Qualitative vs. Quantitative Reporting and the Standard Being Applied

ASNT Level III IR · Put your knowledge to work in context.

All case studies

Qualitative vs. Quantitative Reporting and the Standard Being Applied

A client's specification cites 'infrared inspection of electrical distribution equipment per the applicable ASTM standard' and requires 'temperature rise limits per the standard.' You perform a survey of 480 V motor control centers. Loads vary from 20% to 90% of rated. You find three connections: (1) 12 K rise over ambient at 90% load, (2) 22 K rise at 40% load, (3) 8 K rise at 20% load. Ambient is 30 °C. The client's engineer asks you to classify each per the cited standard and to state the pass/fail temperature limit.

1. What is the problem with the client's citation, and how do you handle the classification?

Read the worked answer

The citation is ambiguous and not self-executing. 'The applicable ASTM standard' for IR of electrical equipment is a qualitative/quantitative practice standard (e.g., ASTM E1934 for electrical and mechanical equipment), which describes how to perform and report an IR survey - it does not itself prescribe pass/fail temperature-rise limits. Temperature-rise limits for electrical connections come from other documents (e.g., NFPA 70B maintenance guidance, NETA ATS/MTS tables, or the client's own engineering spec). Citing 'the applicable ASTM standard' for limits is a category error.

Handling:

  1. Ask the client to name the standard and edition that governs acceptance (ASTM E1934 for the survey method; NFPA 70B or NETA for severity; or their internal spec).
  2. If they cannot, state in the report which standard you applied and why, and clearly separate the method standard from the acceptance standard.
  3. Do not invent a pass/fail limit; if none is contractually specified, report relative severity (delta-T versus similar connections under similar load) and flag the missing acceptance criterion as a limitation.

2. How do load and the qualitative/quantitative distinction affect how you rank the three findings?

Read the worked answer

Temperature rise scales roughly with load squared (I²R). A 22 K rise at 40% load implies a much larger rise at full load: scaling by (100/40)² ≈ 6.25 gives an extrapolated ~137 K - far more severe than the 12 K at 90% load (extrapolated ~15 K). The 8 K at 20% load extrapolates to ~200 K by the same crude scaling, which is physically implausible and shows the limits of the scaling - but it still signals a connection that should be re-examined at higher load.

Ranking and reporting:

  • Qualitative: compare each connection to sibling connections in the same equipment under the same load - a connection 20 K hotter than its neighbors is suspect regardless of absolute temperature. This is the most defensible field call.
  • Quantitative: report the measured rise with the load at measurement, and state that the rise is not directly comparable across different loads. Recommend re-survey at a common load (or at rated load) before applying any absolute limit.
  • Provisional ranking: connection (2) is the highest concern (large rise at low load, strong extrapolation), then (1) (moderate rise at high load), then (3) (low rise, low load - verify at load). Flag all three for re-check at matched load and note that no acceptance limit can be applied until the governing standard is named.