Troubleshooting a Double Check Assembly That Fails the Second Check

ASSE 6020 · Put your knowledge to work in context.

All case studies

Troubleshooting a Double Check Assembly That Fails the Second Check

A tester is called to a 4-inch double check valve assembly serving an industrial process line. The first check holds 5 psi with no decay. The second check fails: when the tester closes the high-side valve and opens the low bleed, the gauge drops to zero within seconds. The tester disassembles the assembly and finds the second check's seat is scored and the disc has a nick. The maintenance supervisor asks whether the assembly can be returned to service after cleaning and polishing the seat, or whether parts must be replaced. The line cannot be shut down for more than four hours.

1. Explain why the second check failed and evaluate the proposed repair of cleaning and polishing the seat.

Read the worked answer

The second check failed because the seat and disc no longer form a tight seal. A scored seat and a nicked disc allow water to pass even when the check is closed, which is exactly what the test showed: pressure bled to zero quickly.

Cleaning and polishing a scored seat is generally not an acceptable repair. Polishing removes material and can change the seat geometry, producing a seal that may hold initially but fail again under normal wear. A nicked elastomeric disc cannot be restored by cleaning; it must be replaced. The correct repair is to replace the disc and, if the seat is damaged beyond the manufacturer's tolerance, replace the seat or the check module.

The supervisor should also consider the cause: debris, water hammer, or a worn upstream strainer. Repairing without addressing the cause invites repeat failure.

2. Given a four-hour shutdown limit, outline a repair and retest plan that restores compliance.

Read the worked answer

A workable plan within four hours:

  1. Pre-stage parts. Confirm the correct replacement disc and seat kit are on site before shutdown. Verify the assembly model and serial number against the parts list.
  2. Isolate and drain. Close upstream and downstream isolation valves, drain the assembly, and lock out the isolation valves.
  3. Disassemble and inspect. Inspect both checks, the seat, and the strainer. Replace the second check disc and seat as needed; inspect the first check while open.
  4. Reassemble and pressurize slowly. Fill the assembly slowly to avoid water hammer and to allow the checks to seat.
  5. Retest. Perform the full field test: first check differential hold, second check differential hold, and confirm no leakage past either check. Record all readings.
  6. Return to service and document. Note the parts replaced, the cause, and the test results. If the seat cannot be restored within the window, keep the assembly out of service and provide a temporary approved alternative rather than returning a failed assembly to service.

The four-hour limit is a scheduling constraint, not a reason to skip the retest.