).
- Sensible Heat Equation
- For standard air, sensible heat in Btu/h equals 1.08 times cfm times the dry-bulb temperature difference. The constant 1.08 derives from air density and specific heat.
- Total Heat Equation
- For standard air, total heat in Btu/h equals 4.5 times cfm times the enthalpy difference in Btu per pound of dry air.
- Velocity Pressure Formula
- For standard air, velocity in feet per minute equals 4005 times the square root of velocity pressure in inches of water column.
- Pitot Tube Principle
- Velocity pressure equals total pressure minus static pressure. The total-pressure port faces airflow; the static port is perpendicular to flow.
- Expanded Uncertainty
- Expanded uncertainty equals the coverage factor k times the combined standard uncertainty. k equals 2 gives approximately 95 percent confidence for a normal distribution.
- Combined Standard Uncertainty
- For independent error sources, combine by root-sum-square: the square root of the sum of the squares of each individual standard uncertainty component.
- Percent of Full Scale Error
- An accuracy stated as a percent of full scale yields a fixed absolute error. At low readings this becomes a large percentage of the measured value.
- Calibration Traceability
- An unbroken documented chain of comparisons linking the instrument to a national standard, with recorded as-found and as-left values at each step.
- Equal-Area Traverse
- Divide the duct cross-section into equal-area zones and average the square roots of the velocity pressures from each zone to obtain mean velocity pressure.
- Traverse Location Rule
- Locate the traverse at least 7.5 duct diameters downstream and 3 diameters upstream of elbows, transitions, or other flow disturbances where space permits.
- Proportional Balancing
- A method where the terminal with the lowest measured-to-design flow ratio is left fully open and other terminals are throttled to match that same ratio.
- Airflow From Area
- Volumetric flow in cubic feet per minute equals duct cross-sectional area in square feet multiplied by average velocity in feet per minute.
- Pump Affinity Laws
- Flow varies directly with speed, head with the square of speed, and power with the cube of speed. Used to predict performance at reduced speed.
- Water Horsepower
- Water horsepower equals gallons per minute times head in feet times specific gravity, divided by 3960. Brake horsepower equals water horsepower divided by pump efficiency.
- Valve Flow Coefficient Cv
- Cv is the flow in gallons per minute of water at 60 F that passes through a fully open valve at a pressure drop of one psi.
- System Curve
- A plot of required head versus flow for a piping system. For turbulent flow, head varies with the square of flow; the operating point is where it crosses the pump curve.
- Ventilation Rate Procedure
- ASHRAE 62.1 method: breathing zone outdoor air equals people rate times occupants plus area rate times floor area.
- Building Pressurization
- Positive building pressure results when outdoor air intake exceeds exhaust and relief airflow. It limits infiltration but can cause moisture problems if excessive.
- Hood Face Velocity
- Average velocity at the hood opening, computed as exhaust airflow divided by hood face area. Used to verify capture and containment performance.
- Stair Pressurization Test
- Verify design differential pressure across the stair door with the door closed, and confirm the pressure holds under fire-mode fan and damper operation.
- DDC Point Types
- Analog input, analog output, digital input, and digital output. Each point is documented with range, units, and normal state in the point list.
- Live Zero Signal
- A 4-20 mA analog signal where 4 mA represents the minimum value. The nonzero minimum allows detection of a broken wire or failed transmitter.
- Sensor Scaling Formula
- Engineering value equals the fraction of signal span times the value span, plus the value minimum. Applied to convert raw analog signals to engineering units.
- Functional Performance Test
- A documented test confirming the sequence of operations under normal and failure modes, including forced outputs, trend review, and return to automatic control.
- Balancing Report Contents
- Design versus actual airflow, static pressures, fan speed, motor amperage, final damper and valve positions, calibration records, and a deficiency list.
- Common Airflow Tolerance
- A frequently specified balancing tolerance of plus or minus 10 percent of design airflow. The project specification governs the actual required tolerance.
- AABC and NEBB Standards
- Industry procedural standards that define balancing tolerances, instrument accuracy, report content, and certification requirements for test and balance work.
- Confined Space Entry
- Entry requiring atmospheric testing for oxygen, combustible gas, and toxics before and during entry, with an attendant stationed outside and a rescue plan.
- Lockout Tagout
- Isolation of all energy sources before servicing fans, pumps, or controls. Each worker applies a personal lock and verifies zero energy state.