Boiler horsepower
A unit of boiler capacity equal to 33,475 Btu/h (9.81 kW), approximately the evaporation of 34.5 lb of water per hour at 212°F into dry saturated steam at atmospheric pressure.
ASME Section I
The section of the ASME Boiler and Pressure Vessel Code that provides rules for construction of power boilers, defined as boilers operating above 15 psig steam or 160 psig water.
Thermal efficiency
The ratio of heat absorbed by the working fluid (steam or water) to the heat input from fuel, expressed as a percentage; calculated using fuel flow and heating value.
Circulation ratio
The mass flow rate of steam-water mixture circulating through the boiler divided by the steam mass flow rate leaving the drum; indicates the number of times water circulates before evaporating.
Stoichiometric air
The minimum amount of air required to completely burn a given quantity of fuel, providing exactly enough oxygen for all combustible elements without excess or deficiency.
Excess air
The amount of air supplied beyond stoichiometric requirements, expressed as a percentage of theoretical air; ensures complete combustion but reduces efficiency if excessive.
Flame scanner
A device (ultraviolet or infrared) that detects the presence of a flame and sends a signal to the burner management system; loss of flame signal initiates fuel trip.
Furnace purge
A mandatory procedure before ignition that forces air through the furnace for a specified number of volume changes (typically 5) to remove combustible gases and prevent explosion.
Three-element drum level control
A feedwater control strategy using steam flow, feedwater flow, and drum level signals to maintain drum level; compensates for shrink and swell during load changes.
Low-water trip
A safety interlock that shuts off fuel to the boiler when drum water level falls below a safe limit (typically −6 inches from normal), preventing overheating and explosion.
Safety valve accumulation test
A test verifying that the safety valve relieves capacity without allowing boiler pressure to exceed 10% above the set pressure; required by ASME Code.
Controlled shutdown
A systematic procedure to reduce boiler load gradually, trip fuel, purge the furnace, and allow controlled cooldown to prevent thermal stress and equipment damage.
Deaerator
A feedwater heater that removes dissolved oxygen and other non-condensable gases by heating water to saturation temperature and venting the gases, typically operating at 5–15 psig.
Continuous blowdown
A controlled water discharge from the steam drum to maintain boiler water total dissolved solids (TDS) within limits, preventing scale and carryover.
Carryover
The contamination of steam by boiler water droplets containing dissolved solids, caused by high water level, foaming, or high TDS; can foul superheaters and turbines.
Oxygen scavenger
A chemical (e.g., sodium sulfite, hydrazine, DEHA) added to feedwater to remove residual dissolved oxygen and prevent corrosion in the boiler and condensate system.
NPSH
Net Positive Suction Head: the absolute pressure at a pump suction above the vapor pressure of the liquid, expressed in feet; must exceed the pump's required NPSH to prevent cavitation.
Affinity laws
For centrifugal pumps and fans, flow varies directly with speed, head/pressure with the square of speed, and power with the cube of speed, assuming constant impeller diameter.
Air preheater
A heat exchanger that recovers waste heat from flue gas to preheat combustion air, improving boiler efficiency by reducing flue gas heat loss.
Balanced draft
A furnace operating condition where forced draft and induced draft fans maintain a slight negative pressure (e.g., −0.1 to −0.5 in. w.c.) to prevent hot gas leakage.
Burner management system
A control system that supervises safe startup, operation, and shutdown of burners, including purge, ignition, flame monitoring, and fuel trip functions per NFPA 85.
Safety integrity level (SIL)
A relative level of risk reduction provided by a safety instrumented function, ranging from SIL 1 to SIL 4, with higher levels indicating greater reliability and lower probability of failure.
Double block and bleed
A fuel gas piping arrangement with two safety shutoff valves in series and a vent valve between them, used to ensure positive isolation and leak testing before ignition.
PID control
A control algorithm using proportional, integral, and derivative actions to minimize error between a process variable and setpoint; widely used for boiler pressure, level, and temperature control.
Hydrostatic test
A pressure test in which the boiler is filled with water and pressurized to 1.5 times the maximum allowable working pressure to verify structural integrity and detect leaks.
Non-destructive examination (NDE)
Inspection methods such as visual, liquid penetrant, magnetic particle, ultrasonic, and radiographic testing used to detect surface or internal defects without damaging the component.
ASME PTC 4
The ASME Performance Test Code for steam generators, providing procedures for conducting efficiency and capacity tests, including measurement methods and uncertainty analysis.
Safety valve set pressure
The pressure at which a safety valve begins to open, typically set at or below the boiler maximum allowable working pressure (MAWP) and verified by testing.
NFPA 85
The Boiler and Combustion Systems Hazards Code, which establishes requirements for fuel systems, burner management, purging, ignition, flame monitoring, and interlocks to prevent explosions.
OSHA 29 CFR 1910.261
The OSHA regulation covering safety requirements for boiler operation, including training, personal protective equipment, lockout/tagout, and confined space entry procedures.
NSPS
New Source Performance Standards under the Clean Air Act (40 CFR Part 60), which set emission limits for new, modified, or reconstructed boilers for pollutants such as NOx, SO₂, and particulate matter.
Low-water condition emergency
A critical situation where drum water level is not visible in the gauge glass; immediate fuel trip is required, and water must not be added until the boiler has cooled to prevent a violent steam explosion.