AZ Fire Alarm study materials
AZ Fire Alarm study resources

AZ Fire Alarm cheat sheet

AZ Fire Alarm · Keep the key ideas within reach.

Quick reference

Fire Alarm Codes and Standards

  • NFPA 72 is the installation, testing, and maintenance standard; NFPA 70 (NEC) governs wiring methods; NFPA 101 addresses life safety and occupancy requirements.

  • NFPA 72 Chapter 9 covers initiating devices, Chapter 10 notification, Chapter 12 circuits and pathways, Chapter 14 inspection/testing/maintenance.

  • A pathway is Class A when it survives a single open or ground fault; Class B does not survive an open and is the common style for conventional loops.

  • NFPA 72 survivability requires 2-hour circuit protection for notification circuits in high-rise, assembly, and other specified occupancies.

  • Design documents must show device locations, candela ratings, voltage-drop calculations, and battery calculations per NFPA 72 and adopted local codes.

  • The IBC and IFC adopt fire alarm requirements by reference; the AHJ may amend, so verify the locally adopted edition before design.

  • Detector spacing rules in NFPA 72 Chapter 17 are prescriptive maximums; engineering analysis may justify different spacing.

  • NFPA 72 requires a record of completion (Form) and as-built drawings at system acceptance; the record documents design intent and site-specifics.

Quick reference

Fire Detection Devices and Initiating Circuits

  • Smoke detector spacing: 30 ft (9.1 m) maximum between detectors on smooth ceilings; 15 ft (4.6 m) from walls and obstructions.

  • Spot-type heat detectors: 50 ft (15.2 m) maximum spacing for 135 F rated units; 25 ft (7.6 m) from walls.

  • Duct smoke detectors are required where air-handling units exceed 2,000 cfm; they must be installed in the duct and tested with a smoke source.

  • Initiation circuits may be Class A or B; conventional zones use end-of-line resistors and supervised loops, addressable systems use addressable devices and isolators.

  • Detectors are not permitted in bathrooms, near cooking appliances, or in areas where normal conditions produce smoke or particles exceeding listed thresholds.

  • Beam and air-aspirating smoke detectors have specific listing criteria; use manufacturer spacing and listing data rather than generic rules.

  • Manual pull stations must be located within 5 ft (1.5 m) of an exit door and mounted 42 to 48 in (1.1 to 1.2 m) above the floor.

  • Smoke detector spacing must account for ceiling height, slope, and obstructions; NFPA 72 provides reduction factors for high ceilings.

Quick reference

Notification Appliances and Audible/Visible Signaling

  • Audible appliances must produce a sound level at least 15 dBA above ambient or 5 dBA above maximum ambient, whichever is greater, and at least 75 dBA at 10 ft.

  • Visible appliances must be rated in candela; the required candela depends on room size, ceiling height, and mounting per NFPA 72 Chapter 18.

  • Public mode visible notification is required in public and common areas of occupancies specified by NFPA 101 and the adopted building code.

  • Sleeping areas require visible notification in each sleeping room and at a minimum sound level of 75 dBA at the pillow.

  • Audible signals must use a distinctive three-pulse temporal pattern; voice evacuation systems must meet intelligibility requirements.

  • Notification appliance circuits must be supervised and sized for voltage drop; candela ratings and strobe synchronization must be verified.

  • Synchronization of visible appliances is required within a field of view to prevent seizure hazards; appliances must be listed for synchronization.

  • Mounting height for visible appliances is typically 80 to 96 in (2.0 to 2.4 m) above finished floor; manufacturer listings govern.

Quick reference

Control Panels, Power Supplies, and Circuit Design

  • Primary power must be a dedicated branch circuit; secondary power is battery or generator; batteries must be sized for 24 hours standby plus 5 minutes alarm (or 4 minutes per NFPA 72).

  • Battery calculation: total standby current times standby hours plus alarm current times alarm minutes, divided by battery efficiency and derating.

  • Control panels must be listed for fire alarm service and installed per manufacturer instructions and NFPA 72.

  • Circuit design must account for voltage drop; a typical maximum drop is 10 percent for notification circuits, but verify manufacturer limits.

  • Addressable systems require addressable devices and may use isolator modules to protect loop integrity; conventional panels use zones.

  • Power supplies must be supervised for failure and must provide required notification current; auxiliary power supplies must be listed and monitored.

  • Ground fault detection is required on initiating and notification circuits in many systems; verify listing and code requirements.

  • Remote annunciators and auxiliary devices must be listed and connected per manufacturer instructions; do not exceed panel ratings.

Quick reference

Wiring Methods, Installation, and Pathways

  • Fire alarm wiring must be installed per NEC Article 760; power-limited circuits use Class 2 or 3 wiring; non-power-limited uses Article 300 methods.

  • Fire alarm cables must be listed (FPL, FPLR, FPLP) and installed in accordance with their listing; plenum cable is required in plenums.

  • Pathways must be protected from physical damage; raceways, conduit, and supports must be installed per NEC and NFPA 72.

  • Class A pathways require a redundant path; Class B pathways may be single-path but must be supervised.

  • Survivability requirements may require 2-hour fire-rated cable or raceway for notification and control circuits in specified occupancies.

  • Cable splices must be made in listed junction boxes or enclosures; no splices in inaccessible locations unless listed for the purpose.

  • Separation from power conductors is required by NEC; maintain required spacing and use barriers where necessary.

  • All penetrations of fire-rated assemblies must be sealed with listed firestop systems.

Quick reference

Inspection, Testing, and Maintenance

  • NFPA 72 Chapter 14 sets inspection, testing, and maintenance frequencies; smoke detectors are tested annually, heat detectors annually, and notification appliances annually.

  • Inspection includes visual checks of devices, wiring, and panel status; testing verifies functional operation and response.

  • Test records must be maintained and made available to the AHJ; documentation includes device list, test results, and deficiencies.

  • Battery tests include a load test and a check of charging current; batteries must be replaced per manufacturer recommendations.

  • Sensitivity testing of smoke detectors is required per NFPA 72; detectors outside listed sensitivity must be cleaned or replaced.

  • Duct smoke detectors require annual testing and periodic cleaning; test with approved smoke or aerosol.

  • Notification appliances must be tested for audibility and visibility; verify candela and sound levels at required locations.

  • Deficiencies must be corrected and documented; the AHJ may require reinspection and retesting.

Quick reference

Arizona Statutes, Rules, and Licensing Requirements

  • Arizona fire alarm work is regulated by the Arizona State Fire Marshal and local AHJs; contractors must hold appropriate licenses.

  • Arizona Revised Statutes Title 32 governs contractor licensing; fire alarm contractors must be licensed by the Arizona Registrar of Contractors (ROC).

  • Fire alarm technicians may be required to hold NICET certification or equivalent; verify current Arizona requirements.

  • Permits and plan review are required before installation; the AHJ may require stamped drawings by a licensed engineer.

  • Arizona adopts the IFC and NFPA standards by reference with amendments; verify the locally adopted edition.

  • Contractors must carry insurance and comply with ROC rules on contracts, advertising, and consumer protection.

  • Inspections must be performed by qualified personnel; the AHJ may require certification of test personnel.

  • Violations may result in license discipline, fines, or stop-work orders; maintain records of inspections and tests.