AR Fire Alarm · Keep the key ideas within reach.

Quick reference

Fire Alarm Systems

  • An initiating device circuit (IDC) connects detection devices to the panel; a notification appliance circuit (NAC) powers horns, strobes, and speakers.

  • Class B circuits are two-wire, unprotected-path styles (Styles B, C, D); a single open stops devices beyond the break from reporting.

  • Class A circuits (Styles D, E, F) return the path to the panel, so a single open leaves all devices operational.

  • Two-wire (conventional) detectors draw operating power from the IDC and alarm by dropping circuit impedance; four-wire detectors need separate power and use relay contacts.

  • NFPA 72 spacing for smooth-ceiling smoke detectors: 30 ft (9.1 m) maximum from any point, 21 ft (6.4 m) between detectors on a square grid with 10 ft ceiling.

  • Spot-type heat detector spacing is 50 ft (15.2 m) maximum on smooth ceilings; reduce spacing per NFPA 72 Table 17.6.3.5.1 for ceiling height.

  • Total (100%) smoke detector coverage in a corridor is required when the corridor is used as part of the egress path and the system is installed to that standard.

  • Elevator recall, door release, and smoke-control functions are suppression or building-system interfaces, not notification functions.

  • A waterflow switch on a sprinkler riser is an initiating device; a tamper switch monitors valve position and is supervisory, not alarm.

Quick reference

Fire Alarm Code and Standards

  • NFPA 72 is the National Fire Alarm and Signaling Code; NFPA 70 (NEC) Article 760 governs fire alarm wiring methods.

  • NFPA 101 (Life Safety Code) sets occupancy-based detection, notification, and egress requirements that drive system design.

  • NEC 760.41/760.43: fire alarm power circuits must be mechanically protected and cannot share a raceway with non-power-limited circuits unless separated.

  • NFPA 72 requires visible notification appliances in public and common areas, and in areas where audible signals may be ineffective or ambient sound exceeds 105 dBA.

  • Audible signal sound pressure must be at least 15 dBA above ambient, or 5 dBA above ambient if ambient exceeds 105 dBA, measured at 10 ft (3 m).

  • NFPA 72 inspection, testing, and maintenance frequencies: monthly for batteries under load, quarterly for waterflow devices, annually for most initiating and notification devices.

  • Record retention: inspection and test records must be kept until the next inspection or test, and at least one year for most systems.

  • A fire alarm control unit must be listed to UL 864; initiating devices to UL 268/UL 521 and notification appliances to UL 1971/UL 464.

Quick reference

Electrical Theory and Installation

  • Ohm's law: V = I × R; power: P = V × I = I²R = V²/R.

  • Voltage drop on a NAC: Vdrop = 2 × I × R × L / 1000 for copper resistance in ohms per 1000 ft, using the round-trip length.

  • NAC voltage drop limit: appliance voltage must stay within the listed operating range; design to no more than 10% drop from panel terminals.

  • Battery standby sizing: required amp-hours = (standby current × standby hours) + (alarm current × alarm minutes / 60), then apply a 20% derating factor.

  • NEC 760.130: fire alarm circuits must be installed in raceway, metal-clad cable, or other approved methods; exposed wiring must be protected from physical damage.

  • Fire alarm conductors must be color-coded or otherwise identified; red is the customary color for fire alarm cable.

  • All fire alarm equipment must be grounded per NEC Article 250; the panel's grounding electrode conductor must be sized per Table 250.66.

  • Supervisory current on a conventional IDC is typically a few milliamps; alarm current is much higher, and the panel distinguishes states by current level.

Quick reference

Arkansas Fire Protection Licensing Laws and Rules

  • Arkansas fire protection systems are regulated by the Arkansas Fire Protection Licensing Board under Arkansas Code Title 20, Chapter 22.

  • The Board licenses fire alarm contractors, fire sprinkler contractors, and fire extinguisher firms, and issues individual licenses for installers and technicians.

  • A fire alarm contractor license is required to install, alter, repair, or service fire alarm systems in Arkansas; unlicensed work is a violation subject to penalty.

  • License renewal is required annually; continuing education hours must be completed and documented before renewal.

  • A licensed contractor must obtain permits and inspections from the local authority having jurisdiction (AHJ) before installation or alteration.

  • Individual installers and technicians must work under the supervision of a licensed contractor and hold the appropriate individual license or certification.

  • The Board may suspend or revoke a license for code violations, fraudulent work, or failure to comply with Board rules; it also investigates complaints.

  • Arkansas adopts NFPA 72 and NFPA 101 by reference through Board rules; the edition adopted is the one referenced in the current Board rules.