ACI flashcards
ACI · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Water-cementitious ratio
- Ratio of water mass to total cementitious material mass in a mix; the primary determinant of strength, permeability, and durability, with lower values yielding stronger, less permeable concrete.
- Abrams' strength rule
- Empirical relationship stating that concrete compressive strength increases as the water-cement ratio decreases; small reductions in w/c produce significant strength gains.
- Absolute volume method
- Mixture proportioning approach in which the volume of each ingredient is computed from its mass and specific gravity, and aggregate volume fills the remainder of a unit volume.
- Entrained air purpose
- Tiny, evenly distributed air bubbles intentionally incorporated by admixtures to provide space for freezing water to expand, greatly improving freeze-thaw durability.
- Nominal maximum aggregate size
- The smallest sieve through which the entire aggregate sample passes; limited by member dimensions and reinforcement spacing to ensure workability and proper consolidation.
- Slump test meaning
- A consistency measure of fresh concrete obtained with a standard cone; it indicates workability but does not by itself guarantee placeability or resistance to segregation.
- Fly ash effect
- Supplementary cementitious material that slows early strength gain but improves long-term strength, reduces permeability, and improves sulfate resistance through pozzolanic reaction.
- Batching tolerance water
- Acceptable deviation in batch water quantity, commonly about ±1% of the required mass; accurate water batching is essential because w/cm controls strength.
- Aggregate moisture correction
- Free water on aggregate surfaces must be measured and subtracted from batch water so that the specified water-cementitious ratio is actually achieved in the mix.
- Truck mixer revolutions
- Concrete typically must be discharged before 300 total drum revolutions or 90 minutes after batching, whichever comes first, unless extended time is approved.
- Mixing time requirement
- After all materials are charged, concrete is mixed a minimum period, commonly 60–90 seconds in stationary mixers, to ensure uniform distribution of ingredients.
- Ready-mix delivery ticket
- Record of batch time, mix designation, quantities, water added, and revolution count; serves as the primary documentation of delivery compliance and quality.
- Concrete placement temperature
- Fresh concrete temperature at placement commonly must fall between about 5 and 35 degrees Celsius, with stricter hot-weather limits often near 32 degrees Celsius.
- Free fall limit
- Concrete should not drop freely more than about 1.0 to 1.5 meters; greater drops cause segregation, so drop pipes or chutes are used.
- Vibrator layer penetration
- Internal vibrators should penetrate about 100 to 150 millimeters into the previously placed layer to knit layers together and avoid cold joints.
- Vibration completion sign
- Consolidation is complete when the surface becomes relatively smooth, large air bubbles stop rising, and the concrete begins to level around the vibrator.
- Vibrator spacing rule
- Insertion points should be spaced about 1.5 times the vibrator's radius of action, commonly 450 to 600 millimeters apart, for uniform consolidation.
- Lateral movement prohibition
- Using a vibrator to flow concrete sideways causes segregation; concrete should instead be repositioned with shovels or chutes before consolidation.
- Pump mix characteristics
- Pumpable concrete requires adequate fines, paste content, and cohesive grading; excessive coarse aggregate or harsh mixes cause blockages in the line.
- Bleed water finishing rule
- Finishing while bleed water remains on the surface traps water and weakens the top layer, causing dusting and scaling; wait until bleed water disappears.
- Curing duration
- Concrete should be kept moist continuously for a curing period, commonly 7 days for normal cement and 3 days for high-early-strength cement concrete.
- Curing compound application
- Curing compounds form a membrane that retains moisture and must be applied as a continuous film to a moist surface immediately after finishing.
- Plastic shrinkage cracking
- Cracking caused by rapid surface moisture loss when evaporation exceeds bleeding; prevented by fogging, windbreaks, shading, or evaporation retarders.
- Control joint depth
- Control joints are formed or sawed to about one-quarter of the slab thickness so cracking occurs at a planned location rather than randomly.
- Cold weather protection
- Concrete must be maintained above about 5 degrees Celsius until it reaches sufficient strength, commonly 3.5 MPa, to resist freezing damage.
- Slump tolerance
- Permitted variation in slump test results, commonly plus or minus 25 millimeters for slumps up to 100 millimeters and plus or minus 40 millimeters above that.
- Air content tolerance
- Permitted variation in measured air content of fresh concrete, typically plus or minus 1.5 percentage points for air-entrained concrete.
- Strength test acceptance
- ACI 318 criteria: no individual strength test below fc' minus 3.5 MPa, and averages of three consecutive tests must equal or exceed fc'.
- Cylinder sampling frequency
- Strength specimens are commonly taken at least once per 110 cubic meters of concrete or once per day of placement, whichever occurs more often.
- ACI 318 scope
- Building code requirements for structural concrete, covering design, materials, and construction; it is the primary reference for strength acceptance criteria.
- ACI 305 and 306
- ACI 305 addresses hot-weather concreting practices, while ACI 306 addresses cold-weather concreting; both cover temperature limits and protection requirements.
- Silica dust control
- Cutting, grinding, or drilling concrete requires wet methods or local exhaust ventilation plus respiratory protection to limit crystalline silica exposure.
- Fall protection threshold
- In general construction, fall protection is required at elevations of 1.8 meters (6 feet) or more using guardrails, safety nets, or personal fall arrest.