ACI Post-Installed Anchor Inspector · Put your knowledge to work in context.

All case studies

Hole Cleaning Verification for Adhesive Anchors

An inspector is observing adhesive anchor installation in a dusty, above-grade concrete beam. The crew is using a rotary hammer in hammer-only mode to drill 14 mm holes for M12 threaded rod at 110 mm embedment. The specified cleaning method is brush and blow. The inspector watches one hole: the worker brushes twice, blows once with a hand pump, then inserts the rod. The hole shows visible dust on the wall. The crew says they have done "hundreds of these" and the adhesive will push the dust out. The inspector must decide whether to accept the installation method for the remaining 40 anchors.

1. Is the observed cleaning sufficient? What is the technical basis?

Read the worked answer

No. The observed cleaning (2 brush strokes, 1 hand-pump blow) is generally below the manufacturer's specified brush-and-blow sequence, and visible dust on the hole wall is direct evidence of inadequate cleaning.

Technical basis:

  • Adhesive bonds to the concrete pore structure; dust acts as a release layer and reduces bond strength.
  • The adhesive does not "push dust out" - it encapsulates dust, creating a weak interface.
  • Hammer-only drilling produces more fines than hammer-drill with a carbide bit in many cases; cleaning must match the drilled condition.

The inspector should reject the method and require the manufacturer's specified cleaning (typically multiple brush and blow cycles with the correct brush diameter and a proper blow-out tool).

2. How should the inspector handle the anchors already installed?

Read the worked answer

The inspector cannot assume the already-installed anchors are acceptable. Because the same crew and method produced them, the inspector should:

  1. Document the observed cleaning sequence and the visible dust.
  2. Require the contractor to identify all anchors installed by that method.
  3. Require the engineer/manufacturer to direct remediation - often removal and re-installation, or proof testing per the engineer's direction.
  4. Do not sign off the remaining 40 until the cleaning procedure is corrected and demonstrated on a trial hole observed by the inspector.

The inspector's role is to prevent concealment: once adhesive cures, the defect is hidden, so the decision must be made before the remaining anchors are set.