Surface Preparation and Bonding on Existing Concrete

ACI Shotcrete Nozzleman Wet-Mix · Put your knowledge to work in context.

All case studies

Surface Preparation and Bonding on Existing Concrete

You are preparing to apply a 75 mm wet-mix shotcrete overlay on an existing concrete wall that is 20 years old. The surface has areas of carbonation, some oil stains, and a few cracks. The specified bond strength is 1.0 MPa. The ambient temperature is 10°C and the surface is dry. The crew plans to use a bonding agent and then apply the shotcrete in one pass. The nozzleman has a 50 mm hose and is using a mix with w/c 0.45 and 10% silica fume. The air pressure at the nozzle is 7 bar. The contractor wants to start spraying immediately after applying the bonding agent.

1. What surface preparation steps are necessary before applying the bonding agent and shotcrete?

Read the worked answer

Proper surface preparation is critical for bond. The following steps are required:

  1. Remove all loose material, oil stains, and carbonation. Use high-pressure water blasting (minimum 200 bar) or abrasive blasting to achieve a roughened, clean surface. Oil stains may require degreasing or mechanical removal.
  2. Repair cracks: Inject epoxy or route and seal cracks to prevent reflective cracking.
  3. Check substrate moisture: The surface should be saturated surface-dry (SSD) to prevent absorption of water from the shotcrete. Since the surface is dry, pre-wet it and allow excess water to drain.
  4. Verify surface profile: A profile of CSP 5–7 is recommended for bond.
  5. Apply bonding agent according to manufacturer's instructions; typically, it should be applied to a damp surface and allowed to become tacky before shotcreting. Do not let it dry completely.
  6. Ensure the bonding agent is compatible with the shotcrete mix; some agents require a specific application method.
  7. The nozzleman should not spray until the bonding agent is properly prepared. Starting immediately after application may be too soon; check tackiness.

2. Is it acceptable to apply 75 mm in one pass? What considerations should be made for the low temperature and bonding?

Read the worked answer

75 mm in one pass on a vertical wall is generally acceptable if the mix is properly designed and the surface is prepared. However, for overhead or vertical, 75 mm is at the upper limit; typically 50–75 mm is allowed. Given the low temperature (10°C), the shotcrete will set slower, increasing the risk of sagging. The nozzleman should monitor the build-up and may need to reduce layer thickness to 50 mm. For bonding, the low temperature may affect the bonding agent's curing; ensure it is applied within the manufacturer's temperature range. Also, the substrate should be kept above 5°C. The shotcrete mix may need acceleration to compensate for slow set. The nozzleman should check bond by tapping with a hammer after set. If bond is critical, consider applying a scratch coat first.