AR HVAC flashcards
AR HVAC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ton of Refrigeration
- One ton of refrigeration equals 12,000 BTU per hour, or 200 BTU per minute, or about 3.517 kilowatts of heat removal.
- Sensible Heat Formula
- For standard air, sensible heat in BTU/h equals 1.08 multiplied by airflow in CFM multiplied by the dry-bulb temperature difference across the coil.
- Latent Heat Formula
- Latent heat load in BTU/h equals 0.68 multiplied by airflow in CFM multiplied by the moisture difference in grains per pound of dry air.
- Superheat Definition
- Superheat is the number of degrees a vapor is above its saturation temperature, calculated as measured suction line temperature minus saturation temperature at suction pressure.
- Subcooling Definition
- Subcooling is the number of degrees a liquid is below its saturation temperature, calculated as the saturation temperature at discharge pressure minus the liquid line temperature.
- Micron Gauge Purpose
- A micron gauge measures deep vacuum during evacuation; a proper evacuation reaches 500 microns and holds below 1,000 microns after the pump is valved off.
- Manifold Gauge Hose Colors
- Blue connects to the low side, red to the high side, and yellow to the center port for a vacuum pump, recovery machine, or refrigerant cylinder.
- Oxygen Pressure Test Ban
- Oxygen or compressed shop air must never pressure-test a refrigeration system, because mixing it with refrigerant oil can cause an explosion; use dry nitrogen instead.
- Refrigeration Cycle Four Components
- Compressor, condenser, metering device, and evaporator; the compressor raises pressure, the condenser rejects heat, the metering device drops pressure, and the evaporator absorbs heat.
- TXV Function
- A thermostatic expansion valve modulates refrigerant flow to hold a constant superheat at the evaporator outlet by sensing suction line temperature and pressure at the bulb.
- R-410A Liquid Charging
- R-410A is a near-azeotropic blend of R-32 and R-125, so it must be removed from the cylinder and charged as a liquid to avoid fractionation.
- A2L Safety Classification
- A2L is the ASHRAE class for refrigerants with low toxicity and mild flammability, such as R-32 and R-454B, which carry specific handling and charge-limit rules.
- Filter Drier Purpose
- A filter drier removes moisture, acid, and particulates from the refrigerant circuit; heat pumps require a bi-flow drier so it works in both flow directions.
- Crankcase Heater Function
- A crankcase heater warms compressor oil during the off cycle to prevent refrigerant migration and dilution, protecting the compressor from lubrication failure at startup.
- Reversing Valve Function
- A reversing valve changes the direction of refrigerant flow in a heat pump, swapping the roles of the indoor and outdoor coils between heating and cooling.
- Refrigerant Safety Groups
- ASHRAE classifies refrigerants by toxicity and flammability: A1 (R-22, R-410A) is low toxicity and nonflammable, A2L is mildly flammable, and B1 is more toxic.
- Ohm's Law
- Voltage equals current multiplied by resistance, or E equals I times R. Combined with P equals E times I, it lets a technician verify expected circuit readings.
- Three-Phase Power Formula
- Power in watts for a balanced three-phase load equals 1.732 multiplied by line voltage multiplied by line current multiplied by the power factor.
- Run Capacitor Testing
- The capacitor is discharged, disconnected, and measured on the meter's microfarad setting; a reading more than about 10 percent from rated indicates replacement.
- PSC Motor
- A permanent split capacitor motor has a run capacitor in series with the start winding and uses no start capacitor or centrifugal switch.
- Locked Rotor Amps
- LRA is the current drawn when the rotor cannot turn; it is many times the running current and is used to size overloads and identify a seized compressor.
- Compressor Terminal Identification
- The highest resistance reading is across common-to-start, the lowest across common-to-run, and the run-to-start reading equals the sum of the other two.
- Voltage Imbalance Limit
- On three-phase systems the voltage imbalance between phases should not exceed 2 percent; greater imbalance causes motor overheating and shortened service life.
- 24-Volt Control Transformer
- A step-down transformer supplies 24 volts to thermostats, contactors, and safety switches, forming the low-voltage control circuit in residential equipment.
- ACCA Manual J
- Manual J is the accepted residential method for calculating room-by-room heating and cooling loads from construction, insulation, window, and climate data.
- Manual D Duct Sizing
- Manual D sizes supply and return ducts using a calculated friction rate, commonly about 0.1 inch of water column per 100 feet of equivalent length.
- Airflow Per Ton Rule
- Nominal cooling airflow is about 400 CFM per ton of capacity; reducing to roughly 350 CFM per ton in humid climates increases moisture removal.
- Total External Static Pressure
- TESP is the sum of supply and return static pressure measured across the air handler, commonly 0.5 inch of water column and checked against the fan table.
- Recovery Cylinder Fill Limit
- A recovery cylinder must never be filled above 80 percent of its capacity by weight, leaving room for liquid expansion and preventing hydrostatic rupture.
- Nitrogen Purge While Brazing
- A slow nitrogen flow displaces air inside the tubing during brazing, preventing internal oxidation that forms carbon scale and contaminates the refrigerant circuit.
- Condensate Trap Slope
- A condensate drain needs a trap to overcome cabinet pressure and must slope at least 1/8 inch per foot, without a lift above the drain pan outlet.
- Weigh-In Charging Method
- Weigh-in charging uses a refrigerant scale and the nameplate charge to add an exact amount, making it the most accurate method, especially with long line sets.