ASSE 6020 key terms
ASSE 6020 · Get comfortable with the vocabulary.
- Cross-Connection
- Related: Backflow, Air Gap
Any actual or potential physical link between a potable water supply and a source of contamination or pollution, through which backflow could move undesirable substances into drinking water.
- Backflow
- Related: Backsiphonage, Backpressure, Cross-Connection
The unwanted reversal of water flow from its intended direction, carrying nonpotable water or other substances into a potable piping system.
- Backsiphonage
- Related: Backpressure, Vacuum Breaker
Backflow caused by negative or sub-atmospheric pressure in the supply piping, which draws contaminants into the system through a cross-connection.
- Backpressure
- Related: Backsiphonage, Reduced Pressure Principle Assembly
Backflow resulting from downstream pressure that exceeds the pressure of the potable supply, pushing water backward through a cross-connection.
- Air Gap
- Related: Cross-Connection, Flood Level Rim
The unobstructed vertical distance between the lowest opening of a water outlet and the flood level rim of the receiving vessel; the highest-level fixed backflow protection.
- Flood Level Rim
- Related: Air Gap, Critical Level
The edge of the receptacle from which water overflows, used as the reference point for measuring air gaps and establishing minimum installation heights for vacuum breakers.
- Reduced Pressure Principle Assembly
- Related: Check Valve, Differential Relief Valve, Backpressure
A testable backflow preventer with two independently acting check valves and a hydraulically operated differential relief valve, used where both backpressure and backsiphonage hazards exist.
- Double Check Valve Assembly
- Related: Check Valve, Reduced Pressure Principle Assembly
A testable assembly of two independently acting check valves used to protect against backflow hazards that are not health hazards, such as low-hazard pollution connections.
- Pressure Vacuum Breaker
- Related: Atmospheric Vacuum Breaker, Backsiphonage, Critical Level
A testable assembly containing a spring-loaded check valve and an air-inlet valve that opens to atmosphere when supply pressure drops, protecting against backsiphonage only.
- Atmospheric Vacuum Breaker
- Related: Pressure Vacuum Breaker, Backsiphonage
A non-testable device with an air-inlet valve that admits air when supply pressure falls, used on noncontinuous-pressure, backsiphonage-only applications such as hose bibbs.
- Check Valve
- Related: Double Check Valve Assembly, Reduced Pressure Principle Assembly
A valve that permits flow in one direction only and closes automatically to prevent reversal, forming the core component of many backflow prevention assemblies.
- Differential Relief Valve
- Related: Reduced Pressure Principle Assembly, Zone Pressure Differential
The diaphragm-operated relief port in a reduced pressure principle assembly that discharges water when the pressure differential between zones is lost, protecting against both backflow types.
- Critical Level
- Related: Atmospheric Vacuum Breaker, Flood Level Rim
The marked or established elevation on a vacuum breaker or similar device to which the unit must be installed above all downstream piping and outlets to prevent spillage or contamination.
- Zone Pressure Differential
- Related: Differential Relief Valve, Reduced Pressure Principle Assembly
The pressure relationship between the inlet, first intermediate zone, and second intermediate zone of a reduced pressure principle assembly that keeps the relief valve seated during normal flow.
- Test Cock
- Related: Differential Pressure Gauge, Field Test Report
A small valved opening on a backflow assembly that allows a tester to connect gauges, read zone pressures, and bleed air or water during field testing.
- Differential Pressure Gauge
- Related: Test Cock, Zone Pressure Differential
A test instrument with two hoses and a sensitive gauge that measures the pressure difference across check valves and zones of a backflow prevention assembly during field testing.
- Field Test Report
- Related: Test Cock, Annual Testing
The documented record of an assembly's test results, including serial number, gauge readings, pass or fail status, tester identity, and date, submitted to the water authority.
- Annual Testing
- Related: Field Test Report, Certified Tester
The recurring requirement that testable backflow prevention assemblies be verified by a certified tester at least once each year or at the interval set by the local authority.
- Certified Tester
- Related: Annual Testing, Field Test Report
A person who has completed recognized training and passed an examination demonstrating competence to test backflow prevention assemblies and submit valid field test reports.
- Containment Protection
- Related: Isolation Protection, Cross-Connection Control Program
Backflow prevention installed at the service connection or property line to isolate the entire premises from the public water system, protecting the distribution main from site hazards.
- Isolation Protection
- Related: Containment Protection, Cross-Connection Control Program
Point-of-use backflow prevention installed at individual fixtures or pieces of equipment within a facility, supplementing rather than replacing containment protection.
- Cross-Connection Control Program
- Related: Containment Protection, Annual Testing, Hazard Classification
The organized local effort to identify hazards, require appropriate protection, track assemblies, verify testing, and enforce compliance through a public water system's authority.
- Hazard Classification
- Related: Cross-Connection Control Program, Reduced Pressure Principle Assembly
The process of rating a cross-connection as a health hazard or non-health hazard to determine the minimum type of backflow protection required at that location.
- Health Hazard
- Related: Hazard Classification, Air Gap
A cross-connection condition that could introduce contaminants capable of causing illness or disease, requiring the highest degree of protection such as an air gap or reduced pressure assembly.
- Thermal Expansion
- Related: Differential Relief Valve, Closed System
Pressure buildup caused by heated water expanding in a closed system, which can damage assemblies and cause relief valve discharge when a backflow preventer is installed.
- Closed System
- Related: Thermal Expansion
A piping arrangement with no open outlet or relief path, where thermal expansion or pressure surges can stress components and require a thermal expansion control device.
- Water Hammer
- Related: Differential Relief Valve, Closed System
A pressure surge caused by a sudden change in flow velocity, such as rapid valve closure, that can damage backflow assemblies and cause nuisance relief valve discharge.
- Nuisance Discharge
- Related: Differential Relief Valve, Repair Kit
Water escaping from the relief port of a reduced pressure principle assembly during normal operation, usually indicating debris, worn seals, or a damaged check valve.
- Repair Kit
- Related: Nuisance Discharge, Annual Testing
A manufacturer-supplied set of replacement parts, such as seats, springs, diaphragms, and check assemblies, used to restore a backflow preventer to proper operating condition.
- Freeze Protection
- Related: Repair Kit
Measures such as insulation, enclosures, or drain-down procedures that prevent water in a backflow assembly from freezing and cracking its body or internal components.
- Degree of Hazard
- Related: Hazard Classification, Health Hazard
The severity of risk posed by a cross-connection, ranging from pollution that degrades quality to contamination that endangers health, which sets the required protection level.
- Pollution
- Related: Health Hazard, Double Check Valve Assembly
A foreign substance in water that lowers its quality or appearance but does not create a health risk, typically addressed with double check valve protection.
- Contaminant
- Related: Health Hazard, Pollution
Any substance that, if introduced into potable water, could cause illness, disease, or death, distinguishing a health hazard from a mere aesthetic problem.
- Service Connection
- Related: Containment Protection, Cross-Connection Control Program
The pipe linking a public water main to a customer's plumbing, often the required location for containment backflow prevention in a cross-connection control program.
- Premises Isolation
- Related: Containment Protection, Service Connection
Protecting the public supply by installing a testable assembly at the meter or property line so that all on-site hazards are contained within the customer's system.
- Model Plumbing Code
- Related: Cross-Connection Control Program, Annual Testing
A consensus document such as the Uniform Plumbing Code or International Plumbing Code that establishes cross-connection control and backflow prevention requirements adopted by jurisdictions.
- Authority Having Jurisdiction
- Related: Cross-Connection Control Program, Model Plumbing Code
The organization or official empowered to adopt, interpret, and enforce cross-connection control rules, approve assembly installations, and require corrective action.
- Approved Assembly
- Related: Authority Having Jurisdiction, Annual Testing
A backflow prevention device or assembly listed by a recognized testing organization and accepted by the local authority for the specific hazard and installation conditions.