ASE S7 Air Conditioning Systems & Controls (School Bus) · Put your knowledge to work in context.

All case studies

Rear Evaporator Frosts While Front Stays Warm

A 2019 school bus has a dual evaporator system: front dash unit and rear roof unit, both fed from a single compressor through a receiver-drier and a manifold that splits liquid to two TXVs. Complaint: rear vents blow 40°F and the rear evaporator ices over after 20 minutes, while front vents stay at 58°F. The system uses a single low-side pressure transducer read by the body control module; the BCM controls compressor cycling and a rear evaporator fan. Gauge set at the service ports: low 28 psig, high 195 psig at 90°F ambient. The rear TXV sensing bulb is clamped to the suction line but the insulation is missing. The front TXV is not accessible without dash removal. Both evaporator fans run.

1. Explain how a single low-side transducer and two TXVs can produce this front/rear imbalance, and what the missing bulb insulation on the rear TXV does.

Read the worked answer

With one compressor and one low-side transducer, the BCM cycles the compressor based on the coldest point it can 'see' - effectively the suction pressure, which is dominated by the evaporator pulling the lowest pressure. If the rear TXV bulb is uninsulated, it reads ambient/suction-line air rather than true suction temperature, so the valve over-opens, flooding the rear evaporator; the rear coil runs colder than the front and ices. The iced coil insulates itself, so the rear TXV then hunts and the shared suction pressure is pulled low, causing the BCM to cycle the compressor off before the front coil reaches temperature - front stays warm. The single transducer cannot distinguish front from rear demand, so one misbehaving TXV skews control for both. Fix the bulb insulation and verify rear superheat before condemning the front TXV.

2. Describe a step-by-step test plan to isolate whether the front warm condition is caused by the rear TXV fault or by a separate front-side restriction, without removing the dash.

Read the worked answer
  1. Correct the rear TXV bulb insulation and recheck; measure rear suction-line temperature and superheat (target typically 8–12°F). 2) Measure front and rear evaporator outlet temperatures with contact probes or IR, and compare. 3) Check liquid-line temperature at the manifold split to each TXV - a large temperature drop across a fitting or a frosted line indicates a restriction. 4) Temporarily isolate the rear circuit if the manifold has a service valve; if front performance recovers, the rear TXV was the culprit. 5) Verify front TXV operation indirectly by checking front suction-line superheat and watching for frost patterns at the front expansion valve inlet screen. 6) Confirm charge by weight. Only if front superheat is abnormal after the rear is corrected do you pursue dash access.