Refrigeration Principles and System Components

  • Superheat = suction line temperature minus saturation temperature at suction pressure; measured at the evaporator outlet.

  • Subcooling = saturation temperature at liquid line pressure minus liquid line temperature; typical target 8–12°F on TXV systems.

  • Compression ratio = absolute discharge pressure ÷ absolute suction pressure; ratios above roughly 10:1 raise discharge temperature and stress compressor valves.

  • The four core components: compressor raises pressure, condenser rejects heat, metering device drops pressure, evaporator absorbs heat.

  • At saturation, a pure refrigerant boils and condenses at a single temperature for a given pressure; PT charts give that relationship for R-410A, R-32, and R-454B.

  • R-410A is a near-azeotropic 50/50 blend of R-32 and R-125 and must be charged as a liquid from the cylinder to avoid fractionation.

  • The evaporator absorbs mostly latent heat; the condenser rejects desuperheating sensible heat plus the latent heat of condensation.

  • When a system is off, refrigerant migrates to the coldest point; crankcase heaters and pump-down cycles limit migration and liquid floodback.

  • In zeotropic blends with glide, use the dew point for superheat and the bubble point for subcooling calculations.

Quick reference

Heating Systems (Gas, Oil, Electric, and Heat Pumps)

  • Natural gas manifold pressure is typically 3.5 in. w.c.; LP gas is typically 10–11 in. w.c.; always confirm against the rating plate.

  • Temperature rise = supply air temperature minus return air temperature, and it must fall inside the range printed on the rating plate.

  • 1 watt of electric resistance heat = 3.412 Btu/h, so a 5 kW heater delivers about 17,060 Btu/h.

  • Unconfined-space rule: 50 ft³ of indoor volume per 1,000 Btu/h of total input is required for combustion, draft, and dilution air.

  • AFUE is annual fuel utilization efficiency; 80% units are non-condensing while 90%+ condensing furnaces recover latent heat and require a condensate drain.

  • Heat pump balance point = outdoor temperature where capacity equals building heat loss; below it, auxiliary or supplemental heat stages run.

  • Defrost is initiated by outdoor coil temperature and/or demand; the reversing valve shifts to cooling mode and auxiliary heat tempers supply air.

  • No. 2 heating oil delivers roughly 138,000–140,000 Btu per gallon, so nozzle size in GPH × 140,000 approximates input Btu/h.

  • COP = heat output (Btu) ÷ energy input (Btu), and HSPF ≈ COP × 3.412.

Quick reference

Air Conditioning and Cooling Equipment

  • 1 ton of refrigeration = 12,000 Btu/h; nominal airflow for standard residential cooling is 400 CFM per ton.

  • Sensible heat ratio (SHR) = sensible capacity ÷ total capacity, where total capacity = sensible + latent.

  • A normal air temperature split across an operating evaporator coil is 16–22°F.

  • Design evaporator temperature difference (entering air dry bulb minus evaporating temperature) is about 35°F.

  • Design condenser temperature difference (outdoor ambient to condensing temperature) is about 15–20°F at design conditions.

  • Chilled water coils commonly use 44°F supply and 54°F return water, a 10°F delta-T.

  • Fixed-orifice systems are charged by superheat; TXV systems are charged by subcooling.

  • Low-ambient operation requires head pressure control such as fan cycling, fan speed control, or a flooding valve to keep condensing pressure up.

  • Coil bypass factor decreases as coil surface area increases or as airflow through the coil decreases.

Quick reference

Electrical Systems, Motors, and Controls

  • Ohm's law: E = I × R; single-phase power = E × I × power factor.

  • Three-phase power = 1.732 × line voltage × line current × power factor.

  • Locked rotor amps (LRA) is roughly 5–6 times rated load amps; a compressor held at LRA trips the overload.

  • Run capacitors should read within ±6% of rated microfarads; start capacitors are short-time rated and include bleed resistors.

  • Residential control circuits are 24 VAC; the C terminal supplies the common return needed by smart thermostats.

  • Motor service factor, such as 1.15, permits a small overload above nameplate amps at rated ambient conditions.

  • PSC blower speed is selected by choosing motor taps; ECM blower speed is set by low-voltage programming taps.

  • Contactor pitting or welded contacts cause single-phasing; verify line-to-line voltage on all three legs under load.

  • A 2% voltage imbalance in a three-phase supply can produce roughly 8–10 times that percentage in motor winding heating.

Quick reference

Ductwork, Air Distribution, and Ventilation

  • Sensible airflow: CFM ≈ sensible Btu/h ÷ (1.08 × temperature difference).

  • Duct velocity in feet per minute = CFM ÷ free area in square feet.

  • Equal-friction residential duct design uses about 0.1 in. w.c. static loss per 100 ft of equivalent length.

  • A typical residential air handler has 0.5 in. w.c. of external static pressure available, split between supply and return.

  • Flex duct must be pulled tight; a sag equal to 1.5 times the duct diameter can substantially cut delivered capacity.

  • Return grilles are sized for lower face velocity (about 500 FPM) than supply diffusers to reduce noise.

  • Seal duct joints with mastic or UL 181 tape; leakage in unconditioned space adds directly to the building load.

  • Each 90° elbow is roughly equivalent to 30–40 ft of straight duct in equivalent-length calculations.

  • ASHRAE 62.2 whole-house ventilation rate ≈ 0.03 × conditioned floor area + 7.5 × (bedrooms + 1) CFM.

Quick reference

Piping, Tubing, Fittings, and Brazing

  • Dry nitrogen must flow through the tubing during brazing to displace oxygen and prevent internal oxide and carbon scale.

  • Copper-to-copper joints use phosphorus-bearing brazing filler that self-fluxes; copper to brass or steel requires a separate flux.

  • Suction lines are sized for about 1–2°F equivalent pressure drop; liquid lines for about 1°F.

  • ACR tubing is cleaned, dehydrated, and nitrogen-charged and is the only grade acceptable for refrigerant piping.

  • Evacuate to 500 microns or lower and hold with the pump isolated; a rising reading indicates moisture or a leak.

  • Oil traps at the base of a suction riser, and a trap every 15–20 ft of riser, return oil to the compressor.

  • Soft copper minimum bend radius is roughly 3–5 times the tube diameter; a bender prevents kinking and flattening.

  • Flare fittings use a 45° flare and must be torqued to manufacturer specification to avoid leaks.

  • Triple evacuation with nitrogen sweeps between pulls removes moisture from large or wet systems.

Quick reference

Load Calculation and System Design

  • ACCA Manual J = residential load calculation; Manual S = equipment selection; Manual D = duct design; Manual T = diffuser selection.

  • Winter heat loss = U × A × temperature difference summed over all envelope surfaces, plus infiltration and ventilation load.

  • Cooling load components: conduction through envelope, solar gain through glazing, internal gains, infiltration, and duct gains.

  • Use 1% summer dry-bulb and 99% winter design temperatures for the location rather than record extremes.

  • Lower solar heat gain coefficient (SHGC) glazing reduces solar load; low-E coatings cut both solar and long-wave radiation.

  • Ducts located in unconditioned attics gain or lose heat; apply duct gain/loss multipliers from Manual J.

  • Infiltration latent load (Btu/h) = 0.68 × CFM × humidity ratio difference in grains.

  • Oversizing causes short cycling, poor latent removal, and elevated indoor humidity, so equipment is sized to the calculated load.

  • As altitude rises, air density falls, so the 1.08 sensible heat factor becomes proportionally smaller.

Quick reference

Installation, Testing, and Commissioning

  • Pressure test with dry nitrogen at the manufacturer's specified test pressure, commonly 150–300 psig for R-410A systems.

  • Acceptable evacuation is 500 microns or below with the pump valved off and a 10–15 minute decay hold.

  • Weigh-in charging is used for new systems or when the line set differs from the factory charge, adding the per-foot adjustment.

  • Startup documentation records final superheat or subcooling, temperature split, static pressure, voltage, and amp draw.

  • Air balance: set blower speed for design CFM, then adjust branch dampers; total airflow within ±10% of design.

  • Refrigerant must never be used to leak-test or purge lines; nitrogen serves both purposes.

  • Before startup, verify the condensate trap, drain slope, and secondary pan float switch.

  • Supply voltage must be within 10% of nameplate, phase balance acceptable, lugs tight, and breaker and wire size correct.

  • Confirm the nameplate refrigerant type and charging method before adding refrigerant; mixing refrigerants is prohibited.

Quick reference

Service, Maintenance, and Troubleshooting

  • High superheat with low suction pressure = starved evaporator (undercharge, restriction, or failed metering device).

  • Low superheat with high suction pressure = overcharge or overfeeding metering device.

  • Low superheat with low suction pressure = restricted evaporator airflow or a flooded coil.

  • High head pressure with high subcooling suggests non-condensables or overcharge; high head with normal subcooling suggests a dirty condenser or high ambient.

  • Frost or ice on the suction line and evaporator indicates low charge, restricted airflow, or a blockage.

  • Compressor short cycling causes include high/low pressure switches, internal overload, thermostat faults, and control board failures.

  • Capacitor diagnosis: bulge, oil leak, or an out-of-tolerance microfarad reading means replacement; discharge before testing.

  • A low temperature split with normal airflow indicates low charge or poor compressor performance.

  • High amp draw on a motor points to high head pressure, low supply voltage, bad bearings, or shorted windings.

Quick reference

Safety, Environmental Regulation, and Refrigerant Handling

  • EPA Section 608 certification is required to service, maintain, or dispose of appliances containing regulated refrigerants.

  • Knowingly venting refrigerant to the atmosphere is prohibited; recovery equipment must be used.

  • Recovery cylinders are filled by weight and never above 80% of capacity, leaving room for liquid expansion.

  • R-410A has zero ODP and a GWP near 2,088; R-22 has an ODP of 0.055 and has been banned from US production and import since 2020.

  • A2L refrigerants such as R-32 and R-454B are mildly flammable, so charge limits, ignition-source clearance, and leak detection apply.

  • EPA carbon monoxide limits are 9 ppm for 8 hours and 35 ppm for 1 hour; CO alarms are installed per manufacturer instructions.

  • Liquid refrigerant causes frostbite and eye injury; wear safety glasses and insulated gloves and never trap liquid between valves.

  • Lockout/tagout: lock the disconnect, verify with a meter, and discharge capacitors before servicing.

  • Section 608 leak repair rules apply to appliances containing 50 or more pounds of refrigerant, with allowable leak rates that vary by appliance type.