DM Electrical Exam study materials
DM Electrical Exam study resources

DM Electrical Exam flashcards

DM Electrical Exam · Build recall with a focused review session.

33 cards. Read the term and the definition here. The deck at the top of this page is optional.

Ohm's Law
The relationship E = I × R, where E is voltage in volts, I is current in amperes, and R is resistance in ohms. Used to solve any DC resistive circuit.
Power Formula
For DC or resistive AC, P = E × I = I²R = E²/R, giving power in watts. In AC circuits, multiply by the power factor for real power.
Series Circuit Rules
Total resistance is the sum of all resistances, current is the same through every element, and voltage divides among elements in proportion to their resistance.
Parallel Circuit Rules
Voltage is the same across all branches, total resistance is less than the smallest branch resistance, and branch currents sum to total current.
Three-Phase Power
For a balanced three-phase load, real power is P = √3 × line voltage × line current × power factor. The √3 factor comes from phase-to-line relationships.
Inductive Reactance
X_L = 2πfL, the opposition to AC current from an inductor, in ohms. It rises with frequency, and inductor current lags voltage by 90 degrees.
Branch Circuit Definition
Per NEC Article 100, the circuit conductors between the final overcurrent protection device protecting the circuit and the outlet or outlets served.
Continuous Load Rule
A load operating at maximum current for three hours or more is continuous and must be calculated at 125% of its rating for branch circuits and feeders.
Standard OCPD Sizes
NEC 240.6 lists standard ampere ratings, including 15, 20, 30, 40, 50, 60, 70, 100, 125, 150, and 200 amperes for fuses and breakers.
Working Clearance Rule
NEC 110.26 requires dedicated space in front of electrical equipment; the minimum depth starts at 3 feet for equipment up to 150 volts to ground.
GFCI Protection Locations
NEC 210.8 requires ground-fault circuit-interrupter protection for receptacles in bathrooms, garages, outdoors, kitchens, and other wet or damp locations.
Conductor Ampacity Adjustment
NEC 310.15 requires derating for ambient temperature and for more than three current-carrying conductors in a raceway or cable, applied to table ampacities.
Electrical Shock Thresholds
About 1 mA is perceptible, 10 to 20 mA can cause muscle lock preventing release, and 100 mA or more through the heart can be fatal.
Arc Flash Boundary
The distance at which incident energy equals 1.2 cal/cm², the threshold for a second-degree burn. It is calculated from fault current and clearing time.
Lockout Tagout Verification
After de-energizing and locking, a qualified worker tests for zero energy with a meter rated for the system voltage and category before beginning work.
Class C Fire
A fire involving energized electrical equipment. A nonconductive extinguishing agent is used, or power must be removed before applying water or foam.
Equipment Grounding Conductor
A conductor that provides a low-impedance path from equipment enclosures back to the source, allowing fault current to trip the overcurrent device.
NM-B Cable Restrictions
Nonmetallic sheathed cable is permitted in dry, protected locations but is prohibited in wet locations, masonry cavities, and where subject to physical damage.
EMT Support Intervals
Electrical metallic tubing must be supported within 3 feet of each box and at intervals not exceeding 10 feet along the run.
Box Fill Calculation
NEC 314.16 assigns volume allowances to conductors, devices, and grounds, which are compared against the box's marked cubic-inch capacity.
Conduit Fill Percentages
Chapter 9 Table 1 permits 53% fill for one conductor, 31% for two, and 40% for three or more conductors in a raceway.
360-Degree Bend Rule
No more than 360 degrees of total bends, including offsets and kicks, is permitted between pull points in a run of conduit.
Motor Short-Circuit Protection
NEC 430.52 sizes the branch-circuit short-circuit and ground-fault device, often up to 250% of full-load current for an inverse-time breaker.
Motor Overload Protection
A running overload device protects the motor from sustained overcurrent and is sized to the motor's nameplate current and service factor.
Contactor Versus Starter
A contactor switches load current only; a starter adds overload relays to the contactor to provide motor running overload protection.
GFCI Versus AFCI
A GFCI detects current imbalance to ground and protects people from shock; an AFCI detects arcing signatures and protects against fire ignition.
Dwelling Lighting Load
NEC 220 uses 3 volt-amperes per square foot for general lighting in dwellings, with small-appliance and laundry circuits added separately.
Voltage Drop Formula
Single-phase voltage drop is approximately VD = (2 × K × I × L) / CM, where K is conductor resistivity and CM is circular-mil area.
Interrupting Rating
The maximum fault current a device can safely interrupt. It must equal or exceed the calculated available fault current at its point of installation.
Meter CAT Rating
A measurement category indicating the transient overvoltage environment a meter can withstand; CAT III and CAT IV are required for service and distribution work.
Insulation Resistance Test
A megohmmeter applies a DC voltage and reads resistance in megohms; declining readings over time indicate moisture, contamination, or insulation degradation.
Clamp Ammeter Use
A clamp meter measures current by surrounding a single conductor; clamping around both supply and return conductors cancels the fields and reads near zero.
Neutral-Ground Bond Fault
A neutral-to-ground connection downstream of the service creates parallel return paths that can cause nuisance GFCI trips and objectionable current on grounding conductors.