Water Treatment Operator Class I study materials
Water Treatment Operator Class I study resources

Water Treatment Operator Class I cheat sheet

Water Treatment Operator Class I · Keep the key ideas within reach.

Quick reference

Water Sources, Quality, and Characteristics

  • Groundwater typically shows higher hardness, iron, manganese, and dissolved solids; surface water shows more variable turbidity, color, TOC, and microbial load.

  • Turbidity is reported in NTU and measured by nephelometry; it is a surrogate for particle and pathogen removal, not a direct pathogen count.

  • Total hardness (mg/L as CaCO3) = carbonate hardness + noncarbonate hardness; carbonate hardness equals alkalinity when alkalinity is less than total hardness.

  • Convert an ion to CaCO3 equivalent: mg/L as CaCO3 = mg/L ion x (50 / equivalent weight of the ion).

  • LSI = pH minus pHs; a positive LSI indicates calcium carbonate scaling tendency, a negative LSI indicates corrosive tendency.

  • Waters with alkalinity below about 50 mg/L as CaCO3 may not buffer alum or ferric coagulation and require lime, caustic, or soda ash addition.

  • TOC and UV254 are DBP-precursor indicators; higher TOC and higher UV254 mean greater coagulant demand and greater THM/HAA formation potential.

  • Under the Surface Water Treatment Rule, conventional filtration must achieve at least 3-log Giardia and 4-log virus inactivation/removal combined.

Quick reference

Coagulation, Flocculation, and Sedimentation

  • Common coagulants are alum, ferric chloride, ferric sulfate, polyaluminum chloride, and cationic polymers; each has its own optimum pH and alkalinity demand.

  • Alkalinity consumption: 1 mg/L of alum consumes roughly 0.45-0.5 mg/L of alkalinity as CaCO3; 1 mg/L of ferric chloride consumes about 0.9 mg/L.

  • Optimum coagulation pH is typically 6.0-7.0 for alum; ferric salts work over a wider range, roughly 4.5-7.5.

  • Rapid mix design: velocity gradient of 300-1000 per second for 10-60 seconds; flocculation: tapered G of 10-75 per second for 15-45 minutes.

  • Surface overflow rate (gpm/ft2) = flow (gpm) / clarifier surface area (ft2); particles with settling velocity greater than the overflow rate are removed.

  • Conventional sedimentation basins are designed for overflow rates of about 0.3-1.0 gpm/ft2 and detention times of 2-4 hours.

  • A zeta potential near zero indicates charge neutralization and good destabilization; a strongly negative zeta potential indicates underdosing.

  • Jar test rules: identical rapid mix, flocculation, and settling times in all jars; vary only coagulant dose and pH; select the lowest settled turbidity.

  • Sludge production rises with coagulant dose and raw water turbidity, so solids handling must be sized for the highest expected raw turbidity.

Quick reference

Filtration

  • Conventional rapid-rate filters are designed for about 2-6 gpm/ft2; dual-media anthracite-over-sand beds commonly run at 3-5 gpm/ft2.

  • Slow sand filters run at 0.1-0.4 gpm/ft2 and rely on the schmutzdecke biological layer; they are cleaned by scraping, not backwashing.

  • Backwash at 15-20 gpm/ft2 for 10-15 minutes to reach 20-50 percent bed expansion; poor expansion leaves mudballs and media cracks.

  • L/d ratio = media depth / effective size; values of at least 1000 are needed to prevent turbidity breakthrough.

  • Uniformity coefficient = d60 / d10; values of 1.3-1.5 give even backwashing and limit media stratification.

  • End a filter run on whichever occurs first: turbidity breakthrough at the state limit (often 0.3 NTU), maximum head loss, or maximum run time.

  • Combined filter effluent must be 0.3 NTU or less in at least 95 percent of monthly samples and must never exceed 1 NTU for conventional filtration.

  • Filter-to-waste or a slow start after backwash prevents the post-backwash turbidity spike from reaching the clearwell.

  • Typical media: anthracite effective size about 0.9-1.1 mm, sand about 0.45-0.55 mm, with garnet used in the bottom support layer.

Quick reference

Disinfection and Disinfection Byproducts

  • CT = disinfectant residual (mg/L) x contact time (min); the required CT depends on disinfectant type, pH, temperature, and the log credit needed.

  • Free chlorine is a stronger biocide than chloramine; chloramines maintain a distribution residual while lowering THM and HAA formation.

  • Breakpoint chlorination: at the breakpoint all ammonia is oxidized; beyond it, free chlorine residual rises roughly 1:1 with additional dose.

  • Stage 2 DBPR MCLs are TTHM 80 ug/L and HAA5 60 ug/L, both evaluated as locational running annual averages.

  • THM formation increases with higher pH, temperature, contact time, and TOC; HAA formation is favored at lower pH.

  • Enhanced coagulation removes TOC; the required removal percentage depends on raw TOC and raw alkalinity under the D/DBP Rule.

  • UV disinfection dose is expressed in mJ/cm2 and leaves no residual, so a chemical secondary disinfectant is still required in distribution.

  • Maintain a detectable free chlorine residual throughout distribution, typically at least 0.2 mg/L at the farthest points per state rule.

  • Chlorine demand = dose applied minus residual remaining; demand must be satisfied before any measurable residual persists.

Quick reference

Pumping, Storage, and Distribution System Interface

  • Affinity laws for a constant impeller diameter: flow varies with speed, head with speed squared, and brake horsepower with speed cubed.

  • The operating point is the intersection of the pump curve and the system curve; speed changes or valve throttling move that point.

  • Brake horsepower = (gpm x head in ft x specific gravity) / (3960 x efficiency expressed as a decimal).

  • NPSH available must exceed NPSH required at all flow rates to prevent cavitation, which causes noise, vibration, and impeller pitting.

  • 1 psi = 2.31 ft of water head, so a 100-ft head equals about 43.3 psi.

  • Minimum distribution pressure is commonly 20 psi under all conditions; normal service pressure is about 35-80 psi with a 150 psi typical maximum.

  • Storage must provide equalization, fire flow, and emergency reserve; many states require total storage equal to maximum-day demand plus fire flow.

  • Dead-end mains promote stagnation, low residual, and biofilm; looped grids plus routine flushing control these conditions.

  • Water hammer from rapid valve closure or pump trip is controlled with slow-closing valves, surge tanks, air chambers, and flywheels.

Quick reference

Laboratory Analysis and Process Control

  • Calibrate nephelometric turbidimeters with formazin or approved polymer standards and verify with a secondary standard each day of use.

  • Free and total chlorine residual are measured by DPD colorimetry or amperometric titration; DPD is the standard field method.

  • pH meters need two-point calibration using buffers that bracket the sample, typically 4.0, 7.0, and 10.0.

  • Holding times: chlorine residual and pH 15 minutes; turbidity 48 hours; nitrate 48 hours; coliform samples 8 hours (up to 30 hours with refrigeration in transit).

  • Revised Total Coliform Rule: a total-coliform-positive routine sample triggers repeat sampling within 24 hours and may require a Level 1 or Level 2 assessment.

  • Individual filter and combined filter effluent turbidity must be recorded at least every 15 minutes to establish compliance with the SWTR.

  • Quality control checks include method blanks, duplicates, matrix spikes, and continuing calibration verification; blanks should read near zero.

  • Trend coagulant dose, filtered turbidity, and chlorine residual on control charts and investigate shifts before they become exceedances.

Quick reference

Applied Calculations and Unit Conversions

  • Feed rate (lb/day) = mg/L x MGD x 8.34; rearranged, dose (mg/L) = lb/day / (MGD x 8.34).

  • Detention time = volume / flow; keep units consistent so gal / gpm gives minutes and ft3 / cfs gives seconds.

  • Surface loading rate (gpm/ft2) = flow (gpm) / area (ft2); weir loading (gpm/ft) = flow (gpm) / weir length (ft).

  • Conversions: 1 ft3 = 7.48 gal; 1 MGD = 694.4 gpm = 1.547 cfs; 1 cfs = 448.8 gpm.

  • Cylinder volume = 0.785 x D2 x H; rectangular basin volume = L x W x H.

  • Head (ft) = psi x 2.31; psi = ft of head / 2.31.

  • Percent removal = [(influent concentration - effluent concentration) / influent concentration] x 100.

  • Hypochlorite feed (lb/day) = gpd x 8.34 x (percent strength / 100).

  • CT = residual (mg/L) x contact time (min), where contact time = basin volume (gal) / flow (gpm) with consistent time units.

Quick reference

Safety, Regulations, and Recordkeeping

  • Permit-required confined space entry requires atmospheric testing (O2 19.5-23.5 percent, LEL under 10 percent, H2S under 10 ppm, CO under 35 ppm), a permit, an attendant, and rescue provisions.

  • Chlorine gas is heavier than air with an IDLH of 10 ppm; use supplied-air respiratory protection, keep cylinders away from heat, and evacuate upwind.

  • An SDS must be available for every hazardous chemical, and eyewash stations and safety showers must be within about 10 seconds of travel.

  • Lockout/tagout is required before servicing pumps, mixers, or chemical feeders; verify zero energy before work begins.

  • Public notice tiers: Tier 1 within 24 hours (immediate risk, such as an E. coli MCL), Tier 2 within 30 days, Tier 3 within 90 days.

  • Community water systems must deliver the annual Consumer Confidence Report to customers by July 1 covering the previous calendar year.

  • Retain turbidity and filter operating records at least 3 years, microbiological records at least 5 years, and chemical analysis records at least 10 years.

  • Operator certification requires passing the state exam and earning continuing education credits for renewal, commonly on a 2- or 3-year cycle.

  • Falsifying a monitoring report is a criminal violation; report MCL and monitoring violations to the primacy agency within the regulation's deadline.