AL Fire Sprinkler key terms
AL Fire Sprinkler · Get comfortable with the vocabulary.
- Automatic Sprinkler
- Related: Thermal Element, Sprinkler Spacing
A heat-activated device that discharges water over a specific area when its thermal element operates, opening individually while the rest of the system stays closed and pressurized.
- Thermal Element
- Related: Temperature Rating, Automatic Sprinkler
The heat-sensitive component of a sprinkler, such as a fusible solder link or a glass bulb, that ruptures at its rated temperature and releases the water seal.
- Temperature Rating
- Related: Thermal Element, Quick-Response Sprinkler
The nominal activation temperature marked on a sprinkler's thermal element, chosen to exceed expected ambient heat while responding quickly to a developing fire.
- K-Factor
- Related: Discharge Density, Residual Pressure
A number expressing the discharge coefficient of a sprinkler or nozzle, relating flow in gallons per minute to the square root of supply pressure in psi.
- Design Density
- Related: Design Area, Hazard Classification
The minimum water flow rate, in gallons per minute, that must be applied over each square foot of the design area for a given hazard classification.
- Design Area
- Related: Design Density, Hydraulic Calculation
The most hydraulically demanding remote group of sprinklers, measured in square feet, assumed to be flowing simultaneously when calculating system demand.
- Hydraulic Calculation
- Related: Design Area, Residual Pressure
A pressure-and-flow analysis proving that the water supply can deliver the required density to the design area while meeting minimum residual pressure at the most remote sprinkler.
- Hazard Classification
- Related: Design Density, Ordinary Hazard
A category assigned to an occupancy based on the amount and combustibility of its contents and expected heat release, which sets density, spacing, and protection requirements.
- Ordinary Hazard
- Related: Hazard Classification, Light Hazard
A classification for occupancies where combustibility is low to moderate and fuel loads are moderate, such as offices, restaurants, and mercantile areas, requiring moderate design densities.
- Light Hazard
- Related: Hazard Classification, Ordinary Hazard
A classification for occupancies with low combustibility and small quantities of combustible contents, such as churches, schools, and hospitals, allowing the lowest design densities.
- Extra Hazard
- Related: Hazard Classification, Design Density
A classification for occupancies with high amounts of combustibles, flammable liquids, or dusts that produce rapid, intense fires, requiring the highest design densities and flows.
- Sprinkler Spacing
- Related: Coverage Area, Automatic Sprinkler
The maximum permitted distance between adjacent sprinklers and between sprinklers and walls, set by hazard classification and ceiling construction to ensure adequate coverage overlap.
- Coverage Area
- Related: Sprinkler Spacing, Design Density
The floor area assigned to a single sprinkler, calculated from the spacing between branch lines and between sprinklers on a line, and limited by hazard classification.
- Quick-Response Sprinkler
- Related: Temperature Rating, Design Area
A sprinkler with a fast-acting thermal element and high response time index, designed to operate sooner in a fire and often permitting reduced design areas in wet systems.
- Wet Pipe System
- Related: Dry Pipe System, Automatic Sprinkler
A sprinkler system in which pipes are always filled with pressurized water, so a sprinkler opens and discharges immediately upon activation, with no delay for water travel.
- Dry Pipe System
- Related: Wet Pipe System, Dry Pipe Valve
A sprinkler system where pipes hold pressurized air or nitrogen and water is admitted only when a sprinkler opens and drops the pressure, tripping the dry pipe valve.
- Dry Pipe Valve
- Related: Dry Pipe System, Trip Point
A latching valve that separates the air-filled sprinkler piping from the water supply and opens automatically when air pressure drops, allowing water to enter the system.
- Preaction System
- Related: Dry Pipe System, Deluge System
A system where piping is normally dry and water is admitted only after a fire detection signal, often with a second interlock, protecting areas where accidental discharge is costly.
- Deluge System
- Related: Preaction System, Deluge Valve
A system with open sprinklers or nozzles where a single detection event opens a control valve and discharges water from every head simultaneously over the protected area.
- Deluge Valve
- Related: Deluge System, Preaction System
A valve held closed by pressure or a mechanical latch that releases on a detection signal, admitting water to open nozzles in a deluge or preaction system.
- Riser
- Related: Riser Nipple, Alarm Check Valve
The vertical section of pipe that connects the water supply main to the overhead sprinkler piping and typically carries the main control valve, check valve, and alarm devices.
- Alarm Check Valve
- Related: Riser, Water Motor Gong
A check valve on a wet system riser that opens to allow water flow but closes to hold pressure, and that routes water to a water motor gong or pressure switch when a sprinkler flows.
- Water Motor Gong
- Related: Alarm Check Valve, Flow Switch
A mechanical alarm device driven by water flowing through the alarm line of a sprinkler system, producing a loud local sound when a sprinkler or valve operates.
- Flow Switch
- Related: Alarm Check Valve, Supervisory Signal
An electrical device installed in sprinkler piping that detects water movement and sends an alarm signal to the fire alarm panel or monitoring service.
- Inspector's Test Valve
- Related: Flow Switch, Water Motor Gong
A valve at the end of the alarm test line that simulates a sprinkler flow, allowing the alarm devices and water flow to be tested without opening an actual sprinkler.
- Main Drain
- Related: Riser, Residual Pressure
A valve and drain connection on the riser used to remove water from the system and to conduct a flow test that reveals the condition of the supply and the valve.
- Fire Pump
- Related: Churn, Rated Flow
A pump, typically centrifugal, that boosts water pressure from a supply to meet sprinkler system demand when the available pressure is insufficient.
- Rated Flow
- Related: Fire Pump, Churn
The flow, in gallons per minute, at which a fire pump is designed to operate and at which its rated pressure is stated, usually the pump's best efficiency point.
- Churn
- Related: Fire Pump, Rated Flow
The condition of a fire pump operating at zero flow with its discharge closed, producing its maximum pressure and requiring a bypass or relief arrangement to prevent overheating.
- Net Pump Pressure
- Related: Fire Pump, Suction Pressure
The pressure actually added by a fire pump, equal to discharge pressure minus suction pressure, used when plotting the pump curve against system demand.
- Suction Pressure
- Related: Net Pump Pressure, Residual Pressure
The pressure available at the pump inlet from the water supply, which affects the pump's net output and must be subtracted from discharge pressure to find net pump pressure.
- Static Pressure
- Related: Residual Pressure, Flow Test
The pressure measured in a water supply when no water is flowing, reflecting elevation and the pressure in the source main or tank.
- Residual Pressure
- Related: Static Pressure, Flow Test
The pressure remaining in a water supply while water is flowing at a measured rate, used with static pressure and flow to estimate the supply's available capacity.
- Flow Test
- Related: Residual Pressure, Static Pressure
A field test that measures static pressure, residual pressure, and flow rate at hydrants to determine the actual water supply available for sprinkler system design.
- Fire Pump Controller
- Related: Fire Pump, Pressure Maintenance Pump
The electrical panel that starts and stops a fire pump automatically or manually, monitors power, and provides alarms and transfer between normal and emergency power.
- Pressure Maintenance Pump
- Related: Fire Pump Controller, Fire Pump
A small jockey pump that keeps sprinkler system pressure above the fire pump start point to prevent the main fire pump from cycling during minor leaks.
- Water Supply
- Related: Flow Test, Static Pressure
The source of water for a sprinkler system, such as a public main, private main, tank, or reservoir, evaluated for its available flow, pressure, and reliability.
- Supervisory Signal
- Related: Flow Switch, Dry Pipe Valve
An alarm signal indicating an abnormal condition in a system, such as a closed control valve, low air pressure, or low water level, that could impair fire protection.