AMPP CIP Level 2: Inspection Instruments and Test Methods

AMPP CIP Level 2 · Work through your exam, one topic at a time.

All guide sections

Inspection Instruments and Test Methods

Environmental and surface checks

Measure air temperature, surface temperature, dew point, and RH with calibrated instruments. Contact thermometers and infrared thermometers are both used; remember that IR devices read surface temperature and are affected by emissivity and nearby hot or cold sources. Dew point may be measured directly (electronic meters) or derived from a sling psychrometer.

Dry film thickness

SSPC-PA 2 governs magnetic gauge measurements. A spot is the average of several gauge readings; no individual reading may fall below 80% of the specified minimum, and the spot average must meet the minimum. The number of spots scales with area - check the current edition for the exact count. Gauge types differ (Type 1 pull-off magnetic, Type 2 permanent magnet, electronic types), and all are affected by substrate curvature, edge proximity, and surface roughness. Calibrate with foils on a smooth reference surface and verify on the actual substrate where possible. Tooke-style destructive gauges cross-check readings on critical work.

Holiday and adhesion testing

Low-voltage wet sponge testers (typically battery-powered, for thinner films) and high-voltage spark testers (for thicker or conductive-substrate systems) locate discontinuities; select voltage from the manufacturer's or standard's chart so it does not damage sound film. Adhesion is assessed by tape test (ASTM D3359; lattice for thinner films, X-cut for thicker films, rated 5B best to 0B worst) or by pull-off (ASTM D4541), recording both the pressure and the failure mode (adhesive versus cohesive, and the percentage of each).

Traps

Reporting a single DFT reading as the film thickness; testing holidays in a solvent-rich or explosive atmosphere with a spark tester; and ignoring failure mode in pull-off results. Instrument calibration records must be current and traceable - an out-of-calibration gauge invalidates the survey, not just the reading.