Cross-Corridor Doors and a Hold-Open That Was Never Tested

ALOA AFL · Put your knowledge to work in context.

All case studies

Cross-Corridor Doors and a Hold-Open That Was Never Tested

A hospital’s annual fire door inspection covers 110 openings. The previous vendor’s records consist of a single page stating “all fire doors inspected and functioning,” with a date. You find 8 cross-corridor door pairs labeled 20-minute with smoke gasketing, each held open by a magnetic hold-open. The hold-opens are tied to the fire alarm, but the last alarm test record is 14 months old. When you test one pair by activating the nearest smoke detector, one leaf releases and the other remains held open; the door also has a wedge on the corridor side. A maintenance technician says the detector test is “the alarm company’s job” and asks you to skip it.

1. What testing is required for the hold-opens, and what do you do when one leaf fails to release?

Read the worked answer

Each hold-open must be tested to confirm that it releases when the smoke detection it is tied to operates. The annual fire door inspection includes auxiliary hardware, and a hold-open that does not release means the door will not close in a fire. Testing only by pulling the door by hand does not prove the release function.

When one leaf fails, record the failure immediately and treat the pair as nonfunctional. Remove the wedge. Do not leave the door in hold-open service; either take the hold-open out of service and keep the door closed and latched, or provide a documented fire watch or interim life-safety measure. Notify the facility and the AHJ. The failure may be in the hold-open, the wiring, the detector, or the alarm panel, so coordinate with the alarm contractor and reinspect after correction. A 14-month-old alarm test record is not evidence that the release works today.

2. How should the records be structured, and what belongs in the finding for the failed release?

Read the worked answer

Replace the single-page statement with an opening-by-opening record. For each opening, record the identifier and location, door and frame labels, hardware, each checklist item, the test method, the result, and the corrective action. For hold-opens, record the release device used, the detector or link tested, the time to release, and whether both leaves closed and latched.

The finding should state that the hold-open on one leaf did not release when the detector was activated, that the door therefore would not close, and that the condition is life-safety critical. Include the date, the person who performed the test, the detector identifier, photographs, and the interim measure taken. Note separately that alarm system testing is outside your scope, but that you performed a functional release test of the door hardware. State the reinspection requirement and retain the record for the AHJ.

3. How do you handle the technician’s request to skip the detector test and the boundary with the alarm contractor?

Read the worked answer

You can acknowledge the boundary without accepting it as a reason to skip the door test. The alarm contractor verifies detection and panel operation; you verify that the door assembly responds. Activating a detector to observe door release is a functional test of the door hardware, and it is within the fire door inspection.

Coordinate the test with the facility and the alarm contractor so the alarm is not left in a compromised state and so the activation is documented. If the detector cannot be safely activated, use an alternative approved method, such as a test key or panel input, and record exactly what was done and what was not verified. Do not accept “the alarm company tested it” as evidence for the door release unless you have the record and the door was observed. Report the scope limitation plainly so the AHJ can see what remains unverified.