ASSE 5120 key terms
ASSE 5120 · Get comfortable with the vocabulary.
- Cross-Connection
- Related: Backflow, Air Gap
Any actual or potential physical link between a potable water supply and a source of contamination or pollution, through which backflow could move undesirable substances into drinking water.
- Backflow
- Related: Backsiphonage, Backpressure, Cross-Connection
The unwanted reversal of water flow from its intended direction, carrying nonpotable water, gases, or suspended solids into a potable piping system.
- Backsiphonage
- Related: Backpressure, Vacuum Breaker
Backflow caused by a negative or sub-atmospheric pressure in the supply piping, which draws nonpotable fluid into the system through a cross-connection.
- Backpressure
- Related: Backsiphonage, Reduced Pressure Principle Assembly
Backflow resulting from downstream pressure that exceeds the pressure of the potable supply, pushing water backward through a cross-connection.
- Pollution
- Related: Contamination, Health Hazard
The introduction of any substance into potable water that degrades its quality or appearance but does not create a hazard to health, such as taste, odor, or color changes.
- Contamination
- Related: Pollution, Health Hazard
The introduction of a substance into potable water that creates a hazard to health, including disease organisms, toxic chemicals, or other harmful material.
- Air Gap
- Related: Flood-Level Rim, Cross-Connection
A physical separation between the free-flowing discharge end of a supply pipe and the flood-level rim of a receiving vessel, providing the highest degree of backflow protection.
- Flood-Level Rim
- Related: Air Gap
The edge of the receptacle from which water would overflow if the receptacle were filled to its maximum working capacity, used as the reference point for air gap measurement.
- Reduced Pressure Principle Assembly
- Related: Check Valve, Differential Relief Valve, Backpressure
A testable assembly with two independently acting check valves and a hydraulically operating differential relief valve, used where both backsiphonage and backpressure health hazards exist.
- Double Check Valve Assembly
- Related: Check Valve, Reduced Pressure Principle Assembly
A testable assembly of two independently acting check valves, used to protect against backflow where only a pollution hazard, not a health hazard, exists.
- Pressure Vacuum Breaker
- Related: Atmospheric Vacuum Breaker, Backsiphonage
A testable device with a spring-loaded check valve and an air-inlet valve that opens to atmosphere when supply pressure drops, protecting against backsiphonage only.
- Atmospheric Vacuum Breaker
- Related: Pressure Vacuum Breaker, Backsiphonage
A non-testable device with a float-operated air-inlet valve that admits air when supply pressure falls, used on noncontinuous-pressure applications for backsiphonage protection only.
- Check Valve
- Related: Double Check Valve Assembly, Reduced Pressure Principle Assembly
A valve that permits flow in one direction only and closes automatically to prevent reversal, forming a core component of many backflow prevention assemblies.
- Differential Relief Valve
- Related: Reduced Pressure Principle Assembly, Pressure Differential
The hydraulically operated valve in a reduced pressure principle assembly that discharges water to atmosphere to maintain a pressure differential between the two zones.
- Pressure Differential
- Related: Differential Relief Valve, Static Pressure
The difference in pressure between two points in a piping system; in an RP assembly, the relief valve maintains the first zone at least a set amount above the second.
- Static Pressure
- Related: Residual Pressure, Pressure Differential
The pressure exerted by water at rest in a system, measured perpendicular to the pipe wall and unaffected by flow velocity.
- Residual Pressure
- Related: Static Pressure, Friction Loss
The pressure remaining at a point in a piping system while water is flowing, reflecting losses caused by friction and elevation.
- Friction Loss
- Related: Residual Pressure, Head
The reduction in pressure caused by water rubbing against pipe walls, fittings, and valves as it flows through a system.
- Head
- Related: Static Pressure, Friction Loss
A measure of pressure expressed as the height of a water column it can support, where one pound per square inch equals about 2.31 feet of water.
- Water Hammer
- Related: Backpressure, Check Valve
A pressure surge caused by sudden stopping or reversal of flow, which can damage piping and backflow assemblies and may create temporary backpressure conditions.
- Thermal Expansion
- Related: Pressure Differential, Water Hammer
The increase in water volume as it is heated in a closed system, which raises pressure and can cause relief valve discharge or stress on backflow assemblies.
- Degree of Hazard
- Related: Contamination, Pollution, Containment
The classification of a cross-connection risk as either a health hazard or a pollution hazard, which determines the minimum type of backflow protection required.
- Containment
- Related: Isolation, Degree of Hazard
Backflow protection installed at the service connection or property line to isolate the entire premises from the public water system.
- Isolation
- Related: Containment, Air Gap
Backflow protection installed at an individual fixture, appliance, or point of use to protect a specific cross-connection within a building.
- Test Cock
- Related: Differential Pressure Gauge, Field Test
A small valved opening on a backflow assembly used to attach test equipment, bleed air, and read pressure at specific points during field testing.
- Differential Pressure Gauge
- Related: Test Cock, Field Test
A test instrument with two hoses that measures the difference in pressure between two points, used to verify check valve and relief valve operation.
- Field Test
- Related: Test Cock, Differential Pressure Gauge, Annual Inspection
The on-site procedure performed with gauges and test cocks to confirm that a backflow assembly meets its required performance criteria at installation and annually thereafter.
- Annual Inspection
- Related: Field Test, Test Report
The recurring testing and inspection of a backflow assembly required by regulation, typically every twelve months, to confirm continued proper operation.
- Test Report
- Related: Field Test, Annual Inspection
The written record of a field test documenting assembly type, serial number, gauge readings, pass or fail result, tester identity, and date of service.
- Gauge Calibration
- Related: Differential Pressure Gauge, Test Report
The periodic verification and adjustment of test instrument accuracy against a known reference, ensuring field readings are reliable and defensible.
- Certified Backflow Tester
- Related: Field Test, Test Report
A person who has completed recognized training and passed an examination, and who holds current credentials authorizing performance of backflow assembly field tests.
- Premises Isolation
- Related: Containment, Cross-Connection Control Program
The practice of protecting a water system at the boundary of each customer property so that contamination originating inside cannot reach the public main.
- Cross-Connection Control Program
- Related: Premises Isolation, Degree of Hazard
The organized set of policies, surveys, device requirements, testing schedules, and records a water purveyor uses to prevent contamination of its distribution system.
- Vacuum Relief Valve
- Related: Backsiphonage, Pressure Vacuum Breaker
A device that opens to admit air into a system when internal pressure falls below atmospheric, preventing backsiphonage in tanks and heaters.
- Spill-Resistant Vacuum Breaker
- Related: Pressure Vacuum Breaker, Backsiphonage
A testable vacuum breaker designed with a check valve arrangement that limits discharge from the air inlet during normal operation, used for backsiphonage health hazards.
- Incident Report
- Related: Test Report, Personal Protective Equipment
A written account of an unusual event such as assembly discharge, injury, or property damage, prepared promptly and retained for liability and compliance purposes.
- Personal Protective Equipment
- Related: Incident Report, Field Test
Gear such as gloves, eye protection, and hearing protection worn during testing to reduce exposure to pressurized water, chemicals, and physical hazards.