ACCA Residential HVAC Design study materials
ACCA Residential HVAC Design study resources

ACCA Residential HVAC Design: Residential HVAC System Design: Manual J, S, and D

ACCA Residential HVAC Design · Work through your exam, one topic at a time.

All guide sections

Residential HVAC System Design: Manual J, S, and D

The design triad

Manual J estimates room-by-room heating and cooling loads from an ACCA-approved method: envelope areas and U-factors, window solar gain and orientation, infiltration (or a blower-door result), internal gains, and design indoor/outdoor conditions. Manual S then selects equipment so its capacity meets the load at design conditions, not just nominal tonnage. Manual D sizes the duct system so each room receives its share of airflow within acceptable static pressure and velocity.

Concepts to know

  • Sensible vs latent load: total capacity must cover both; equipment sensible heat ratio must track the load SHR or you get short cycling and humidity problems.
  • Design conditions: use the correct outdoor design temperature for the location and indoor design (e.g., 75°F/50% RH cooling).
  • Equipment selection: capacity within the load range; avoid gross oversizing; check latent capacity at the actual entering wet-bulb.
  • Duct design: equivalent length, friction rate, fitting losses, and available static pressure after subtracting filter, coil, and register losses.
  • Airflow: roughly 400 cfm per ton nominal, adjusted for the equipment and sensible/latent balance.

Traps

Questions often tempt you to size by square footage alone or to "round up" tonnage. Oversizing raises first cost, shortens runtime, worsens dehumidification, and can void warranty or rebate eligibility. Another trap: confusing nominal tonnage with delivered capacity at real conditions, or ignoring duct static pressure when selecting a blower.

Rule of thumb / worked example

A room load of 2,400 Btu/h sensible plus 600 Btu/h latent (3,000 total) is not a half-ton job by rule; verify at design conditions. For airflow, 3 tons at 400 cfm/ton needs 1,200 cfm total; if a 12-room layout gives one room 10% of the load, deliver about 120 cfm there. Always confirm the equipment's rated capacity at the actual entering conditions.