NFPA 72 purpose
NFPA 72 provides requirements for the application, installation, location, performance, inspection, testing, and maintenance of fire detection and alarm systems.
Class A pathway
A pathway that survives a single open or ground fault because it has a redundant path and remains operational, providing a higher level of reliability than Class B.
Record of completion
A document required by NFPA 72 at system acceptance that records the installed system, design intent, and site-specific information for the AHJ and owner.
Smoke detector spacing
NFPA 72 permits a maximum of 30 feet between smoke detectors on smooth ceilings and requires at least 15 feet from walls and obstructions.
Heat detector spacing
Spot-type heat detectors rated 135 F may be spaced up to 50 feet apart and no closer than 25 feet from walls on smooth ceilings.
Duct smoke detector threshold
Duct smoke detectors are required where air-handling units exceed 2,000 cfm and must be installed in the duct and tested with smoke.
Manual pull station location
Manual fire alarm pull stations must be installed within 5 feet of an exit door and mounted 42 to 48 inches above the finished floor.
End-of-line resistor
A resistor installed at the end of a conventional initiating or notification circuit that allows the panel to supervise the circuit for opens and shorts.
Audible signal level
Audible notification must produce at least 15 dBA above ambient or 5 dBA above maximum ambient, whichever is greater, and at least 75 dBA at 10 feet.
Candela rating
The measure of visible appliance light intensity; required candela depends on room size, ceiling height, and mounting location per NFPA 72.
Temporal pattern
A distinctive three-pulse audible signal pattern required for fire alarm notification to distinguish it from other signals and improve recognition.
Strobe synchronization
Visible appliances within a field of view must be synchronized to prevent seizure hazards and must be listed for synchronization.
Battery sizing formula
Battery capacity equals standby current times standby hours plus alarm current times alarm minutes, divided by efficiency and derating factors.
Dedicated branch circuit
Primary power for a fire alarm control panel must be supplied by a dedicated branch circuit that cannot be switched off accidentally.
Voltage drop limit
Notification circuit design must account for voltage drop; a common maximum is 10 percent, but manufacturer limits and listings govern.
Addressable isolator
A module that isolates a faulted segment of an addressable loop so the remainder of the loop continues to operate during a fault.
NEC Article 760
The National Electrical Code article governing fire alarm systems, including power-limited and non-power-limited fire alarm circuit wiring methods.
Plenum cable
Fire alarm cable listed for use in plenums (FPLP) that has low smoke and flame characteristics and is required in air-handling spaces.
Firestop system
A listed assembly used to seal penetrations of fire-rated walls and floors to maintain the fire-resistance rating of the assembly.
Survivability requirement
A requirement that certain notification and control circuits remain operational for a specified period, often two hours, in designated occupancies.
Annual smoke detector test
NFPA 72 requires smoke detectors to be tested annually for functional operation and sensitivity, with records maintained for the AHJ.
Battery load test
A test that verifies battery capacity and charging current; batteries are replaced when they fail to meet manufacturer performance criteria.
Sensitivity testing
A test of smoke detector response that verifies the detector is within its listed sensitivity range; out-of-range units are cleaned or replaced.
Test documentation
Records of inspection and testing that identify devices, results, and deficiencies and must be maintained and available to the AHJ.
Arizona ROC license
Arizona requires fire alarm contractors to hold a license from the Registrar of Contractors; licensing rules cover contracts and consumer protection.
State Fire Marshal role
The Arizona State Fire Marshal and local AHJs enforce fire codes, review plans, and may require permits and inspections for fire alarm work.
Plan review requirement
Many Arizona jurisdictions require plan review and permits before fire alarm installation, sometimes with drawings stamped by a licensed engineer.
Adopted code edition
Arizona adopts the IFC and NFPA standards by reference with local amendments; always verify the edition adopted by the specific AHJ.
NICET certification
A nationally recognized certification for fire alarm technicians; some Arizona jurisdictions or employers require it for testing and inspection personnel.
AHJ authority
The authority having jurisdiction interprets and enforces fire codes, approves installations, and may require additional testing or documentation.
Deficiency correction
Identified deficiencies must be corrected and documented; the AHJ may require reinspection and retesting before the system is accepted.
Initiating device circuit
A supervised circuit connecting detectors and manual stations to the control panel; it may be conventional or addressable and Class A or B.