Automatic Sprinkler

A heat-activated device that discharges water over a specific area when its thermal element operates, opening individually while the rest of the system stays closed and pressurized.

Related: Thermal Element, Sprinkler Spacing
Thermal Element

The heat-sensitive component of a sprinkler, such as a fusible solder link or a glass bulb, that ruptures at its rated temperature and releases the water seal.

Related: Temperature Rating, Automatic Sprinkler
Temperature Rating

The nominal activation temperature marked on a sprinkler's thermal element, chosen to exceed expected ambient heat while responding quickly to a developing fire.

Related: Thermal Element, Quick-Response Sprinkler
K-Factor

A number expressing the discharge coefficient of a sprinkler or nozzle, relating flow in gallons per minute to the square root of supply pressure in psi.

Related: Discharge Density, Residual Pressure
Design Density

The minimum water flow rate, in gallons per minute, that must be applied over each square foot of the design area for a given hazard classification.

Related: Design Area, Hazard Classification
Design Area

The most hydraulically demanding remote group of sprinklers, measured in square feet, assumed to be flowing simultaneously when calculating system demand.

Related: Design Density, Hydraulic Calculation
Hydraulic Calculation

A pressure-and-flow analysis proving that the water supply can deliver the required density to the design area while meeting minimum residual pressure at the most remote sprinkler.

Related: Design Area, Residual Pressure
Hazard Classification

A category assigned to an occupancy based on the amount and combustibility of its contents and expected heat release, which sets density, spacing, and protection requirements.

Related: Design Density, Ordinary Hazard
Ordinary Hazard

A classification for occupancies where combustibility is low to moderate and fuel loads are moderate, such as offices, restaurants, and mercantile areas, requiring moderate design densities.

Related: Hazard Classification, Light Hazard
Light Hazard

A classification for occupancies with low combustibility and small quantities of combustible contents, such as churches, schools, and hospitals, allowing the lowest design densities.

Related: Hazard Classification, Ordinary Hazard
Extra Hazard

A classification for occupancies with high amounts of combustibles, flammable liquids, or dusts that produce rapid, intense fires, requiring the highest design densities and flows.

Related: Hazard Classification, Design Density
Sprinkler Spacing

The maximum permitted distance between adjacent sprinklers and between sprinklers and walls, set by hazard classification and ceiling construction to ensure adequate coverage overlap.

Related: Coverage Area, Automatic Sprinkler
Coverage Area

The floor area assigned to a single sprinkler, calculated from the spacing between branch lines and between sprinklers on a line, and limited by hazard classification.

Related: Sprinkler Spacing, Design Density
Quick-Response Sprinkler

A sprinkler with a fast-acting thermal element and high response time index, designed to operate sooner in a fire and often permitting reduced design areas in wet systems.

Related: Temperature Rating, Design Area
Wet Pipe System

A sprinkler system in which pipes are always filled with pressurized water, so a sprinkler opens and discharges immediately upon activation, with no delay for water travel.

Related: Dry Pipe System, Automatic Sprinkler
Dry Pipe System

A sprinkler system where pipes hold pressurized air or nitrogen and water is admitted only when a sprinkler opens and drops the pressure, tripping the dry pipe valve.

Related: Wet Pipe System, Dry Pipe Valve
Dry Pipe Valve

A latching valve that separates the air-filled sprinkler piping from the water supply and opens automatically when air pressure drops, allowing water to enter the system.

Related: Dry Pipe System, Trip Point
Preaction System

A system where piping is normally dry and water is admitted only after a fire detection signal, often with a second interlock, protecting areas where accidental discharge is costly.

Related: Dry Pipe System, Deluge System
Deluge System

A system with open sprinklers or nozzles where a single detection event opens a control valve and discharges water from every head simultaneously over the protected area.

Related: Preaction System, Deluge Valve
Deluge Valve

A valve held closed by pressure or a mechanical latch that releases on a detection signal, admitting water to open nozzles in a deluge or preaction system.

Related: Deluge System, Preaction System
Riser

The vertical section of pipe that connects the water supply main to the overhead sprinkler piping and typically carries the main control valve, check valve, and alarm devices.

Related: Riser Nipple, Alarm Check Valve
Alarm Check Valve

A check valve on a wet system riser that opens to allow water flow but closes to hold pressure, and that routes water to a water motor gong or pressure switch when a sprinkler flows.

Related: Riser, Water Motor Gong
Water Motor Gong

A mechanical alarm device driven by water flowing through the alarm line of a sprinkler system, producing a loud local sound when a sprinkler or valve operates.

Related: Alarm Check Valve, Flow Switch
Flow Switch

An electrical device installed in sprinkler piping that detects water movement and sends an alarm signal to the fire alarm panel or monitoring service.

Related: Alarm Check Valve, Supervisory Signal
Inspector's Test Valve

A valve at the end of the alarm test line that simulates a sprinkler flow, allowing the alarm devices and water flow to be tested without opening an actual sprinkler.

Related: Flow Switch, Water Motor Gong
Main Drain

A valve and drain connection on the riser used to remove water from the system and to conduct a flow test that reveals the condition of the supply and the valve.

Related: Riser, Residual Pressure
Fire Pump

A pump, typically centrifugal, that boosts water pressure from a supply to meet sprinkler system demand when the available pressure is insufficient.

Related: Churn, Rated Flow
Rated Flow

The flow, in gallons per minute, at which a fire pump is designed to operate and at which its rated pressure is stated, usually the pump's best efficiency point.

Related: Fire Pump, Churn
Churn

The condition of a fire pump operating at zero flow with its discharge closed, producing its maximum pressure and requiring a bypass or relief arrangement to prevent overheating.

Related: Fire Pump, Rated Flow
Net Pump Pressure

The pressure actually added by a fire pump, equal to discharge pressure minus suction pressure, used when plotting the pump curve against system demand.

Related: Fire Pump, Suction Pressure
Suction Pressure

The pressure available at the pump inlet from the water supply, which affects the pump's net output and must be subtracted from discharge pressure to find net pump pressure.

Related: Net Pump Pressure, Residual Pressure
Static Pressure

The pressure measured in a water supply when no water is flowing, reflecting elevation and the pressure in the source main or tank.

Related: Residual Pressure, Flow Test
Residual Pressure

The pressure remaining in a water supply while water is flowing at a measured rate, used with static pressure and flow to estimate the supply's available capacity.

Related: Static Pressure, Flow Test
Flow Test

A field test that measures static pressure, residual pressure, and flow rate at hydrants to determine the actual water supply available for sprinkler system design.

Related: Residual Pressure, Static Pressure
Fire Pump Controller

The electrical panel that starts and stops a fire pump automatically or manually, monitors power, and provides alarms and transfer between normal and emergency power.

Related: Fire Pump, Pressure Maintenance Pump
Pressure Maintenance Pump

A small jockey pump that keeps sprinkler system pressure above the fire pump start point to prevent the main fire pump from cycling during minor leaks.

Related: Fire Pump Controller, Fire Pump
Water Supply

The source of water for a sprinkler system, such as a public main, private main, tank, or reservoir, evaluated for its available flow, pressure, and reliability.

Related: Flow Test, Static Pressure
Supervisory Signal

An alarm signal indicating an abnormal condition in a system, such as a closed control valve, low air pressure, or low water level, that could impair fire protection.

Related: Flow Switch, Dry Pipe Valve