- Fire door assembly
- A door, frame, hinges, closing device, latching or exit hardware, and any glazing or gasketing that together carry a fire rating as a listed system.
- Maximum door-to-frame clearance
- One-eighth inch (3.2 mm) at the jambs and head of a swinging fire door; larger gaps allow flame and smoke passage and fail the assembly.
- Fire door undercut limit
- The gap between the bottom of a fire door and the finished floor may not exceed 3/4 inch (19 mm).
- Positive latching
- The door must engage the strike so the latch holds the door closed; fire exit hardware and closers must produce latching without manual assistance.
- Fire exit hardware
- Panic hardware that also provides positive latching; required on fire-rated doors in the means of egress, unlike standard panic hardware.
- Hold-open on fire door
- Permitted only when the device is listed and releases automatically on fire alarm or smoke detection, allowing the door to self-close and latch.
- Temperature-rise door
- A fire door rated to limit heat transmission at 250 F, 450 F or 650 F above ambient after 30 minutes; commonly used at stair enclosures.
- Door closer requirements
- The closer must be listed for fire doors, sized to the door, and strong enough to close and latch it from any open position.
- Fire-rated glazing
- Glass in a fire door must carry a fire rating label (20 to 180 minutes) and be set in listed glazing compound; maximum size per label.
- Fire door frame label
- A metal or wood frame must bear a fire door frame label matching the required rating; unlabeled or altered frames invalidate the assembly.
- NFPA 80
- Standard for Fire Doors and Other Opening Protectives; sets installation, annual inspection, testing, and maintenance requirements for fire-rated openings.
- NFPA 101
- Life Safety Code; specifies where fire door assemblies are required, egress door criteria, panic hardware thresholds, and means-of-egress details.
- UL 10C
- Positive-pressure fire test standard for door assemblies; a passing test supports the hourly label (20 minutes to 3 hours) applied to doors.
- Opening rating relationship
- The required door rating follows the wall rating: a 4-hour wall uses a 3-hour door, and a 3-hour wall uses a 1 1/2-hour door.
- Panic hardware threshold
- Required in Assembly and Educational occupancies with occupant load of 100 or more, and in High Hazard occupancies, at egress doors.
- Accessible opening force
- Interior hinged doors on accessible routes may require no more than 5 lbf to open, measured with the door at rest, per ICC A117.1.
- Label removal prohibition
- Fire labels may not be painted over, removed, or replaced in the field; relabeling is done only by the listing agency.
- NFPA 105
- Standard for Smoke Door Openings; addresses smoke gasketing, smoke door assemblies, and their inspection and testing.
- Annual inspection interval
- NFPA 80 requires fire door assemblies to be inspected and tested at least annually, and additionally after damage, repairs, or field modifications.
- Gap gauge
- A 1/8-inch (3.2 mm) feeler or gap gauge is the field tool for verifying door-to-frame and meeting-edge clearances.
- Functional closing test
- Open the door to its full swing, release it, and confirm unassisted closing and latching; repeat for both leaves of pairs.
- Written inspection record
- The record should identify the opening, date, inspector, findings, corrective actions, and photos, and be kept for AHJ review.
- Inspector qualification
- NFPA 80 requires inspection by qualified persons who know door types, labeling, hardware, and the standard's inspection requirements.
- Deficiency categories
- Typical findings include missing labels, oversize gaps, failure to latch, missing screws, broken closers, damaged frames, and unauthorized field modifications.
- Pre-inspection planning
- Review drawings, door schedules, and hardware sets; identify each opening, coordinate access, and notify the owner and AHJ before testing.
- Re-inspection trigger
- Any repair, hardware replacement, or field modification requires re-inspection to confirm the assembly again closes, latches, and matches its label.
- Conflict of interest
- Disclose any relationship with a firm that will repair deficiencies you inspect; third-party inspectors should not certify their own work.
- Scope of competence
- Inspect only what you are trained to evaluate; state limitations in the report and refer specialized items to qualified professionals.
- Honest reporting
- Record only observed conditions; never certify an opening you could not access, and never alter or falsify inspection records.
- Confidentiality
- Building floor plans, keying, and security details learned during inspection should not be disclosed without owner authorization.
- Authority limits
- An inspector does not approve code compliance or alter life-safety systems; the authority having jurisdiction makes final determinations.
- Restoring doors
- After testing, return every door to normal operation, remove temporary holds, and report any door left out of service.