Design density
The amount of water in gallons per minute per square foot (gpm/ft²) that must be applied over the design area; it is determined by the occupancy hazard classification.
Remote area
The hydraulically most demanding area of sprinkler operation used for calculating water demand; its size depends on hazard and system type.
Light hazard occupancy
An occupancy where the amount of combustibles is low and fire severity is expected to be low, such as offices, churches, and schools; design density is typically 0.10 gpm/ft².
Ordinary hazard Group 1
An occupancy with moderate combustibles and stockpiles up to 8 ft high, such as parking garages and restaurants; design density is 0.15 gpm/ft² over 1,500 ft².
Ordinary hazard Group 2
An occupancy with moderate to high combustibles and stockpiles up to 12 ft high, such as mercantile and manufacturing; design density is 0.20 gpm/ft² over 1,500 ft².
Extra hazard occupancy
An occupancy with high combustibles, flammable liquids, or high-piled storage where fire severity is high; design densities start at 0.30 gpm/ft² and require larger remote areas.
Sprinkler temperature rating
The temperature at which a sprinkler's heat-responsive element operates; ordinary ratings are 135–170°F, intermediate 175–225°F, and high 250–300°F.
Response time index (RTI)
A measure of sprinkler thermal sensitivity; quick-response sprinklers have RTI ≤ 50 (m·s)^0.5 and standard-response have RTI ≥ 80 (m·s)^0.5.
Quick-response sprinkler
A sprinkler with a fast-acting heat-responsive element (RTI ≤ 50) that activates sooner, allowing a smaller design area and often reducing water demand.
Standard spray sprinkler
A sprinkler with a defined spray pattern, available as upright or pendent, typically listed for a minimum operating pressure of 7 psi.
Sidewall sprinkler
A sprinkler mounted on a wall or side of a pipe that discharges water outward and downward; spacing and placement rules differ from pendant and upright sprinklers.
Hose allowance
The additional water flow (gpm) added to sprinkler demand for manual hose streams; typically 100 gpm for light hazard, 250 gpm for ordinary hazard, and 500 gpm for extra hazard.
Sprinkler spacing maximum
The maximum distance between sprinklers on a branch line or between branch lines, generally 15 ft for light and ordinary hazards, with area limits per sprinkler.
Obstruction rule
Sprinklers must be positioned relative to walls and obstructions; obstructions up to 4 ft wide may require additional sprinklers depending on distance and depth.
Dry-pipe system
A sprinkler system where the piping is normally filled with air or nitrogen under pressure; water enters after a sprinkler opens, increasing the remote area by 30%.
Preaction system
A dry-pipe system that requires a separate detection event to admit water into the piping before sprinkler activation, reducing water damage risk.
Deluge system
A system where all sprinklers are open and water discharges simultaneously upon activation of a detection system; used for high-hazard occupancies.
Main drain test
A test that flows water from the main drain to verify the water supply and control valve status; results are compared to previous tests to detect changes.
Waterflow alarm test
A test that verifies the waterflow alarm activates within a specified time when a sprinkler or test valve is opened; required periodically per NFPA 25.
Fire pump churn pressure
The pressure produced by a fire pump at zero flow; it must not exceed 140% of the rated pressure to prevent overpressure of the system.
Fire pump 150% flow
At 150% of rated flow, a fire pump must produce at least 65% of its rated pressure; this ensures adequate performance during high-demand conditions.
Net pump pressure
The difference between discharge pressure and suction pressure across a fire pump; used to calculate the actual pressure added by the pump.
Brake horsepower (BHP)
The power required by a fire pump, calculated as (gpm × psi) / (1,714 × pump efficiency); used to size the driver and ensure adequate power.
Suction pressure requirement
The minimum residual pressure at the pump suction flange, typically 20 psi, that must be maintained under all flow conditions to avoid cavitation and ensure reliable operation.
Fire pump controller
A device that starts and stops the fire pump automatically or manually; it must be listed for fire pump service and sized per NFPA 20.
Automatic transfer switch
A switch that transfers the fire pump power source to an emergency generator within 10 seconds of a power loss, ensuring continuous pump operation.
Weekly fire pump test
A no-flow (churn) run of the fire pump for at least 10 minutes each week to verify automatic starting, alarms, and general condition.
Annual fire pump flow test
A test that flows water at multiple points (e.g., 100% and 150% of rated flow) and compares results to the manufacturer's curve to verify pump performance.
Test header
A piping arrangement with valves and hose connections used to flow water during fire pump testing; it must be capable of flowing at least 150% of rated capacity.
Water supply curve
A graph showing available pressure versus flow from a water source; the system demand point must fall below this curve for an adequate design.
Static pressure
The pressure in a water supply system when no water is flowing; it is used with residual pressure to determine the available water supply for fire protection.
Residual pressure
The pressure remaining in a water supply system when water is flowing at a given rate; it indicates the available pressure for firefighting operations.