ASSE 6020 study materials
ASSE 6020 study resources

ASSE 6020 study plan

ASSE 6020 · Give each week a clear focus.

8 weeks · About 6 hours per week

Week 1

Field Testing Procedures and Test Equipment & Hydraulics and Backflow Principles

  • Explain how differential pressure across a check valve relates to gauge readings during a field test

  • Identify each component of the test kit and state its function before connecting anything

  • Demonstrate the correct hose routing for a reduced pressure principle assembly test on a practice rig

  • Calculate expected gauge readings for a known supply pressure using the pressure relationship formula

Your checkpoint

A one-page annotated diagram of the test kit and hose routing for an RP assembly, plus five worked pressure-calculation problems with correct answers

Week 2

Field Testing Procedures and Test Equipment & Backflow Prevention Assembly Types and Operation

  • Perform the full reduced pressure principle assembly test sequence on a practice rig without instructor prompting

  • Record test results on a standard test report form legibly and completely

  • Describe the internal operation of each check valve and relief valve during normal flow and during backflow conditions

  • Diagnose which component has failed when given a set of abnormal gauge readings

Your checkpoint

Three completed practice test reports for an RP assembly with all readings within tolerance and a written justification for each pass or fail determination

Week 3

Field Testing Procedures and Test Equipment & Backflow Prevention Assembly Types and Operation

  • Execute the double check valve assembly test procedure and document both check valve hold pressures

  • Execute the pressure vacuum breaker and spill-resistant vacuum breaker test procedures

  • Compare the test sequence differences among RP, DC, PVB, and SVB assemblies and explain why each step differs

  • Set up and zero the test kit gauges and verify calibration status before each session

Your checkpoint

A comparison table of test procedures for four assembly types plus one passing test report for each type performed on a practice rig

Week 4

Backflow Prevention Assembly Types and Operation & Hydraulics and Backflow Principles

  • Classify each backflow prevention assembly type by its degree of hazard protection and approved installation orientation

  • Explain the hydraulic principle of backsiphonage versus backpressure and give one field scenario for each

  • Identify the causes of check valve chatter, relief valve discharge, and gauge fluctuation during testing

  • Select the correct assembly type for five given installation scenarios based on hazard and code requirements

Your checkpoint

A hazard-classification reference sheet covering at least six assembly types with application notes, plus a scored set of ten scenario-based assembly selection questions

Week 5

Cross-Connection Control Program Administration & Codes, Standards, and Regulations

  • Outline the elements of a cross-connection control program including survey, inventory, and device tracking

  • Draft a sample notification letter and testing schedule for a small water system

  • Locate and summarize the code provisions governing tester certification, testing frequency, and reporting deadlines

  • Explain the difference between containment and isolation policies and when each applies

Your checkpoint

A complete draft cross-connection control program outline for a hypothetical 200-service water system, including inventory fields, testing schedule, and reporting workflow

Week 6

Troubleshooting, Repair, and Maintenance & Field Testing Procedures and Test Equipment

  • Disassemble, inspect, and reassemble the check valve and relief valve of an RP assembly using the correct tools

  • Identify worn or fouled components by visual inspection and state the corrective action for each

  • Troubleshoot a failed test by isolating the faulty component through systematic gauge reading analysis

  • Document a repair with parts replaced, before-and-after readings, and a retest result

Your checkpoint

A repair log for two practice assemblies showing the diagnosed fault, parts replaced, and a post-repair passing test report

Week 7

Troubleshooting, Repair, and Maintenance & Cross-Connection Control Program Administration

  • Describe a preventive maintenance schedule for each assembly type and justify the interval

  • Explain recordkeeping requirements for tests, repairs, and device inventory and design a tracking log

  • Troubleshoot three written fault scenarios and rank the most likely causes

  • Explain how to handle a device that fails retest after repair, including notification obligations

Your checkpoint

A written response to three troubleshooting scenarios with ranked causes and corrective steps, plus a preventive maintenance schedule template

Week 8

Field Testing Procedures and Test Equipment & Backflow Prevention Assembly Types and Operation & Cross-Connection Control Program Administration & Hydraulics and Backflow Principles & Troubleshooting, Repair, and Maintenance & Codes, Standards, and Regulations

  • Complete a timed full-length practice exam under test conditions

  • Review every missed question and write the underlying principle it tested

  • Re-perform two assembly tests on a practice rig to confirm retained procedural skill

  • Summarize the six domains into a single condensed review sheet for final recall

Your checkpoint

A scored practice exam with a written error analysis and a one-page condensed review sheet covering all six domains

Milestones

Week 2: Pass a proctored RP assembly field test with all readings within tolerance and a correctly completed report form

Week 4: Score at least 80 percent on a 25-question quiz covering assembly types, hydraulics, and test procedures

Week 6: Diagnose and repair a seeded fault in a practice assembly and obtain a passing retest without assistance