AL Electrician study materials
AL Electrician study resources

AL Electrician flashcards

AL Electrician · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Grounded conductor
A circuit conductor that is intentionally connected to earth and carries current during normal operation, such as the neutral in a 120/240-volt system.
Equipment grounding conductor
A conductor that connects non-current-carrying metal parts to the grounding electrode system and provides a low-impedance fault path.
Continuous load
A load expected to operate at maximum current for three hours or more; branch conductors and overcurrent devices are sized at 125 percent of it.
Working clearance
The clear space in front of electrical equipment required by NEC 110.26, at least 3 feet deep, 30 inches wide, and 6.5 feet high for 600-volt equipment.
Type NM cable
A factory-assembled cable with insulated conductors and an overall nonmetallic sheath, permitted in dry protected locations but not in wet or damp locations.
Type UF cable
A nonmetallic-sheathed cable listed for direct burial and wet locations, with conductors suitable for underground use and protection where exposed to damage.
Raceway fill
The percentage of a conduit’s interior cross section occupied by conductors; NEC Chapter 9 permits 40 percent for three or more conductors.
Box fill allowance
The cubic-inch volume assigned to each conductor, device, clamp, and grounding conductor when sizing an outlet box under NEC Table 314.16(B).
Equipment grounding
Bonding metal enclosures and equipment to the grounding system so fault current returns to the source and opens the overcurrent device.
Grounding electrode conductor
The conductor that connects the grounding electrode system to the service neutral or separately derived system grounding point.
Main bonding jumper
The connection between the service neutral and equipment grounding bus at the service equipment; it must not be repeated downstream.
Standard ampere rating
A listed overcurrent device rating such as 15, 20, 30, 40, 50, 60, 70, 80, 100, 110, 125, 150, 200, or 400 amperes.
Small-appliance branch circuit
A 20-ampere branch circuit supplying kitchen and dining receptacles; dwelling units require at least two such circuits.
Receptacle spacing rule
In dwelling units, wall receptacles must be installed so no point along the floor line is more than six feet from an outlet.
Service disconnecting means
The switch or breaker that disconnects all service-entrance conductors from the building; one-family dwellings require at least 100 amperes.
Feeder
A circuit conductor between the service equipment or source and a final branch-circuit overcurrent device, sized for the calculated load.
Motor full-load current
The current value from NEC Tables 430.248 through 430.250 used to size motor branch-circuit conductors and short-circuit protection, not the nameplate current.
Motor overload protection
Protection against sustained excessive current, usually a thermal overload relay set to the motor nameplate current; it is separate from branch short-circuit protection.
Transformer primary protection
Overcurrent protection on the primary side sized per NEC 450.3(B), generally 125 percent of primary current for transformers over 9 amperes.
Hazardous location
An area where flammable gases, vapors, dust, or fibers may be present; equipment must be listed and marked for the class and division.
Ohm’s law
The relationship V = I × R, where voltage equals current times resistance; used to solve circuit values when two quantities are known.
Three-phase power
Real power equals √3 times line-to-line voltage times line current times power factor for a balanced three-phase circuit.
Conduit fill percentage
NEC Chapter 9 limits conduit fill to 53 percent for one conductor, 31 percent for two, and 40 percent for three or more.
Ampacity adjustment
Derating of conductor current capacity when more than three current-carrying conductors share a raceway, per NEC Table 310.15(C)(1).
CAT III meter
A test instrument rated for distribution-level circuits such as panelboards and feeders; CAT IV is for service entrance and CAT II for receptacle circuits.
Live-dead-live test
A voltage verification method that checks the tester on a known live source, then the de-energized circuit, then the known source again.
Megohmmeter test
An insulation resistance measurement using a high-voltage DC tester on de-energized conductors to detect moisture, damage, or deterioration.
Clamp meter
An instrument that measures current by sensing the magnetic field around a single conductor placed within its jaws; it must not encircle both supply and return.
Alabama Electrical Contractors Board
The state board that licenses electrical contractors in Alabama and enforces qualification, examination, and disciplinary requirements for electrical contracting.
Direct labor cost
The wages and burden for electricians and helpers directly installing the work, usually estimated as hours multiplied by a loaded hourly rate.
Change order
A written modification to a contract that documents added or deleted work, price adjustment, and schedule impact before the work is performed.
Mechanic’s lien
A legal claim against improved property that may secure payment for labor or materials furnished under an Alabama construction contract, subject to notice rules.