Mortar Type M
Highest-strength mortar in ASTM C270; used for reinforced masonry and severe exposures; minimum 28-day compressive strength is 2500 psi.
Mortar Type S
Medium-high strength mortar in ASTM C270; minimum 28-day compressive strength 1800 psi; suitable for normal reinforced masonry.
Mortar Type N
General-purpose mortar in ASTM C270; minimum 28-day compressive strength 750 psi; common for above-grade nonreinforced exterior walls.
Mortar Type O
Low-strength mortar in ASTM C270; minimum 28-day compressive strength 350 psi; used for nonload-bearing interior partition walls.
ASTM C270
Standard specification for mortar for unit masonry; defines mortar types by proportion and minimum 28-day compressive strength.
ASTM C90
Standard specification for load-bearing concrete masonry units; covers materials, dimensions, and strength requirements for hollow and solid units.
Grout sampling
Fresh grout is sampled per ASTM C1019 from the mixer or pump discharge before placement, then molded into test specimens.
Flow table test
ASTM C1437 consistency test; mortar is placed in a mold, dropped 25 times in 15 seconds, and spread is measured.
Flow formula
Flow (%) = [(spread diameter minus original diameter) / original diameter] x 100; average four measured diameters.
Mortar water content
Determined by drying a weighed fresh mortar sample to constant mass; water content compares mass loss with dry mass.
Mortar cube specimen
Field mortar compressive strength is commonly evaluated with 2-inch cubes molded per ASTM C780 and cured to test age.
Grout specimen
ASTM C1019 grout specimens are molded from fresh grout, consolidated, cured, and tested in compression at the specified age.
Specimen identification
Each field specimen must be marked with project, location, batch, date, and test age before curing.
Initial curing
Field specimens must be protected from moisture loss, vibration, and temperature extremes during initial curing.
Masonry prism
A small assemblage of units, mortar, and grout built to represent masonry and tested in compression per ASTM C1314.
Prism test set
A set typically contains at least three prisms; the average strength is used to evaluate the masonry.
Prism construction
Prisms must use the same units, mortar, grout, and joint construction as the masonry they represent.
Height-to-thickness ratio
Prism strength is corrected for h/t ratio because short prisms give higher apparent strength; C1314 gives correction factors.
Prism capping
Caps must be plane, parallel, and perpendicular to the load; sulfur or gypsum caps are commonly used.
Prism compressive strength
Computed as maximum load divided by the specified cross-sectional area; report average, individual values, and age.
Prism curing
Prisms are cured under conditions representative of the field masonry before capping and testing at the specified age.
ASTM C140
Standard test methods for sampling and testing concrete masonry units, including compressive strength, absorption, and saturation.
Unit compressive strength
Maximum load on a capped unit loaded perpendicular to the bed divided by gross cross-sectional area.
Absorption formula
Absorption (%) = [(saturated mass minus oven-dry mass) / oven-dry mass] x 100 for the specified immersion period.
Saturation coefficient
Ratio of a unit's 24-hour cold-water absorption to its absorption after a longer saturation or boiling procedure.
Oven-dry mass
Unit mass after drying to constant mass at the standard temperature; it is the denominator in absorption calculations.
Unit specimen defects
Units with cracks, chips, or irregular geometry that affect load or absorption should be noted or excluded per the standard.
Test report contents
Report must identify project, sample location, test method, test date, specimen age, dimensions, results, and tester.
ACI MFTT
ACI Masonry Field Testing Technician certification qualifies personnel to perform specified masonry field tests under ACI requirements.
Record retention
Test records must be retained per contract or code and protected from loss or unauthorized alteration.
Anomalous result
A result that is unusual or nonconforming must be reported and investigated, not discarded without record.
Field batch record
Notes should include batch time, mixer, materials, water additions, and any deviation from the specified procedure.