ASSE 5120 study materials
ASSE 5120 study resources

ASSE 5120 key terms

ASSE 5120 · Get comfortable with the vocabulary.

Cross-Connection

Any actual or potential physical link between a potable water supply and a source of contamination or pollution, through which backflow could move undesirable substances into drinking water.

Related: Backflow, Air Gap
Backflow

The unwanted reversal of water flow from its intended direction, carrying nonpotable water, gases, or suspended solids into a potable piping system.

Related: Backsiphonage, Backpressure, Cross-Connection
Backsiphonage

Backflow caused by a negative or sub-atmospheric pressure in the supply piping, which draws nonpotable fluid into the system through a cross-connection.

Related: Backpressure, Vacuum Breaker
Backpressure

Backflow resulting from downstream pressure that exceeds the pressure of the potable supply, pushing water backward through a cross-connection.

Related: Backsiphonage, Reduced Pressure Principle Assembly
Pollution

The introduction of any substance into potable water that degrades its quality or appearance but does not create a hazard to health, such as taste, odor, or color changes.

Related: Contamination, Health Hazard
Contamination

The introduction of a substance into potable water that creates a hazard to health, including disease organisms, toxic chemicals, or other harmful material.

Related: Pollution, Health Hazard
Air Gap

A physical separation between the free-flowing discharge end of a supply pipe and the flood-level rim of a receiving vessel, providing the highest degree of backflow protection.

Related: Flood-Level Rim, Cross-Connection
Flood-Level Rim

The edge of the receptacle from which water would overflow if the receptacle were filled to its maximum working capacity, used as the reference point for air gap measurement.

Related: Air Gap
Reduced Pressure Principle Assembly

A testable assembly with two independently acting check valves and a hydraulically operating differential relief valve, used where both backsiphonage and backpressure health hazards exist.

Related: Check Valve, Differential Relief Valve, Backpressure
Double Check Valve Assembly

A testable assembly of two independently acting check valves, used to protect against backflow where only a pollution hazard, not a health hazard, exists.

Related: Check Valve, Reduced Pressure Principle Assembly
Pressure Vacuum Breaker

A testable device with a spring-loaded check valve and an air-inlet valve that opens to atmosphere when supply pressure drops, protecting against backsiphonage only.

Related: Atmospheric Vacuum Breaker, Backsiphonage
Atmospheric Vacuum Breaker

A non-testable device with a float-operated air-inlet valve that admits air when supply pressure falls, used on noncontinuous-pressure applications for backsiphonage protection only.

Related: Pressure Vacuum Breaker, Backsiphonage
Check Valve

A valve that permits flow in one direction only and closes automatically to prevent reversal, forming a core component of many backflow prevention assemblies.

Related: Double Check Valve Assembly, Reduced Pressure Principle Assembly
Differential Relief Valve

The hydraulically operated valve in a reduced pressure principle assembly that discharges water to atmosphere to maintain a pressure differential between the two zones.

Related: Reduced Pressure Principle Assembly, Pressure Differential
Pressure Differential

The difference in pressure between two points in a piping system; in an RP assembly, the relief valve maintains the first zone at least a set amount above the second.

Related: Differential Relief Valve, Static Pressure
Static Pressure

The pressure exerted by water at rest in a system, measured perpendicular to the pipe wall and unaffected by flow velocity.

Related: Residual Pressure, Pressure Differential
Residual Pressure

The pressure remaining at a point in a piping system while water is flowing, reflecting losses caused by friction and elevation.

Related: Static Pressure, Friction Loss
Friction Loss

The reduction in pressure caused by water rubbing against pipe walls, fittings, and valves as it flows through a system.

Related: Residual Pressure, Head
Head

A measure of pressure expressed as the height of a water column it can support, where one pound per square inch equals about 2.31 feet of water.

Related: Static Pressure, Friction Loss
Water Hammer

A pressure surge caused by sudden stopping or reversal of flow, which can damage piping and backflow assemblies and may create temporary backpressure conditions.

Related: Backpressure, Check Valve
Thermal Expansion

The increase in water volume as it is heated in a closed system, which raises pressure and can cause relief valve discharge or stress on backflow assemblies.

Related: Pressure Differential, Water Hammer
Degree of Hazard

The classification of a cross-connection risk as either a health hazard or a pollution hazard, which determines the minimum type of backflow protection required.

Related: Contamination, Pollution, Containment
Containment

Backflow protection installed at the service connection or property line to isolate the entire premises from the public water system.

Related: Isolation, Degree of Hazard
Isolation

Backflow protection installed at an individual fixture, appliance, or point of use to protect a specific cross-connection within a building.

Related: Containment, Air Gap
Test Cock

A small valved opening on a backflow assembly used to attach test equipment, bleed air, and read pressure at specific points during field testing.

Related: Differential Pressure Gauge, Field Test
Differential Pressure Gauge

A test instrument with two hoses that measures the difference in pressure between two points, used to verify check valve and relief valve operation.

Related: Test Cock, Field Test
Field Test

The on-site procedure performed with gauges and test cocks to confirm that a backflow assembly meets its required performance criteria at installation and annually thereafter.

Related: Test Cock, Differential Pressure Gauge, Annual Inspection
Annual Inspection

The recurring testing and inspection of a backflow assembly required by regulation, typically every twelve months, to confirm continued proper operation.

Related: Field Test, Test Report
Test Report

The written record of a field test documenting assembly type, serial number, gauge readings, pass or fail result, tester identity, and date of service.

Related: Field Test, Annual Inspection
Gauge Calibration

The periodic verification and adjustment of test instrument accuracy against a known reference, ensuring field readings are reliable and defensible.

Related: Differential Pressure Gauge, Test Report
Certified Backflow Tester

A person who has completed recognized training and passed an examination, and who holds current credentials authorizing performance of backflow assembly field tests.

Related: Field Test, Test Report
Premises Isolation

The practice of protecting a water system at the boundary of each customer property so that contamination originating inside cannot reach the public main.

Related: Containment, Cross-Connection Control Program
Cross-Connection Control Program

The organized set of policies, surveys, device requirements, testing schedules, and records a water purveyor uses to prevent contamination of its distribution system.

Related: Premises Isolation, Degree of Hazard
Vacuum Relief Valve

A device that opens to admit air into a system when internal pressure falls below atmospheric, preventing backsiphonage in tanks and heaters.

Related: Backsiphonage, Pressure Vacuum Breaker
Spill-Resistant Vacuum Breaker

A testable vacuum breaker designed with a check valve arrangement that limits discharge from the air inlet during normal operation, used for backsiphonage health hazards.

Related: Pressure Vacuum Breaker, Backsiphonage
Incident Report

A written account of an unusual event such as assembly discharge, injury, or property damage, prepared promptly and retained for liability and compliance purposes.

Related: Test Report, Personal Protective Equipment
Personal Protective Equipment

Gear such as gloves, eye protection, and hearing protection worn during testing to reduce exposure to pressurized water, chemicals, and physical hazards.

Related: Incident Report, Field Test