Groundwater versus surface water
Groundwater usually has lower turbidity and TOC but higher hardness, iron, and dissolved solids; surface water has variable turbidity and higher microbial and DBP-precursor loading.
Turbidity
An optical measure of light scattering by suspended particles, reported in NTU; it is not a direct pathogen count but indicates how well filtration is working.
Langelier Saturation Index
An index calculated as measured pH minus the pH of calcium carbonate saturation; positive values indicate a scaling tendency and negative values indicate a corrosive tendency.
Alkalinity
The acid-neutralizing capacity of water, expressed as mg/L CaCO3; it buffers pH and supplies the bicarbonate that alum and ferric coagulants consume.
Jar test
A bench-scale test that mixes a coagulant at several doses and pH values under identical rapid mix, flocculation, and settling to identify the best dose.
Velocity gradient G
A measure of mixing intensity in reciprocal seconds; rapid mix typically uses 300 to 1000 per second and flocculation uses 10 to 75 per second.
Surface overflow rate
The clarifier loading equal to flow divided by surface area, expressed in gpm/ft2; particles settling faster than this rate are removed in the basin.
Alum alkalinity consumption
Each mg/L of alum dosed consumes roughly 0.45 to 0.5 mg/L of alkalinity as CaCO3, so low-alkalinity waters may need lime or caustic added.
Effective size
The media particle diameter at which 10 percent of the bed by weight is finer, designated d10; it governs head loss and the required media depth.
Uniformity coefficient
The ratio of d60 to d10 for filter media; values near 1.3 to 1.5 indicate a narrowly graded bed that backwashes evenly.
Filter backwash expansion
Media bed expansion of about 20 to 50 percent, produced by backwash rates of 15 to 20 gpm/ft2 for 10 to 15 minutes, clears accumulated solids.
Combined filter effluent limit
Under the SWTR, combined filter effluent turbidity must be 0.3 NTU or less in at least 95 percent of monthly samples and never exceed 1 NTU.
CT value
The product of disinfectant residual concentration in mg/L and contact time in minutes; the required CT varies with disinfectant, pH, temperature, and target log inactivation.
Breakpoint chlorination
The chlorine dose at which all ammonia has been oxidized and free chlorine residual begins to persist; beyond the breakpoint residual rises nearly one to one with dose.
TTHM MCL
The Stage 2 maximum contaminant level for total trihalomethanes is 80 micrograms per liter, evaluated as a locational running annual average at each monitoring site.
Enhanced coagulation
A treatment strategy that raises coagulant dose or lowers pH beyond normal practice to remove total organic carbon, the precursor to trihalomethanes and haloacetic acids.
Affinity laws
For a centrifugal pump at constant impeller diameter, flow varies with speed, head varies with speed squared, and power varies with speed cubed.
NPSH available
The absolute pressure head at the pump suction above the liquid vapor pressure; it must exceed the pump's required NPSH or cavitation will damage the impeller.
Brake horsepower formula
Pump power in horsepower equals flow in gpm times head in feet times specific gravity, divided by 3960 times the pump efficiency expressed as a decimal.
Water hammer
A pressure surge caused by a rapid velocity change when a valve closes or a pump stops; controlled with slow-closing valves, surge tanks, and air chambers.
DPD method
A colorimetric procedure using N,N-diethyl-p-phenylenediamine to measure free and total chlorine residual in both field and laboratory testing.
Formazin turbidity standard
The primary reference suspension used to calibrate nephelometric turbidimeters; it is prepared from hydrazine sulfate and hexamethylenetetramine and assigned NTU values.
Chlorine residual holding time
Chlorine residual and pH samples must be analyzed within 15 minutes of collection because both parameters change rapidly after the sample is taken.
Revised Total Coliform Rule
Requires routine coliform monitoring plus a Level 1 or Level 2 assessment and corrective action when a sample is total-coliform positive or E. coli is detected.
Pounds formula
Pounds per day of chemical equals the concentration in mg/L multiplied by the flow in million gallons per day multiplied by 8.34.
Detention time formula
Detention time equals basin volume divided by flow rate; units must match, so gallons divided by gallons per minute yields minutes.
Feet of head to psi
One pound per square inch equals 2.31 feet of water head, so divide feet of head by 2.31 to obtain pressure in psi.
Surface loading rate units
Flow in gallons per minute divided by clarifier surface area in square feet gives gpm/ft2, the overflow rate that governs particle removal.
Permit-required confined space
A space with limited entry that is not designed for occupancy and may contain a hazardous atmosphere, engulfment, or entrapment; entry requires a permit and attendant.
Chlorine gas IDLH
The immediately dangerous to life or health concentration for chlorine is 10 ppm; escape from a release requires supplied-air respirators and upwind evacuation.
Tier 1 public notice
Required within 24 hours for violations posing an immediate health risk, such as an E. coli MCL or a situation prompting a boil water order.
Consumer Confidence Report deadline
Community water systems must deliver the annual Consumer Confidence Report to customers by July 1, covering monitoring results from the previous calendar year.