On a 12 V boat, a 100 A alternator charges the house bank through a 2 AWG cable with a 14 ft one-way run. The cable is protected at the battery by a 300 A fuse. The cable runs in a 50 °C engine room bundled with two other cables. The builder's table gives 2 AWG 130 A at 30 °C free air, with a 0.82 temperature correction and a 0.70 bundling correction. A separate 10 AWG branch feeds a 25 A deck-wash pump. That branch is protected by a 30 A breaker at the main panel, and the one-way run is 30 ft. The 10 AWG rating is 60 A at 30 °C, corrected by 0.70 for bundling. Use K = 10.7.

1. Evaluate the 2 AWG charge cable and the 300 A fuse. What size cable and fuse would you select?

Read the worked answer

Corrected ampacity = 130 x 0.82 x 0.70 = 74.6 A. The alternator can produce 100 A, so the 2 AWG cable is undersized for the source, and the 300 A fuse is far above the cable ampacity. The fuse at the battery is correctly located to protect against battery fault current, but it must be sized to the cable: a 300 A fuse will not open before the 2 AWG overheats. 1/0 gives 170 x 0.574 = 97.6 A, still marginal for 100 A; 2/0 gives 195 x 0.574 = 111.9 A. Use 2/0 with a 125 A fuse, or a fuse sized per the chosen cable and alternator, and verify voltage drop: 2 x 10.7 x 100 x 14 / 133,100 = 0.23 V. Also check the alternator's own output protection requirements.

2. Evaluate the 10 AWG deck-wash branch for both overcurrent protection and voltage drop. What minimum size would you recommend for a 10% drop target, and for a 3% target?

Read the worked answer

Ampacity: 60 x 0.70 = 42 A, so the 30 A breaker protects the 10 AWG conductor. Protection is not the problem; voltage drop is. At 25 A: 2 x 10.7 x 25 x 30 / 10,380 = 16,050 / 10,380 = 1.55 V, or 12.9% of 12 V. That exceeds a 10% motor-circuit guideline and is worse at startup. 8 AWG (16,510 cm) gives 0.97 V (8.1%); 6 AWG (26,240 cm) gives 0.61 V (5.1%); 4 AWG (41,740 cm) gives 0.38 V (3.2%). For a 10% target, use 8 AWG with a 30 A breaker; for a 3% target, use 4 AWG. Confirm the pump's starting current and the breaker's motor rating.

3. The owner wants to move the 300 A fuse from the battery end to the alternator end because it is closer to the alternator. Evaluate.

Read the worked answer

No. The fuse must be at the battery end of the charge cable because the battery is the high-fault-current source. Moving it to the alternator end would leave the 14 ft cable unprotected if it chafes and shorts to ground; the battery would feed the fault through the cable, and the alternator's 100 A output would not limit it. The alternator end may need its own protection for the alternator's output, but that does not replace battery-end protection. Keep the fuse at the battery, size it to the cable, and protect the cable from chafe.